calcareous  drops  into  the  plate  heat  exchanger.  It  is 
mandatory  to  avoid  to  run  dry  the  circulation  group. 
The  primary  circuit    must  be  connected  to  a  boiler 
temperature 

check 

(thermostat). 

All 

electricity 

connections  have  to  be  executed  by  qualified 
personnel only.  

  Verify  that  the  position  where  Boilers  are  to  open  are 

large enough to allow for free passage toward the outside 
without  any  need  for  demolition.  The  guarantee  does  not 
cover  any  costs  derived  from  a  failure  to  observe  this 
point. 

  Handling  phases  require  movement  of  equipment  with 

weight  exceeding  30  kg  and  require  the  use  of  proper 
hoisting  and  transport  means.  For  this  purpose, 
receptacles  are  to  be  moved  only  when  empty  by  means 
of special platforms or hoisting eyebolts. 

  In  general  with  sanitary  hot  water  production  plants, 

follow  norms  and  local  regulations  regarding  water 
treatment  in  accordance  with  characteristics.  The 
guarantee  does  not  cover  any  damages  derived  from 
failure to comply with the aforementioned prescriptions. 

  Equipment  installation  and  operation  in  respect  of  these 

instructions  must  always  respect  norms  of  national  and 
local laws in the place of installation. In particular, the inlet 
connection  for  cold  sanitary  water  supply  to  the  water 
system  must  take  place  by  means  of  a  hydraulic  safety 
group in accordance with norm EN 1487:2002, including at 
least one shut-off valve, a relief valve, a relief valve control 
device, a safety valve, a hydraulic load shut-off device, all 
accessories necessary for working in safety with boilers. 

 This plant shall also have an adequate expansion system 

both  on  the  heating  side  and  on  the  sanitary  side.  Even 
when  laws  permit  that  said  expansion  system  can  be 
made up only of one properly sized safety valve, it is best 
to  install  a  membrane  closed  non-toxic  expansion  tank 
also to prevent continuous opening of the safety valve and 
to prevent needlessly overloading the boiler. 

  If  the  sanitary  water  system  exceeds  admissible  boiler 

pressure levels, install a pressure regulator at an adequate 
distance  from    the  boiler  to  prevent  overheating  of  the 
pressure regulator itself.   

 The Anoden Tester device allows a periodic control of the 

efficiency of the magnesium-anode and cathode protection 
and in case replace the magnesium-anode at a later stage. 
After  a  first  replacement,  it  is  recommended  to  arrange 
periodical  maintenance  and  replacement  of  the  anodes 
without waiting for their complete degradation. This is due 
to  the  fact  that  only  an  updated  and  efficient  protection 
system will ensure a long duration of the equipment. In the 
case  in  which  the  operating  conditions  (temperature  and 

water  features)  lead  to  a  high  deterioration  of  the 
magnesium  anodes,  it  is  possible  to  install  anodes  with 
impressed electricity that are available on request.  

 It is reminded that all the electronically equipment are  to

be  always  connected  to  the  ground.  Upon  start-up  and 
after some days of operation, check bolt tightening on the 
flange,  easily  accessible  thanks  to  the  removable  flange 
covering. 

6. Connections 
6.1 Hydraulic connections  

The  plant  connection  diagram  shown  here  within  is 
intended  solely  as  a  guideline  and  is  not  binding  in  as 
much as it is the job of the designer of the plant onto which 
the  boiler  will  be  installed  to  evaluate,  in  accordance  with 
current installation norms, the best plant diagram for use in 
compliance  with  limits  set  by  data  stated  by  the 
manufacturer. 

  DO  NOT  START  THE  CIRCULATION  GROUP 

BEFORE  THE  BOILER    IS  FILLED  UP  WITH 
WATER   

6.2 Electric connections  

At  installation  of  the  Piastraterm  boiler,  connect  the 

electricity  supply  of  the  sanitary  circulation 
group  provided  with  the  product.  Usually,  it  is 
recommended to connect the circulation group 

to  the  electricity  supply  network    through  an  independent 
switch  and  keep  such  circulation  group  always  in  use 
(without  the  use  of  any  thermostat)  in  order  to  avoid 
calcareous  deposit  phenomenon  into  the  plate  to  plate 
heat  exchanger. 

Do  not  start  the  circulation  group 

before the boiler is filled up with water

.

Boiler  Piastraterm  can  be  supplied  with  the  electronic 
display  for  calorifiers  Easy  Conctrol  mounted  on  the  tank 
and  not  wired 

(only  for  models  that  are  compatible  for 

it).

 In this case connections related to the electricity supply 

box have to be executed. 
  

ATTENTION!!  Carefully read  the usage  instructions of 
the  electronic  supply  box  Easy  Control  for  all 
information related to connections, use, programming,  
functionality 

features, 

safety 

and 

product 

recommendations!   

7. Disposal 

At the end of the working life cycle of this product, its metal 

components  must  be  given  to  operators 

authorised  in  the  collection  of  metal 

materials  for  recycling,  while  all  non-metal 

components  must  be  given  to  operators 

authorised  for  their  separate  disposal. 

Products  must  be  managed,  if  disposed  of  by  the  final 
client,  as  similar  urban  waste  and  therefore  respecting 
town  laws  in the  town  where they  are  located.  They  must 
never however be managed as household waste.  

BS_038  Rev_1 del 10-2014_PIASTRATERM.doc 