background image

 Page 13 

4. Remove the PVC tape from the ends of the 

pipe when you're ready to perform the flaring 

work.

 

5. Clamp the flare form on the end of the pipe. The 

end of the pipe must extend beyond the flare 

form. 

Flare form

Pipe

Fig. 7.4

Refrigerant Piping 

Connection

6.

 

Place the flaring tool onto the form.

7. Turn the handle of the flaring tool 

clockwise until the pipe is fully flared. Flare 

the pipe in accordance with the dimensions 

shown in table 7.1.  

T

able 7.1: PIPING EXTENSION BEYOND FLARE 

                 FORM

  Pipe 

gauge 

Tightening 

torque

Flare dimension (A)

(Unit: in/mm)

Flare shape

Min.

Max

.

Ø 6.4

14.2-17.2 N.m 

(144-176 kgf.cm)

0.3/8.3

0.3/8.3

R0.4~0.8

45

°±

2

90

°      

±

4

A

Fig. 7.5

Ø 9.5

32.7-39.9 N.m 

(333-407 kgf.cm)

0.48/12.4

0.48/12.4

Ø 12.7

49.5-60.3 N.m 

(504-616 kgf.cm)

0.6/15.4

0.6/15.8

Ø 15.9

61.8-75.4 N.m 

(630-770 kgf.cm)

0.7/18.6

0.74/19

Ø 19.1

97.2-118.6 N.m 

(990-1210 kgf.cm)

0.9/22.9

0.91/23.3

8. Remove the flaring tool and flare form, 

then inspect the end of the pipe for cracks 

and even flaring.  

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, 

then connect them to the outdoor unit. First connect

the low-pressure pipe, then the high-pressure pipe.  

1. When connecting the flare nuts, apply a thin 

coat of refrigeration oil to the flared ends of 

the pipes.  

2. Align the center of the two pipes that you will 

connect.  

Indoor unit tubing

Flare nut

Pipe

Fig. 7.6

3. Tighten the flare nut as tightly as possible 

by hand. 

4. Using a spanner, grip the nut on the unit 

tubing.

5. While firmly gripping the nut, use a torque 

wrench to tighten the flare nut according to 

the torque values in table 7.1.  

NOTE: 

Use both a spanner and a torque wrench 

when connecting or disconnecting pipes to/from 

the unit.

 

Fig. 7.7

 CAUTION

• 

Be sure to wrap insulation around the piping. 

Direct contact with the bare piping may result 

in burns or frostbite.  

• 

Make sure the pipe is properly connected. 

Over tightening may damage the bell mouth 

and under tightening may lead to leakage.   

NOTE ON MINIMUM BEND RADIUS

Carefully bend the tubing in the middle 

according to the diagram below. 

DO NOT 

bend 

the tubing more than 90° or more than 3 times.  

 

 

Bend the pipe with your thumb

min. radius 10 cm (3.9”)

Fig. 7.8

6. After connecting the copper pipes to the 

indoor unit, wrap the power cable, signal 

cable, and piping together with binding 

tape.  

NOTE: 

When bundling these items together, 

do not intertwine or cross the signal 

cable with any other wiring. 

 

7. Thread this pipeline through the wall and 

connect it to the outdoor unit.  

8. Insulate all the piping, including the valves 

of the outdoor unit.  

9. Open the stop valves of the outdoor unit to 

start the flow of the refrigerant between 

the indoor and outdoor units.  

 CAUTION

After completing the installation work, make sure

there is no refrigerant leak. If there is, ventilate

the area immediately and evacuate the system

(refer to the Air Evacuation section of this

manual).    

Ø 22

109.5-133.7 N.m 

(1117-1364 kgf.cm)

1.06/27

1.07/27.3

Summary of Contents for SOPHIA CH-18MSPH-230VO

Page 1: ...fore installing or operating your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of the outdoor unit When installing the indoo...

Page 2: ...stallation Instructions 09 B Drain Joint Installation 11 C Notes on Drilling the Hole in the Wall 11 D When Selecting a 24K Indoor Unit 11 Table of Contents Installation Manual Installation Diagram 07...

