Menvier40/100 

Technical Specification 

Page 33 

Other 

If you wish to connect the control unit to a 
PC using either the Ethernet or the USB 
port then make sure that the cables have 
the following specifications: 

Ethernet 

Cat5e patch cable, RJ45 
male plugs at each end, 
suitable for 10/100Base-T. 

USB 

Mini-B plug for control unit 
end, USB-A for PC end. 
Max length 3m.  

Radio Expander and Keypads 

Radio 

Operating frequency 
868.6625MHz Narrowband. 

  

EN 300 220-3. 

 

EN 300 330-2 

Transmitter 
range 

The range of the 
transmitters compatible 
with this control unit 
depends on the 
environment in which they 
are installed. As a 
guideline, most 
transmitters will work up 
200m range in free space 
conditions. 

 

Compliance Statements 

The Menvier40 and Menvier100 are 
compliant with EN50130-5 environmental 
class II. 

The Menvier40 and Menvier100 are suitable 
for use in systems designed to comply with 
PD 6662: 2010 at grade 3. 

When installed correctly the Menvier40 and 
Menvier100 are capable of compliance with 
EN50131 at Grade 3. 

To maintain Grade 3 the Menvier40 and 
Menvier100 must be fitted with a 
communicator of level ATS4 or above. 

When fitted with radio devices the 
Menvier40 and Menvier100 are capable of 
compliance with EN50131 at Grade 2. 

The i-sd02 is compliant with EN50136-1 as 
an ATS2 communicator. 

The i-sd02 may be used as a 
supplementary communicator at Grade 3.  

At Grade 2 the i-sd02 provides a compliant 
communicator for the Menvier40 and 
Menvier100 provided that: 

a)  It is installed in accordance with the 

installation instructions. 

b)  The connected PSTN is functioning 

normally. 

When fitted with an i-sd02 the control unit 
provides options A, B and C at Grade 2 as 
noted in Table 10 of EN50131-
1:2006+A1:2009. 

If the installer selects a non-compliant 
configuration then they must remove or 
adjust compliance labelling 

Third party testing carried out by Anpi. 

Compatible Equipment 

705rEUR-00 

Two button HUA (top 
button is disabled) 

703rEUR-00 

4-channel (2 zone) 
transmitter 

706rEUR-00 

Two button HUD/tilt 
switch transmitter 

710rEUR-00 

Two button HUD 

713rEUR-00 

Pet tolerant PIR 

714rEUR-00 

PIR Transmitter (Small 
case) 

720rEUR-00 

Smoke Detector 
Transmitter 

726rEUR-50 

Long range hand held HUD 

726rEUR-60 

Short range hand held HUD 

727rEUR-00 

Four button remote 
control with encrypted 
code (HUD function not 
compatible with BS8243) 

734rEUR-00/01  CC/FSL Door Contact 

Transmitter (white) 

734rEUR-05/06  CC/FSL Door Contact 

Transmitter (brown) 

738rEUR-00/04  Spyder shock sensor 

(white/brown) 

739rEUR-50 

Sentrol glass break 
detector (no tamper) 

760ES 

External Wireless 
sounder 

762rEUR-00 

Two Channel Receiver 

768rEUR-50 

Eight Channel Receiver 

770rEUR-00 

Wireless Accessory 
Module (repeater mode 
only) 

08844EUR-00 

GPRS module (obsolete) 

Summary of Contents for Menvier 100

Page 1: ...MENVIER SECURITY...

Page 2: ...Describes actions that will physically damage the equipment and prevent its proper function WARNING Describes actions that are hazardous to health or cause injury or death Please pay particular atten...

Page 3: ...Addressing Expanders 14 Expander Loudspeakers 14 Step 5 Connect Control Unit to Mains 14 Mains Cabling 14 Step 6 Connect Wired Zones 15 Four Wire Closed Circuit Connections 15 Fully Supervised Loop Co...

Page 4: ...Menvier40 100 Page iv This page is intentionally blank...

Page 5: ...t of a Security Grade 3 system The control unit is also approved to operate as part of a Security Grade 2 system If you install any radio devices this will limit approval to Security Grade 2 in the wa...

Page 6: ...condensed reference table of the Installer menu 2 Before You Begin Preparation Before installation you should carry out a survey of the site You need to know how many and what kind of detectors will...

Page 7: ...t is on a similar level to the transmitters or receivers More than 10m from another radio expander Do NOT site the unit In the entry or exit zones or outside the area covered by the alarm system Close...

Page 8: ...Control Unit 1 PSTN Connector for on board communicator 2 Lid tamper connector 3 RS485 terminator 4 Engineering keypad connector 5 USB socket Mini B 6 Heartbeat LED 7 Zone output and Aux power connec...

Page 9: ...in Page 5 1 Bus cable connector 2 Aux power 3 Wired zone connectors 4 Aux power 5 Outputs relay and transistorised 6 12V Siren Bell supply 7 Siren and strobe 8 Auxiliary tamper 9 Loudspeaker Figure 4...

Page 10: ...he front of the keypad containing the PCB and display away from the keypad rear housing 1 2 3 4 Figure 6 Opening the Keypad 2 4 3 3 1 1 Central keyhole 2 Rear tamper shroud 3 Cable entry 4 Fixing hole...

