background image

Wiring

Safety Precautions

 

WARNING

  Be sure to disconnect the power supply 

before working on the unit. 

  All electrical wiring must be done 

according to local and national regulations. 

  Electrical wiring must be done by a 

qualified technician. Improper connections 

may cause electrical malfunction, injury, 

and fire. 

  An independent circuit and single outlet 

must be used for this unit. 

DO NOT 

plug 

another appliance or charger into the 

same outlet. If the electrical circuit capacity 

is not enough or there is a defect in the 

electrical work, it can lead to shock, fire, 

and unit and property damage.

 

  Connect the power cable to the terminals 

and fasten it with a clamp. An insecure 

connection may cause a fire.

  Make sure that all wiring is done correctly 

and the control board cover is properly 

installed. Failure to do so can cause 

overheating at the connection points, fire, 

and electrical shock.  

  Ensure that the main supply connection is 

made through a switch that disconnects 

all poles, with a contact gap of a least 

0.118 in (3 mm). 

• 

DO NOT 

modify the length of the power 

cord or use an extension cord. 

  

 CAUTION

  Connect the outdoor wires before 

connecting the indoor wires.

  Make sure to ground the unit. The 

grounding wire should be away from gas 

pipes, water pipes, lightning rods, 

telephone wires, or other grounding wires. 

Improper grounding may cause electrical 

shock.    

• 

DO NOT 

connect the unit with the power 

source until all wiring and piping is 

completed.

  Make sure that you do not cross your 

electrical wiring with your signal wiring, as 

this can cause distortion and interference.  

Follow these instructions to prevent distortion 

when the compressor starts: 

  The unit must be connected to the main 

outlet. Normally, the power supply must 

have a low output impedance of 32 ohms.  

  No other equipment should be connected 

to the same power circuit.

  The unit’s power information can be found 

on the rating sticker on the product. 

Outdoor Unit Wiring

 

WARNING

Before performing any electrical or wiring work, 

turn off the main power to the system. 

1. Prepare the cable for connection

A. First choose the right cable size. Be sure to

use H07RN-F cables. 

T

able 8.1: Minimum Cross-Sectional 

A

rea 

of Power and Signal Cables North America

Rated Current of 

 

Appliance (A)

AWG

≤ 

7

18

7 - 13

16

13 - 18

14

18 - 25

12

25 - 30

10

 Page 14 

8

Wiring

Summary of Contents for SOPHIA CH-18MSPH-230VO

Page 1: ...fore installing or operating your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of the outdoor unit When installing the indoo...

Page 2: ...stallation Instructions 09 B Drain Joint Installation 11 C Notes on Drilling the Hole in the Wall 11 D When Selecting a 24K Indoor Unit 11 Table of Contents Installation Manual Installation Diagram 07...

Page 3: ...nnection 12 Wiring 14 A Outdoor Unit Wiring 14 B Wiring Figure 16 Air Evacuation 20 A Evacuation Instructions 20 B Note on Adding Refrigerant 21 22 23 Test Run Function of Automatic Wiring Piping Corr...

Page 4: ...r connector packed with the indoor unit or outdoor unit depending on the model NOTE Pipe sizes differ from appliance to appliance To meet different pipe size requirements sometimes a transfer connecto...

Page 5: ...your unit and locate it accordingly Failure to do so could cause damage to the unit After installation ensure there are no refrigerant leaks and that the unit is operating properly Refrigerant is toxi...

Page 6: ...Unit Installation Overview L N 1 2 3 MC MC 4 5 INSTALLATION ORDER Install the outdoor unit Page 9 Evacuate the refrigeration system Page 20 Connect the wires Page 14 Connect the refrigerant pipes Pag...

Page 7: ...nt unnecessary damage to the wall use a stud finder to locate studs A minimum pipe run of 9 8 ft 3 m is required to minimize vibration and excessive noise Two of the A B and C directions should be fre...

Page 8: ...47 6 45 Max length for one indoor unit 65 6 20 82 25 Max height different between indoor and outdoor unit OU higher than IU 32 8 10 32 8 10 OU lower than IU 49 15 49 15 Max height difference between i...

Page 9: ...tween the outdoor and indoor units must not exceed the maximum allowable pipe length If possible DO NOT install the unit where it will be exposed to direct sunlight If possible make sure the unit is l...

Page 10: ...12 6 22 560 13 2 335 900 x 860 x 315 35 4 x 33 85 x 12 4 23 2 590 13 1 333 945 x 810 x 395 37 2 x 31 9 x 15 55 25 2 640 15 95 405 990 x 965 x 345 38 98 x 38 x 13 58 24 58 624 14 4 366 946 x 810 x 420...

Page 11: ...al on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joint into the hole in the base pan of the unit 3 Rotate the drain joint 90 until it clicks in place facing th...

Page 12: ...nsulate the gas and liquid piping to prevent water leakage Step1 Cut pipes When preparing refrigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and mini...

Page 13: ...hten the flare nut as tightly as possible by hand 4 Using a spanner grip the nut on the unit tubing 5 While firmly gripping the nut use a torque wrench to tighten the flare nut according to the torque...

Page 14: ...of the power cord or use an extension cord CAUTION Connect the outdoor wires before connecting the indoor wires Make sure to ground the unit The grounding wire should be away from gas pipes water pipe...

Page 15: ...he wiring diagram found inside the electrical box cover 2 Remove the electric cover of the outdoor unit If there is no cover on the outdoor unit disassemble the bolts from the maintenance board and re...

Page 16: ...minals as identified with their respective matched numbers on the terminal block of the indoor and outdoor units For example see the following US models Terminal L1 A on the outdoor unit must connect...

Page 17: ...ring NOTE If the client wants to perform the wiring himself refer to the following figures One three models One four models Model A Model B Model C Model D Model A Model B Model C Model D Model E Mode...

Page 18: ...Page 18 Wiring One five models Model A Model B Model C Model D Model E Model F Model G...

Page 19: ...oist area from vibrations to which the unit will be subjected during the course of transportation Check to make sure they are all tightly fastened If they are loose the wires could burn out The follow...

Page 20: ...wise a 1 4 turn Listen for gas to exit the system then close the valve after 5 seconds Flare nut Cap Valve body Valve stem Fig 9 2 9 Watch the Pressure Gauge for one minute to make sure that there is...

Page 21: ...gth standard pipe length x N x 0 16 oZ ft Liquid Side 9 52 3 8 Total pipe length standard pipe length x N x 30 g m Total pipe length standard pipe length x N x 0 32 oZ ft Electrical safety check Perfo...

Page 22: ...p valves 2 Turn on the main power switch and allow the unit to warm up 3 Set the air conditioner to COOL mode 4 For the indoor unit A Ensure the remote control and its buttons work properly B Ensure t...

Page 23: ...te This Function 1 Check that the outside temperature is above 41 F 5 C This fuction does not work when the outside temperature is not above 41 F 5 C 2 Check that the stop valves on the liquid and gas...

Page 24: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details www cooperandhunter us...

Reviews: