6. OPC UA Server
The TigoMaster 2TH device contains an OPC UA server. An OPC UA client can establish a connection
to the device and access the following parameters:
•
Device Identification
•
Sensor/Actuator Identification
The OPC UA client establishes a connection via the following URL:
http://www.unifiedautomation.com
Note:
For the IP address, use the IP address of the device.
The OPC UA client can access device parameters anonymously
(“read only”) or with a username and
password (“read and write”). The username and password are set by means of the TigoEngine
software tool and Integrated Web Server.
Figure 18
– Device Information Model (Section)
6.1. Connecting with device
Requirements
•
You have an OPC UA client application installed on your local PC
•
For write access to the device: You know the user name and password, and you have the permission to
write.
•
You know the IP address of the device.
Without user name and password, you can access the device "anonymously" and read data.
Step-by-step instructions
Establish a connection to the device:
•
Start UaExpert.
•
Use
File > New
to create a new project.
•
Use
Server > Add
to add a new server.
-
The tab
Discovery
displays the dialog
Add Server
.