Mounting and Operating Manual
Central Battery System EURO ZB.1
28
CEAG Notlichtsysteme GmbH
TLS switching module
If general and safety luminaires are to be
controlled by the same buttons (without
additional installation expense) a TLS
switching module can be mounted in
the lighting distribution systems. Control
is effected via a circuit changeover unit
(SKU).
Technical Data
Connection
– Terminals: 2.5 mm²
– Dimensions (H x W x D) mm:
84 x 52 x 64
Switching capacity
– 3 x 16 A
Note:
As regards planning and use of
the module please refer to the
technical documentation supplied
with the modules and brochures
and leaflets of CEAG Notlichtsy-
steme GmbH.
Description
This module enables time-controlled
switching (1 to 15 minutes) of the final
circuits during mains and battery opera-
tion.
Via the TLSs input channels up to eight
button circuits can be queried. Via an
inverter arranged in the module the illu-
minated buttons are powered in mains as
well as battery operation. The number of
buttons that can be connected has been
indicated in the table below. A maximum
of one input channel of the TLS can be
assigned to each final circuit via the
freely programmable control unit of the
EURO ZB.1.
Technical Data
Connections
– Terminals 2.5 mm², rigid and flexible
Button inputs
– Max. 8 button inputs with:
– 1 mA glow lamp
50 pcs.
– 0,8 mA glow lamp
62 pcs.
– 0,4 mA glow lamp
125 pcs.
per button input
Item 1: top terminal strip
Item 2: bottom terminal strip
Item 3: Indicating LEDs
LED
„S
törung
/ F
ailure“ lights up if a
fault has been detected in the module
Item 4: Fixing element (fastening
screw) for the module.
1 2 3 4
Modules
5.12
Functions of the TLS Switching Module