24VAC Wire Diameter and Transmission Distance
Comparison Chart
When the line diameter size is certain, when the 24VAC voltage attrition rate is lower than 1 0%, the
recommendation maximum transmitting range. (Talking of the exchange power supply's equipment, the
biggest permission voltage attrition rate is 1 0%. For example: An equipment rated power is 80VA, the
Installed Min diameter size which is 35 feet away from the transformer (10m) needs is 0.8000mm .
(mm)
Transmission
Distance
feet(m)
Power {VA}
0.8000
1.000
1.250
2.000
10
283
(
86
)
451
(
137
)
716
(
218
)
1811
(
551
)
20
141
(
42
)
225
(
68
)
358
(
109
)
905
(
275
)
30
94
(
28
)
150
(
45
)
238
(
72
)
603
(
183
)
40
70
(
21
)
112
(
34
)
179
(
54
)
452
(
137
)
50
56
(
17
)
90
(
27
)
143
(
43
)
362
(
110
)
60
47
(
14
)
75
(
22
)
119
(
36
)
301
(
91
)
70
40
(
12
)
64
(
19
)
102
(
31
)
258
(
78
)
80
35
(
10
)
56
(
17
)
89
(
27
)
226
(
68
)
90
31
(
9
)
50
(
15
)
79
(
24
)
201
(
61
)
100
28
(
8
)
45
(
13
)
71
(
21
)
181
(
55
)
110
25
(
7
)
41
(
12
)
65
(
19
)
164
(
49
)
120
23
(
7
)
37
(
11
)
59
(
17
)
150
(
45
)
130
21
(
6
)
34
(
10
)
55
(
16
)
139
(
42
)
140
20
(
6
)
32
(
9
)
51
(
15
)
129
(
39
)
150
18
(
5
)
30
(
9
)
47
(
14
)
120
(
36
)
160
17
(
5
)
28
(
8
)
44
(
13
)
113
(
34
)
170
16
(
4
)
26
(
7
)
42
(
12
)
106
(
32
)
180
15
(
4
)
25
(
7
)
39
(
11
)
100
(
30
)
190
14
(
4
)
23
(
7
)
37
(
11
)
95
(
28
)