Menvier40/100 

Installation 

Page 23 

followed by the words “Please wait...” 
for several seconds while the control 
unit scans the bus. When the control 
unit has finished scanning the bus the 
keypads show: 





2.  Press and hold keys A and 

 

simultaneously on the keypad that you 
wish to use for initial programming. 

NOTE: Hold the keys down for at 
least three seconds.

 

After a short pause the keypad gives a 
confirmation tone. The display briefly 
shows the bus address of the keypad. If 
there are no other keypads connected to 
the bus it should be “b1-d51”(bus 1 
device 51). Keypads take bus device 
addresses 51 upwards. 

The keypad display then shows: 





3.  Press A or B to select either a Ward 

based system or a Part Setting system. 
The display shows: 





4.  Press 

 or 

 to show the Security 

Grades available, for example: 





5.  Press 

 to select the security grade you 

intend to use for the system. 
The display shows: 





6.  Press 

 or 

 to show the range of zone 

wiring types available, for example: 





7.  Press 

 to select the wiring type you 

intend to use for the wired zones. 

Note: This initial choice fixes the wiring 
type for the control unit and any attached 
wired expanders. If you wish to use a 
different wiring type on the expanders then 
use 

Installer Menu – Detectors/Devices – 

Wired Expander

 after the initial power up to 

change the wiring type for each expander. 

The display shows: 





Note that the alert LEDs round the 
navigation key glow red. This is because 
the control unit lid is off and the tamper 
is active.  

8.  Press 

The display shows: 





9.  Press 

The display shows: 





10. Press 

The display shows: 





11. Press 

.  

The display shows: 





At this point you must make the control 
unit allocate an address to each of the 
connected bus devices, as follows: 

12. Go to each bus device. You can visit the 

devices in any order, but if you visit 
them in the order you want their 
address numbers to appear then it will 
make subsequent programming easier. 
The control unit assigns the next free 
bus address to a bus device when you 
make the device request a bus address.  
For keypads: 

 

Hold down keys A and 

 until the 

display shows a bus and device number. 
For example the second keypad would 
be: 





For expanders: 
 

Open the lid (to make sure that the 
tamper switch is open) and hold down 
the addressing button (item 3 on 
Figures 9 and 10 ). When you do so the 
control unit assigns the next free 
address to that expander. The expander 
gives a double “beep” confirmation tone 
and shows its assigned address on the 
two-digit LED display. Replace the lid. 

NOTE: 
1. DO NOT request a bus address from two 
different devices at the same time. 
2. EXP-R30 expanders take three bus 
addresses. 

13. When you have visited all the connected 

bus devices, go back to the keypad and 
press 

. The display shows: 





14. Replace the control unit lid, making 

sure that the lid tamper closes. 

Summary of Contents for Menvier 100

Page 1: ...MENVIER SECURITY...

Page 2: ...Describes actions that will physically damage the equipment and prevent its proper function WARNING Describes actions that are hazardous to health or cause injury or death Please pay particular atten...

Page 3: ...Addressing Expanders 14 Expander Loudspeakers 14 Step 5 Connect Control Unit to Mains 14 Mains Cabling 14 Step 6 Connect Wired Zones 15 Four Wire Closed Circuit Connections 15 Fully Supervised Loop Co...

Page 4: ...Menvier40 100 Page iv This page is intentionally blank...

Page 5: ...t of a Security Grade 3 system The control unit is also approved to operate as part of a Security Grade 2 system If you install any radio devices this will limit approval to Security Grade 2 in the wa...

Page 6: ...condensed reference table of the Installer menu 2 Before You Begin Preparation Before installation you should carry out a survey of the site You need to know how many and what kind of detectors will...

Page 7: ...t is on a similar level to the transmitters or receivers More than 10m from another radio expander Do NOT site the unit In the entry or exit zones or outside the area covered by the alarm system Close...

Page 8: ...Control Unit 1 PSTN Connector for on board communicator 2 Lid tamper connector 3 RS485 terminator 4 Engineering keypad connector 5 USB socket Mini B 6 Heartbeat LED 7 Zone output and Aux power connec...

Page 9: ...in Page 5 1 Bus cable connector 2 Aux power 3 Wired zone connectors 4 Aux power 5 Outputs relay and transistorised 6 12V Siren Bell supply 7 Siren and strobe 8 Auxiliary tamper 9 Loudspeaker Figure 4...

Page 10: ...he front of the keypad containing the PCB and display away from the keypad rear housing 1 2 3 4 Figure 6 Opening the Keypad 2 4 3 3 1 1 Central keyhole 2 Rear tamper shroud 3 Cable entry 4 Fixing hole...

Page 11: ...er behind PCB 9 Bus address display 10 Zone connectors 11 Sounder 12 Bus termination jumper 13 Engineering keypad connector Figure 9 Wired Expander 1 9 1 3 2 10 4 2 8 7 1 6 1 5 1 1 Cable entry also be...

Page 12: ...minals must be included in the overall calculation CAUTION Ensure that the system does not demand more than the maximum current available from the control unit during an alarm see page 31 Bus Cabling...