Page 3: ...nnection 12 Wiring 14 A Outdoor Unit Wiring 14 B Wiring Figure 16 Air Evacuation 20 A Evacuation Instructions 20 B Note on Adding Refrigerant 21 22 23 Test Run Function of Automatic Wiring Piping Corr...

Page 4: ...r connector packed with the indoor unit or outdoor unit depending on the model NOTE Pipe sizes differ from appliance to appliance To meet different pipe size requirements sometimes a transfer connecto...

Page 5: ...your unit and locate it accordingly Failure to do so could cause damage to the unit After installation ensure there are no refrigerant leaks and that the unit is operating properly Refrigerant is toxi...

Page 6: ...Unit Installation Overview L N 1 2 3 MC MC 4 5 INSTALLATION ORDER Install the outdoor unit Page 9 Evacuate the refrigeration system Page 20 Connect the wires Page 14 Connect the refrigerant pipes Pag...

Page 7: ...nt unnecessary damage to the wall use a stud finder to locate studs A minimum pipe run of 9 8 ft 3 m is required to minimize vibration and excessive noise Two of the A B and C directions should be fre...

Page 8: ...47 6 45 Max length for one indoor unit 65 6 20 82 25 Max height different between indoor and outdoor unit OU higher than IU 32 8 10 32 8 10 OU lower than IU 49 15 49 15 Max height difference between i...

Page 9: ...tween the outdoor and indoor units must not exceed the maximum allowable pipe length If possible DO NOT install the unit where it will be exposed to direct sunlight If possible make sure the unit is l...

Page 10: ...12 6 22 560 13 2 335 900 x 860 x 315 35 4 x 33 85 x 12 4 23 2 590 13 1 333 945 x 810 x 395 37 2 x 31 9 x 15 55 25 2 640 15 95 405 990 x 965 x 345 38 98 x 38 x 13 58 24 58 624 14 4 366 946 x 810 x 420...

Page 11: ...al on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joint into the hole in the base pan of the unit 3 Rotate the drain joint 90 until it clicks in place facing th...

Page 12: ...nsulate the gas and liquid piping to prevent water leakage Step1 Cut pipes When preparing refrigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and mini...

Page 13: ...hten the flare nut as tightly as possible by hand 4 Using a spanner grip the nut on the unit tubing 5 While firmly gripping the nut use a torque wrench to tighten the flare nut according to the torque...

Page 14: ...of the power cord or use an extension cord CAUTION Connect the outdoor wires before connecting the indoor wires Make sure to ground the unit The grounding wire should be away from gas pipes water pipe...

Page 15: ...he wiring diagram found inside the electrical box cover 2 Remove the electric cover of the outdoor unit If there is no cover on the outdoor unit disassemble the bolts from the maintenance board and re...

Page 16: ...minals as identified with their respective matched numbers on the terminal block of the indoor and outdoor units For example see the following US models Terminal L1 A on the outdoor unit must connect...

Page 17: ...ring NOTE If the client wants to perform the wiring himself refer to the following figures One three models One four models Model A Model B Model C Model D Model A Model B Model C Model D Model E Mode...

Page 18: ...Page 18 Wiring One five models Model A Model B Model C Model D Model E Model F Model G...

Page 19: ...oist area from vibrations to which the unit will be subjected during the course of transportation Check to make sure they are all tightly fastened If they are loose the wires could burn out The follow...

Page 20: ...wise a 1 4 turn Listen for gas to exit the system then close the valve after 5 seconds Flare nut Cap Valve body Valve stem Fig 9 2 9 Watch the Pressure Gauge for one minute to make sure that there is...

Page 21: ...gth standard pipe length x N x 0 16 oZ ft Liquid Side 9 52 3 8 Total pipe length standard pipe length x N x 30 g m Total pipe length standard pipe length x N x 0 32 oZ ft Electrical safety check Perfo...

Page 22: ...p valves 2 Turn on the main power switch and allow the unit to warm up 3 Set the air conditioner to COOL mode 4 For the indoor unit A Ensure the remote control and its buttons work properly B Ensure t...

Page 23: ...te This Function 1 Check that the outside temperature is above 41 F 5 C This fuction does not work when the outside temperature is not above 41 F 5 C 2 Check that the stop valves on the liquid and gas...

Page 24: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details www cooperandhunter us...

Reviews: