TigoMaster 2TH
– EtherNet/IP
User Manual
Copyright © 2021 CoreTigo Ltd.
Page
40
of
75
5.3.2. IO-Link Wireless Master Settings
The netFIELD Web Server provides Configuration and Scan settings tabs for the IO-Link Wireless Master.
Select the W-Master in the netFIELD Web Server browser to view the tabs.
Configuration Tab:
Set IO-Link Wireless Master configuration settings, including W-Master setting parameters and activation
or deactivation of track0, track1 or track2, as well as specification of the track transmission power.
Scan Tab:
Scan for unconnected IO-Link devices. A scan result then shows the found devices.
See the Hilscher user manual for further details on how to configure and monitor devices.
5.3.3. W-Master Configuration
Parameter
Description
Master ID
W-Master Identifier according to IOLW specification.
Advanced Connectivity
Various advanced configuration parameters.
Pairing Timeout
Timeout for pairing by button/UID in Seconds.
Track Mode
Track operation modes:
INACTIVE
CYCLIC
SERVICE
ROAMING
AUTO
TX Power
Transmission strength.
Blacklist
Blacklist view allows the user to configure the frequency channels which
shall not be used by the W-Master. The W-Master uses non-blacklisted
channels to communicate with the remote W-Devices.
Table 22
– W-Master Advanced Configuration View
Port Cycle Time:
The Port Cycle Time parameter sets up the cycle time of a W-Port of the W-Master. The cycle time is
encoded using "Time base" (bits 6+7) and "Multiplier" (bits 0-5) values, as shown in the following table:
Value
Range
Time Base
(Bits 6+7)
Multiplier
(Bits 0-5)
Resulting Cycle Time
0
0
0
Free-running mode.
1
… 64
00
1
… 63
If the free-running mode is chosen with a time base of 0, the
W- Master stack will automatically configure the Master
cycle time to be the Minimum Master cycle time based on
the PD Segmentation length, Slot Type and Max Retry
configurations.