background image

Fig. 9.3

 Page 20 

Air Evacuation

9

Safety Precautions

Evacuation Instructions

 

Before using the manifold gauge or vacuum 

pump, read their operation manuals to familiarize 

yourself with how to use them properly.  

Manifold gauge

Compound gauge

-76 cmHg

Low-pressure valve

High-pressure valve

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Low-pressure valve

Fig. 9.1

1. Connect the charge hose of the manifold 

gauge to the service port on the outdoor unit’s 

low-pressure valve. 

2. Connect another charge hose from the 

manifold gauge to the vacuum pump. 

3. Open the low-pressure side of the manifold 

gauge. Keep the low-pressure side closed. 

4. Turn on the vacuum pump to evacuate the system.

5. Run the vacuum for at least 15 minutes, or until 

the compound meter reads -76 cmHG (-1x105 Pa). 

6. Close the low-pressure side of the manifold 

gauge and turn off the vacuum pump. 

7. Wait 5 minutes, then check that there has 

been no change in the system pressure.

NOTE: 

If there is no change in the system pressure, 

unscrew the cap from the packed valve (high-

pressure valve). If there is a change in the system

pressure, there may be a gas leak.

8. Insert a hexagonal wrench into the packed valve 

(high-pressure valve) and open the valve by 

turning the wrench counterclockwise a 1/4 turn. 

Listen for gas to exit the system, then 

close the valve after 5 seconds.   

Flare nut

Cap

Valve body Valve stem

Fig. 9.2

9. Watch the Pressure Gauge for one minute to 

make sure that there is no change in pressure. 

The pressure gauge should read slightly higher 

than atmospheric pressure.  

10.Remove the charge hose from the service port.

11. Using a hexagonal wrench, fully open both the 

high-pressure and high-pressure valves. 

OPEN 

VAL

VE STEMS GENT

L

Y

When opening valve stems, turn the hexagonal 

wrench until it hits against the stopper. 

DO NOT 

try to force the valve to open further.   

 

12.Tighten the valve caps by hand, then tighten 

them using the proper tool. 

13.If the outdoor unit uses all vacuum valves, 

and the vacuum position is at the main 

valve, the system is not connected with the 

indoor unit and must be tightened with a 

screw nut. Check the gas leakage before 

operation to prevent leakage.

Air
Evacuation

 CAUTION

  Use a vacuum pump with a gauge reading 

lower than -0.1 MPa and an air discharge 

capacity above 40 L/min. 

  The outdoor unit does not need vacuuming. 

DO NOT 

open the outdoor unit’s gas and 

liquid stop valves.

 

  Ensure that the compound meter reads 

-0.1 MPa or below after 2 hours. If after 3

hours of operation the gauge reading is 

still above -0.1 MPa, check if there is a gas leak 

or water inside the pipe. If there is no leakage, 

perform another evacuation for 1 or 2 hours.    

• 

DO NOT 

use refrigerant gas to evacuate the 

system.  

 

Summary of Contents for SOPHIA CH-18MSPH-230VO

Page 1: ...fore installing or operating your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of the outdoor unit When installing the indoo...

Page 2: ...stallation Instructions 09 B Drain Joint Installation 11 C Notes on Drilling the Hole in the Wall 11 D When Selecting a 24K Indoor Unit 11 Table of Contents Installation Manual Installation Diagram 07...

Page 3: ...nnection 12 Wiring 14 A Outdoor Unit Wiring 14 B Wiring Figure 16 Air Evacuation 20 A Evacuation Instructions 20 B Note on Adding Refrigerant 21 22 23 Test Run Function of Automatic Wiring Piping Corr...

Page 4: ...r connector packed with the indoor unit or outdoor unit depending on the model NOTE Pipe sizes differ from appliance to appliance To meet different pipe size requirements sometimes a transfer connecto...

Page 5: ...your unit and locate it accordingly Failure to do so could cause damage to the unit After installation ensure there are no refrigerant leaks and that the unit is operating properly Refrigerant is toxi...

Page 6: ...Unit Installation Overview L N 1 2 3 MC MC 4 5 INSTALLATION ORDER Install the outdoor unit Page 9 Evacuate the refrigeration system Page 20 Connect the wires Page 14 Connect the refrigerant pipes Pag...

Page 7: ...nt unnecessary damage to the wall use a stud finder to locate studs A minimum pipe run of 9 8 ft 3 m is required to minimize vibration and excessive noise Two of the A B and C directions should be fre...

Page 8: ...47 6 45 Max length for one indoor unit 65 6 20 82 25 Max height different between indoor and outdoor unit OU higher than IU 32 8 10 32 8 10 OU lower than IU 49 15 49 15 Max height difference between i...

Page 9: ...tween the outdoor and indoor units must not exceed the maximum allowable pipe length If possible DO NOT install the unit where it will be exposed to direct sunlight If possible make sure the unit is l...

Page 10: ...12 6 22 560 13 2 335 900 x 860 x 315 35 4 x 33 85 x 12 4 23 2 590 13 1 333 945 x 810 x 395 37 2 x 31 9 x 15 55 25 2 640 15 95 405 990 x 965 x 345 38 98 x 38 x 13 58 24 58 624 14 4 366 946 x 810 x 420...

Page 11: ...al on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joint into the hole in the base pan of the unit 3 Rotate the drain joint 90 until it clicks in place facing th...

Page 12: ...nsulate the gas and liquid piping to prevent water leakage Step1 Cut pipes When preparing refrigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and mini...

Page 13: ...hten the flare nut as tightly as possible by hand 4 Using a spanner grip the nut on the unit tubing 5 While firmly gripping the nut use a torque wrench to tighten the flare nut according to the torque...

Page 14: ...of the power cord or use an extension cord CAUTION Connect the outdoor wires before connecting the indoor wires Make sure to ground the unit The grounding wire should be away from gas pipes water pipe...

Page 15: ...he wiring diagram found inside the electrical box cover 2 Remove the electric cover of the outdoor unit If there is no cover on the outdoor unit disassemble the bolts from the maintenance board and re...

Page 16: ...minals as identified with their respective matched numbers on the terminal block of the indoor and outdoor units For example see the following US models Terminal L1 A on the outdoor unit must connect...

Page 17: ...ring NOTE If the client wants to perform the wiring himself refer to the following figures One three models One four models Model A Model B Model C Model D Model A Model B Model C Model D Model E Mode...

Page 18: ...Page 18 Wiring One five models Model A Model B Model C Model D Model E Model F Model G...

Page 19: ...oist area from vibrations to which the unit will be subjected during the course of transportation Check to make sure they are all tightly fastened If they are loose the wires could burn out The follow...

Page 20: ...wise a 1 4 turn Listen for gas to exit the system then close the valve after 5 seconds Flare nut Cap Valve body Valve stem Fig 9 2 9 Watch the Pressure Gauge for one minute to make sure that there is...

Page 21: ...gth standard pipe length x N x 0 16 oZ ft Liquid Side 9 52 3 8 Total pipe length standard pipe length x N x 30 g m Total pipe length standard pipe length x N x 0 32 oZ ft Electrical safety check Perfo...

Page 22: ...p valves 2 Turn on the main power switch and allow the unit to warm up 3 Set the air conditioner to COOL mode 4 For the indoor unit A Ensure the remote control and its buttons work properly B Ensure t...

Page 23: ...te This Function 1 Check that the outside temperature is above 41 F 5 C This fuction does not work when the outside temperature is not above 41 F 5 C 2 Check that the stop valves on the liquid and gas...

Page 24: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details www cooperandhunter us...

Reviews: