B)
Wall Bracket Mount - Wall Mount Using SWB6 Wall Mount Bracket
and SFA6 Slipfitter
1.
Determine the mounting location of the SWB6 bracket
using the bolt hole pattern shown in Figure 2.
2.
Mount the SWB6 bracket (with elbow pointing up) using
four (4) ½" bolts or lag screws (not provided) or by welding in
position.
3.
Using the ½" bolts, nuts, and lock washers provided, securely fasten
the floodlight yoke to the flange on the SFA6 slipfitter. Torque the
bolts to 45 lbs.-ft.
4.
Position the SFA6 Slipfitter onto the SWB6 bracket.
5.
Secure by tightening the slipfitter base bolts. Torque base bolts to 19
lbs.-ft.
C) Yoke Mount - Wall Mount Using Floodlight Yoke Only
1.
Using floodlight yoke as a template, mark and drill desired location
on mounting surface.
2.
Secure floodlight yoke to surface using ½" bolts or lag screws (not
provided).
IF 1620 • 03/11
Copyright © 2011, Cooper Industries, Inc.
Page 2
Figure 2 -
SWB6 Bolt Hole Pattern
WIRING
A)
Pole Mount with SFA6 Slipfitter
B)
Wall Mount with or Without SWB6 Wall Mount Bracket and
SFA6 Slipfitter
1.
When using the SWB6 wall bracket and SFA6 slipfitter, plug the ¾
NPT entry on the SFA6 slipfitter with Crouse-Hinds plug PLG2 (not
supplied).
2.
To make the required wiring transition to portable cord, use Crouse-
Hinds GRFX229 S752 outlet box, with GRF10SA S752 cover and
GASK 643 gasket. See Figure 4. Wall mount the outlet box
adjacent to the floodlight yoke or SWB6 wall mount bracket if used.
3.
Install one end of a length of #16-3 type SOW portable cord (or
other extra hard usage portable cord) into the GRFX outlet box using
a Crouse-Hinds NCG75-75 cable connector. See Figure 5. The
cord length required will allow ample slack to adjust the aiming angle
of the floodlight.
Figure 3 - Pole Mount with SFA6 Slipfitter
CGB294SA
#16-3 Type
SOW Cord
Figure 4
GASK643
GRF10SA S752
GRFX229 S752
Figure 5 - Wall Mount with Outlet Box
#16-3 Type
SOW Cord
NCG75-75
cable connector
1.
For SFA6 Slipfitter Adapter: Remove the access cover by loosening
the captive screw to disengage the locking tab. Set aside for
reassembly later.
2.
Using access opening pull #16-3 type SO cord (or other extra hard
usage portable cord) supply wire from customer supplied wire
chamber through pole. Using the CGB294 cable connector
provided, position a minimum overall length of 3 ft. cord for final
connection to light fixture. Use a small amount of HTL thread
lubricant when installing cord connector and install according to
instructions supplied with connector. Securely tighten cord
connector into slipfitter.
3.
Strip cord insulation jacket back 3 inches and strip each conductor
3/8”.
4.
Secure the access cover as follows: For SFA6 slipfitter secure
cover by tightening the captive screw to engage locking tab. For
SFA6 SS slipfitter attach access plate with four (4) screws and lock
washers.
Proceed to C) Wiring the Floodlight on the next page.
IMPORTANT !
Under no circumstances may wire splices be used in the slipfitter or
pole. Use continuous length supply cord from fixture to approved
customer supplied wiring chamber.
Note: For Class I, Zone 2 refer to NEC 505.15(c) or 501.10(b). Wiring must
be installed in accordance with NEC 400.14.