Page 11: ...er behind PCB 9 Bus address display 10 Zone connectors 11 Sounder 12 Bus termination jumper 13 Engineering keypad connector Figure 9 Wired Expander 1 9 1 3 2 10 4 2 8 7 1 6 1 5 1 1 Cable entry also be...

Page 12: ...minals must be included in the overall calculation CAUTION Ensure that the system does not demand more than the maximum current available from the control unit during an alarm see page 31 Bus Cabling...

Page 13: ...star configuration If there are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 11 If required fit the termination jumper at the devices on t...

Page 14: ...460mA 0 74V 1 47V 2 21V 2 94V 3 68V 4 42V 5 15V 5 89V 6 62V 7 36V 480mA 0 79V 1 54V 2 30V 3 07V 3 84V 4 61V 5 38V 6 14V 6 91V 7 68V 500mA 0 80V 1 60V 2 40V 3 20V 4 00V 4 80V 5 60V 6 40V 7 20V 8 00V 52...

Page 15: ...back tamper bracket touches the wall There must be enough space around this point to fit the supplied tamper shroud see Figure 14 Fitting Plastic Feet and Tamper Sleeve The control unit is supplied fr...

Page 16: ...rom the transformer to the 20Vac connector on the PCB 11 in Figure 3 Installing the Lid Back Tamper Figure 18 Lid Back Tamper Fit combined lid back tamper bracket and switch provided Ensure that the s...

Page 17: ...pad and control unit Figure 20 Connecting a Keypad to the Bus Keypad Addressing The control unit assigns addresses to all devices connected to the bus cable You must start this process off once all bu...

Page 18: ...io expanders are not approved for Security Grade 3 systems Connecting an Expander to the Bus Both wired and radio expanders provide a connector for the bus at the bottom of their PCBs item 4 on Figure...

Page 19: ...rol unit Figure 24 shows the wiring for four wire CCL zones on the wired expander Note that the connections are different on the expander compared to the control unit Figure 23 Control Unit CCL Zone W...

Page 20: ...in Installer Menu System Options Wired Zone Type To select the resistor values for a wired expander use Installer Menu Detectors Devices Wired Expanders Edit Expander If you wish to connect two or mo...

Page 21: ...the terminal is CC If you program the TR terminal as FSL then make sure you connect a 2k2 resistor in series with the wire to the sounder Note If you do not wish to connect a wired external sounder t...

Page 22: ...t hand terminal is the one next to the Z on the terminal label The maximum length of wire is 50m when using 2k2 4k7 or 4k7 4k7 FSL wiring and a single core of standard 6 core alarm cable Fit EITHER a...

Page 23: ...ynamic test calls occur 24 hours after the last call made by the unit See the Menvier40 100 300 Engineering Guide for details on how to program these functions Statutory Information Applications The b...

Page 24: ...engineer if in any doubt about connecting to these terminals Example connecting a line in the UK The internal communicator must be connected to the telephone network by a If the wiring is owned by Br...

Page 25: ...e defaults Figure 37 Plug By Communicator Wiring Note Comms O P4 will be active when the system is unset This is normal To fit a communicator follow the instructions below Caution Follow the instructi...

Page 26: ...ill generate an ATE L F Single alert if only one of the networks is not available or ATE L F All if both networks are not available Step 10 Fit and Connect Battery Fit a 17Ah Lead Acid battery into th...

Page 27: ...e the wiring type for each expander The display shows Note that the alert LEDs round the navigation key glow red This is because the control unit lid is off and the tamper is active 8 Press The displa...

Page 28: ...f the control unit finds a bus device missing or one with an address that has not been added using the Installer Menu then the display shows for example The top line of the display shows the number of...

Page 29: ...a total of four incorrect codes then the system locks you out for 90 seconds 3 Key in the default user code see Note below At Security Grade 2 the default user access code is 5678 At Security Grade 3...

Page 30: ...Press or to display the desired wiring type on the bottom line of the display and then press to select it The system loads all defaults except for Access Codes and the Log The display briefly shows Fo...

Page 31: ...re detailed description Note make sure that you allocate keypads correctly to wards For more information see Assigning Wired Keypads to Wards in the Menvier40 100 300 Engineering Guide Assemble and cl...

Page 32: ...IONS Wired Zone type Panel All Zones User Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation Confi...

Page 33: ...pe CID or SIA 15 Appears only when Static Test call disabled 16 Appears only when Dynamic Test call is disabled 17 Appears only when Report Type Fast Format and Confirmation Mode Basic 18 Shows None i...

Page 34: ...ake a selected bus device give a continuous tone from its sounder Once you have found the bus device you can silence the tone by opening the case and so activating the device s tamper 5 Technical Spec...

Page 35: ...d radio zone expanders are all bus devices You can connect any combination of these devices to the bus 2 The system can be used as EITHER a ward based system OR a part setting system When used as a pa...

Page 36: ...icator power requirement i sd02 or i dig02 20mA quiescent 50mA max Plug on Communicator power requirement i gsm02 150mA quiescent and max Plug by Communicator pins require 3mA each when active 10 FSL...

Page 37: ...EN50136 1 as an ATS2 communicator The i sd02 may be used as a supplementary communicator at Grade 3 At Grade 2 the i sd02 provides a compliant communicator for the Menvier40 and Menvier100 provided th...