Modbus TCP Configuration:
Enable Modbus TCP Server
(Slave)
Check this box to enable the on-board Modbus TCP Server. All
Modbus TCP connections to the module IP Address and specified
Modbus Server Device ID will be routed to the on-board I/O registers.
Modbus Server Device ID
Specify the Modbus Device ID for the on-board Modbus TCP Server.
Allowed values are 0 to 255.
Enable Modbus TCP Client
(Master)
Check this box to enable the on-board Modbus TCP Client. I/O to be
transferred via the Modbus TCP client is specified with Modbus TCP
Client Mappings.
Modbus Client Scan Rate
Enter the delay (in milliseconds) between execution of consecutive
Modbus TCP Client Mappings to the same server.
Reset Registers on Comms
Fail
When enabled, the value in any on-board I/O register will be reset to
zero if a valid Modbus transaction directed to/from the given register has
not been completed for longer than the Comms Fail Timeout.
Comms Fail Timeout
The period of time after which on-board I/O registers will be reset if a
valid Modbus transaction directed at that register has not completed.
Modbus TCP Client Mappings:
Local Register
Enter the starting on-board I/O register number that the specified
Modbus Master transaction will transfer I/O to/from.
I/O Count
Specify the number of consecutive I/O registers to be transferred for the
specified transaction.
Function Code
Specify the Modbus Function Code for the transaction.
Destination Register
Enter the starting I/O register number in the destination device that the
specified Modbus Master transaction will transfer I/O to/from.
Device ID
Enter the Modbus Device ID of the destination Modbus device.
Server IP Address
Specify the IP Address of the destination Modbus TCP Server for the
specified transaction.
Response Timeout
Enter the timeout (in milliseconds) to wait for a response to the specified
transaction.
Comms Fail Register
Enter the on-board I/O Register number to store the communication
status of the specified transaction. The specified register will be set to 0
if communications is successful, 0xFFFF if there is no connection to the
specified server, or 0xFFxx, where xx is the Modbus Exception Code.
3.15
Module Information Configuration
Module Information Web Page Fields.
This configuration page is primarily for information purposes. With the exception of the password,
the information entered here is displayed on the root web page of the D2 W MDME 2400.