Mounting and Operating Manual
Central Battery System EURO ZB.1
62
CEAG Notlichtsysteme GmbH
A total of 32 inputs can be assigned through
the options DLS (maintained light switch chek-
king function, staircase light switching system).
Each module has two input channels (max.).
Care must be taken during programming that
the 32 inputs are assigned consecutively.
Example:
The first module is a DLS. The second module
is a TLS. Taking this example inputs 1 through
8 would be assigned to the DLS module.
The 8 input channels of the TLS module would
be assigned to inputs 9 through 16.
Press menu button (Item 1) on the control
unit for > 5 sec. Use arrow button to select
programming item 3.
Press the + button to select the circuit that
shall be programmed.
In this example it is circuit 1 of circuit module 1
x 6 A on slot 4 of subrack 2 (see figure).
Enter „No“ for switching variants non-perman-
tent light, permanent light, timer 1 and timer 2
and press OK to confirm.
Use the plus button to select the input channel
via which the circuit is to be controlled.
20
Programming Final Circuits to Switched Maintained Light
Programming the System
In another example it shall be demonstrated
how the factory setting of a circuit switching
variant can be reprogrammed from main-tained
to switched maintained light. A total of 32 input
channels can be assigned.
Example:
The circuit module 1 x 6 A (SKU 1 x 6 A.1)
on Slot 4 of subrack 2 shall be reprogram-
med from maintained to switched maintained
light. To enable the circuits to be switched via
external switching functions in mains operating
mode a circuit DLS module (subrack 1 slot 7)
1
must be installed in the system as an option.
The DLS maintained light switch checking
function has a total of 8 input channels. One
light switch can be connected per input chan-
nel. The assignment, ie. which circuit of the
safety lighting system is to be switched via this
input channel, can be freely selected with the
help of the control unit.
The programming steps necessary for this can
be seen from the flow chart.
H:M:S
T.M.J
U= 242,2 V I=+5,2 A
Operation
Mains=222,3 V
BGT:1 SKU1 Out. circ.1
Slot not active
-------------------------------
+ -
OK
Programming:
1
Progr. contr. unit
-------------------------------
Programming:
2
Progr. charger
-------------------------------
Programming:
3
Programming SKU
-------------------------------
Programming:
4
Programming TLS
-------------------------------
Programming:
5
Teach. curr. values
-------------------------------
Programming:
End
-------------------------------
Non-permanent light ?
No
-------------------------------
Yes No
OK
Permanent light ?
No
-------------------------------
Yes No
OK
Timer -1
No
-------------------------------
Yes No
OK
Timer -2
No
-------------------------------
Yes No
OK
TLS-Input (0=Off)
00
-------------------------------
+ -
OK
Circuit monitoring ?
Yes
-------------------------------
Yes No
OK
DLS/SDS-On
1
(0=Off)
01
-------------------------------
+ -
OK
DLS/SDS-On
2
(0=Off)
00
-------------------------------
+ -
OK
BGT: 2 SKU4 out.circ.1
Type: SKU 1x6__
-------------------------------
+ -
OK
Max. current deviation
10%
-------------------------------
+ -
OK
Note: Current setpoint
Teach new value!!!!
-------------------------------
OK