![Cooper safety CEAG EURO US.1 Mounting And Operating Instructions Download Page 39](http://html1.mh-extra.com/html/cooper-safety/ceag-euro-us-1/ceag-euro-us-1_mounting-and-operating-instructions_2664639039.webp)
Mounting and Operating Manual
Central Battery System EURO ZB.1
39
CEAG Notlichtsysteme GmbH
Connection of the Mains Power Supply to EURO ZB.1
Mains Connections to Substations EURO US.1
Power is supplied to a EURO ZB.1
system via the general power system or
the batteries of a battery bank (battery
cabinet or rack).
In case of a 1-phase operation only a
load-current line is connected to the sy-
stem and the input terminals (see Fig. 22,
Item 2) are bridged on the isolator.
Note:
Only carry out the connecting work
described here.
Switching on and testing the po-
wer supply systems is described
in Chapter 12 „Commissioning
and Miscellaneous Work“!
Connect the lines for mains power
supply to the EURO ZB.1 control
cabinet as follows:
– Make sure the system and inco-
ming feeders have been discon-
nected and safeguarded (cf.
Chapter 12)!
– Connect the protective conductor
to the PE terminal block (Fig.19,
Item 3).
– Connect the neutral conductor to
the N terminal block (Fig.19, Item
2).
– Connect the load lines to the L
terminals (Fig. 22, Item 2) of the
load-break switch.
11.1
Connection of the
Mains Power Supply
to EURO ZB.1
11.2
Mains Connec-
tions to Substations
EURO US.1
Fig. 19: Position of load-break switch
(1) (terminal and fuse box for mains
power supply) and terminal blocks (2)
and (3) for the connection and distri-
bution of the N- and PE lines
1 2 3
Fig. 20: Load-break switch hinged
open to the front (1) with mains fuses
(2) for lines L1, L2 and L3 and
Item 3: Outgoing distributor (mains)
Item 4: Cabinet distributor (mains)
1 2 3 4
Fig. 21: Lift load-break switch
upwards (1) to make connection termi-
nals (Fig. 22) accessible
1
Substations EURO US.1 are energized
via the power supply of the pertinent
EURO ZB.1 system (see outgoing distri-
butor in Fig. 20, Item 3 and outgoing lines
in Fig. 22, Item 4).
An outgoing distributor (reference No.
400 71 347 160) can be employed for
three 1-phase power supply systems.
Notes:
Only carry out the connecting
work described here. Switching
on and testing the power supply
systems is described in Chapter
12 „Commissioning and Miscella-
neous Work“!
To facilitate work outgoing
distributors may be removed from
the conductor rail in forward di-
rection after the catch on the top
casing wall is released (see arrow
in Fig. 23).
After the outgoing lines have been
hooked up the outgoing distribu-
tor can be replaced in position on
the conductor rail and carefully
snapped into place.
Connect the lines for mains power
supply to a EURO US.1 substation as
follows:
– Make sure the system and inco-
ming feeders have been discon-
nected and safeguarded (cf.
Chapter 12)!
– Lay the incoming lines to/within
the EURO ZB.1 control cabinet
and in its cable ducts (Fig. 18,
Item 3 and Fig.22, Item 3) and to/
within the control cabinet of the
EURO US.1 substation.
– Connect the protective conductor
(PE conductor) to the terminal
block (Fig.19, Item 3).
– Connect the N conductor to the
terminal block (Fig.19, Item 2).
– Connect the L conductors to the
terminals of the outgoing distribu-
tor (Fig. 20, Item 3).
Note:
The mains power supply is
hooked up within the control ca-
binet of the EURO US.1 substati-
ons, as described under 11.2.
Example 2:
ZB-S 10C3 with 17 circuits and 10 lumi-
naires per circuit and a RCD with 30mA
in the incoming mains.
17 x 10 x 0.5mA = 85mA leakage
The addition of the single leakages of the
connected user to the RCD exceeds a
value of 30mA and can cause the RCD.