Page 13: ...star configuration If there are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 11 If required fit the termination jumper at the devices on t...

Page 14: ...460mA 0 74V 1 47V 2 21V 2 94V 3 68V 4 42V 5 15V 5 89V 6 62V 7 36V 480mA 0 79V 1 54V 2 30V 3 07V 3 84V 4 61V 5 38V 6 14V 6 91V 7 68V 500mA 0 80V 1 60V 2 40V 3 20V 4 00V 4 80V 5 60V 6 40V 7 20V 8 00V 52...

Page 15: ...back tamper bracket touches the wall There must be enough space around this point to fit the supplied tamper shroud see Figure 14 Fitting Plastic Feet and Tamper Sleeve The control unit is supplied fr...

Page 16: ...rom the transformer to the 20Vac connector on the PCB 11 in Figure 3 Installing the Lid Back Tamper Figure 18 Lid Back Tamper Fit combined lid back tamper bracket and switch provided Ensure that the s...

Page 17: ...pad and control unit Figure 20 Connecting a Keypad to the Bus Keypad Addressing The control unit assigns addresses to all devices connected to the bus cable You must start this process off once all bu...

Page 18: ...io expanders are not approved for Security Grade 3 systems Connecting an Expander to the Bus Both wired and radio expanders provide a connector for the bus at the bottom of their PCBs item 4 on Figure...

Page 19: ...rol unit Figure 24 shows the wiring for four wire CCL zones on the wired expander Note that the connections are different on the expander compared to the control unit Figure 23 Control Unit CCL Zone W...

Page 20: ...in Installer Menu System Options Wired Zone Type To select the resistor values for a wired expander use Installer Menu Detectors Devices Wired Expanders Edit Expander If you wish to connect two or mo...

Page 21: ...the terminal is CC If you program the TR terminal as FSL then make sure you connect a 2k2 resistor in series with the wire to the sounder Note If you do not wish to connect a wired external sounder t...

Page 22: ...t hand terminal is the one next to the Z on the terminal label The maximum length of wire is 50m when using 2k2 4k7 or 4k7 4k7 FSL wiring and a single core of standard 6 core alarm cable Fit EITHER a...

Page 23: ...ynamic test calls occur 24 hours after the last call made by the unit See the Menvier40 100 300 Engineering Guide for details on how to program these functions Statutory Information Applications The b...

Page 24: ...engineer if in any doubt about connecting to these terminals Example connecting a line in the UK The internal communicator must be connected to the telephone network by a If the wiring is owned by Br...

Page 25: ...e defaults Figure 37 Plug By Communicator Wiring Note Comms O P4 will be active when the system is unset This is normal To fit a communicator follow the instructions below Caution Follow the instructi...

Page 26: ...ill generate an ATE L F Single alert if only one of the networks is not available or ATE L F All if both networks are not available Step 10 Fit and Connect Battery Fit a 17Ah Lead Acid battery into th...

Page 27: ...e the wiring type for each expander The display shows Note that the alert LEDs round the navigation key glow red This is because the control unit lid is off and the tamper is active 8 Press The displa...

Page 28: ...f the control unit finds a bus device missing or one with an address that has not been added using the Installer Menu then the display shows for example The top line of the display shows the number of...

Page 29: ...a total of four incorrect codes then the system locks you out for 90 seconds 3 Key in the default user code see Note below At Security Grade 2 the default user access code is 5678 At Security Grade 3...

Page 30: ...Press or to display the desired wiring type on the bottom line of the display and then press to select it The system loads all defaults except for Access Codes and the Log The display briefly shows Fo...

Page 31: ...re detailed description Note make sure that you allocate keypads correctly to wards For more information see Assigning Wired Keypads to Wards in the Menvier40 100 300 Engineering Guide Assemble and cl...

Page 32: ...IONS Wired Zone type Panel All Zones User Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation Confi...

Page 33: ...pe CID or SIA 15 Appears only when Static Test call disabled 16 Appears only when Dynamic Test call is disabled 17 Appears only when Report Type Fast Format and Confirmation Mode Basic 18 Shows None i...

Page 34: ...ake a selected bus device give a continuous tone from its sounder Once you have found the bus device you can silence the tone by opening the case and so activating the device s tamper 5 Technical Spec...

Page 35: ...d radio zone expanders are all bus devices You can connect any combination of these devices to the bus 2 The system can be used as EITHER a ward based system OR a part setting system When used as a pa...

Page 36: ...icator power requirement i sd02 or i dig02 20mA quiescent 50mA max Plug on Communicator power requirement i gsm02 150mA quiescent and max Plug by Communicator pins require 3mA each when active 10 FSL...

Page 37: ...EN50136 1 as an ATS2 communicator The i sd02 may be used as a supplementary communicator at Grade 3 At Grade 2 the i sd02 provides a compliant communicator for the Menvier40 and Menvier100 provided th...

Page 38: ...speech dialling i dig02 PSTN Communication ARC only i gsm02 GSM communications module EXP W10 10 zone wired expander EXP R10 10 zone radio expander EXP R30 30 zone radio expander FOB 2W 4B Two way key...