File : CS-SUP-MUTI-WTHERMAPP-E01.sxw
6.1.2 Parameters specific to the WaveTherm – DALLAS module
N°
Description
Size
(in bytes)
Access
right
Default value
Hexa.
Decimal
0x25
Parameter A relative to the sensor 1
2
R/W
0xFFFF
-
0x26
Parameter B relative to the sensor 1
2
R/W
0xFFFF
-
0x27
Parameter A relative to the sensor 2
2
R/W
0xFFFF
-
0x28
Parameter B relative to the sensor 2
2
R/W
0xFFFF
-
0x23
Measurement period of the threshold detection (in minutes)
1
R/W
0x00
0
0x15
High Threshold Alarm – Sensor 1
2
R/W
0x01A0
26°C
0x16
Low Threshold Alarm – Sensor 1
2
R/W
0x0100
16°C
0x17
High Threshold Excess Time – Sensor 1 (multiple of the measurement
period of threshold detection)
1
R/W
0x04
4
0x18
Low Threshold Excess Time – Sensor 1 (multiple of the measurement
period of threshold detection)
1
R/W
0x04
4
0x2B
High Threshold Alarm – Sensor 2
2
R/W
0x01A0
26°C
0x2C
Low Threshold Alarm – Sensor 2
2
R/W
0x0100
16°C
0x2D
High Threshold Excess Time – Sensor 2 (multiple of the measurement
period of threshold detection)
1
R/W
0x04
4
0x2E
Low Threshold Excess Time – Sensor 2 (multiple of the measurement
period of threshold detection)
1
R/W
0x04
4
6.1.3 Parameters specific to the WaveTherm – PT100 module
N°
Description
Size
(in bytes)
Access
right
Default value
Hexa.
Decimal
0x0C
Precision level of the measurement
1
R/W
0x00
0
0x21
Extended Application Status
1
R/W
0x00
0
0x23
Measurement period of the threshold detection (in minutes)
1
R/W
0x00
0
0x15
High Threshold Alarm – Sensor 1
4
R/W
0x0000C041
24°C
0x16
Low Threshold Alarm – Sensor 1
4
R/W
0x0000A041
20°C
0x17
High Threshold Excess Time – Sensor 1 (multiple of the measurement
period of threshold detection)
1
R/W
0x04
4
0x18
Low Threshold Excess Time – Sensor 1 (multiple of the measurement
period of threshold detection)
1
R/W
0x04
4
0x2B
High Threshold Alarm – Sensor 2
4
R/W
0x0000C041
24°C
0x2C
Low Threshold Alarm – Sensor 2
4
R/W
0x0000A041
20°C
0x2D
High Threshold Excess Time – Sensor 2 (multiple of the measurement
period of threshold detection)
1
R/W
0x04
4
0x2E
Low Threshold Excess Time – Sensor 2 (multiple of the measurement
period of threshold detection)
1
R/W
0x04
4
0x30
Value of the internal reference resistance very low
(32-bit float in LSB First)
4
R
0x00000000
0 Ω
0x31
Value of the internal reference resistance very high
(32-bit float in LSB First)
4
R
0x00000243
130 Ω
0x32
Coefficients of probe 1
32
R/W
-
-
0x33
Coefficients of probe 2
32
R/W
-
-
0x91
Date of probe fault detection on sensor 1
6
R/W
0
0
0x92
Date of probe fault detection on sensor 2
6
R/W
0
0
WaveTherm modules – application handbook