background image

Specialist’s Manual

Repair to intrinsically safe components

Do not apply any permanent inductive or capaci-
tance loads to the circuit without ensuring that this 
will not exceed the permissible voltage and current 
permitted for the equipment in use.
Intrinsically safe components are the only types that 
can be worked on while live in the presence of a fl-
ammable atmosphere. The test apparatus shall be 
at the correct rating.
Replace components only with parts specified by the 
manufacturer. Other parts may result in the ignition 
of refrigerant in the atmosphere from a leak.

 

Cabling

Check that cabling will not be subject to wear, cor-
rosion, excessive pressure, vibration, sharp edges 
or any other adverse environmental effects. The 
check shall also take into account the effects of 
aging or continual vibration from sources such as 
compressors or fans.

 

Detection of flammable refrigerants

Under no circumstances shall potential sources of 
ignition be used in the searching for or detection of 
refrigerant leaks. A halide torch (or any other detec-
tor using a naked flame) shall not be used.

 

Leak detection methods

Leak detection fluids are suitable for use with most 
refrigerants but the use of detergents containing ch- 
lorine shall be avoided as the chlorine may react 
with the refrigerant and corrode the copper pipe-work.

 

Decommissioning

Before carrying out this procedure, it is essential that 
the technician is completely familiar with the equip-
ment and all its detail. It is recommended good pr- 
actice that all refrigerants are recovered safely. 
Prior to the task being carried out, an oil and refri-
gerant sample shall be taken in case analysis is re-
quired prior to re-use of reclaimed refrigerant. It is 
essential that electrical power is available before 
the task is commenced.
a) Become familiar with the equipment and its opera- 
tion.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:

– mechanical handling equipment is available, if
required, for handling refrigerant cylinders;
– all personal protective equipment is available
and being used correctly;
– the recovery process is supervised at all times
by a competent person;

 

Labelling

d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so
that refrigerant can be removed from various parts 
of the system.
f) Make sure that cylinder is situated on the scales
before recovery takes place.
g) Start the recovery machine and operate in accor-
dance with manufacturer's instructions.
h) Do not overfill cylinders. (No more than 80% vo-
lume liquid charge).
i) Do not exceed the maximum working pressure of
the cylinder, even temporarily.
j) When the cylinders have been filled correctly and
the process completed, make sure that the cylinders 
and the equipment are removed from site promptly 
and all isolation valves on the equipment are closed 
off.
k) Recovered refrigerant shall not be charged into
another refrigeration system unless it has been clean- 
ed and checked.

 

Recovery

When removing refrigerant from a system, either 
for servicing or decommissioning, it is recommend-
ed good practice that all refrigerants are removed 
safely.
When transferring refrigerant into cylinders, ensure 
that only appropriate refrigerant recovery cylinders 
are employed. Ensure that the correct number of cy-
linders for holding the total system charge are av-
ailable. All cylinders to be used are designated for 
the recovered refrigerant and labelled for that refri-
gerant (i.e. special cylinders for the recovery of refri- 
gerant). Cylinders shall be complete with pressure-re- 
lief valve and associated shut-off valves in good work- 
ing order. Empty recovery cylinders are evacuated 
and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working 
order with a set of instructions concerning the 
equipment that is at hand and shall be suitable for 
the recovery of all appropriate refrigerants includ-
ing, when applicable, flammable refrigerants. In ad- 

 

– recovery equipment and cylinders conform to
the appropriate standards.

29

Equipment shall be labelled stating that it has been 
de-commissioned and emptied of refrigerant. The 
label shall be dated and signed. For appliances con-
taining flammable refrigerants, ensure that there are 
labels on the equipment stating the equipment con-
tains flammable refrigerant.

Summary of Contents for CH-S07FTXK-NG

Page 1: ...WNER S MANUAL For proper operation please read and keep this manual carefully CH S07FTXK NG CH S09FTXK NG CH S12FTXK NG CH S18FTXK NG CH S24FTXK NG EN Cozy inverter Series HVLJQHG E RRSHU XQWHU QWHUQD...

Page 2: ...reasons This symbol indicates the possibility of death or serious injury This symbol indicates the possibility of injury or damage to property Indicates important but not hazard related information us...

Page 3: ...aware that refrigerants may not contain an odour Read specialist s manual All the work men who are engaging in the refrig eration system should bear the valid certification awarded by the authoritati...

Page 4: ...erant If you should cut or weld the refrigerant system pipes in the process of maintaining please foll ow the steps as below c Vacuuming d e Cutting or welding Clean it with N2 gas f Carry back to the...

Page 5: ...ir conditioner Unstable power supply or incorrect wiring may result in electric shock fire haza rd or malfunction Please install proper power supply cables before using the air conditioner The groundi...

Page 6: ...must be po sitioned so that the plug is accessible For the air conditioner with plug the plug should be re achable after finishing in stallation For the air conditioner with out plug a circuit breaker...

Page 7: ...by the manufacturer its ser vice agent or similarly qua lified persons in order to avoid a hazard Do not connect air condi tioner to multi purpose soc ket Otherwise it may cau se fire hazard Do discon...

Page 8: ...It may cause mal function Do not step on top panel of outdoor unit or put heavy objects It may cause dam age or personal injury When below phenomenon occurs please turn off air conditioner and discon...

Page 9: ...UZLVH LW PD FDXVH DEQRUPDO RSHUDWLRQ ZUoQJ DFWLoQ PHFKDQLFDO PDOIXQFWLoQ oU HYHQ VHULRXV VDIHW DFFLGHQW 1 minute sure that the unit is running in cooling mode Then fully close the valve at high pressu...

Page 10: ...requirement of air conditioner Unstable power supply or incorrect wiring or malfunction Pl ease install proper power supply cables before using the air conditioner grounding wire of power socket 5 Be...

Page 11: ...when opening the hole bellmouth Pretighten the union nut with hand Please refer to the actual circumstances for the number of screws and the position of screws rear right 1 The pipe can be led out in...

Page 12: ...the wire by yourself cable cross hole power connection wire reachable after finishing installation For the air conditioner without plug an air switch must be installed in the line The air switch shou...

Page 13: ...indoor power cord Bind up the connection pipe power cord and Bind them evenly Remove the wire clip connect the power conn ection wire to the wiring terminal according to the color tighten the screw a...

Page 14: ...et for outdoor unit is damaged or corroded If yes please contact dealer The filter should be cleaned every three months If there is much dust in the operation environme After removing the filter do no...

Page 15: ...pansion and or contraction of panel or other parts due to the change of temp erature Whether there s od our source such as furniture and cigare tte etc In order to prevent blowing out cold air indoor...

Page 16: ...button to turn off the air conditioner When the air conditioner is turned on it will operate under auto mode Display Temp indicator Power indicator NOY OY ZNK MKTKXGR OTZXUJ IZOUT GTJ ZNK IURUX UL OTJ...

Page 17: ...ode Outdoor ambient temp Auto mode Cool mode X FAN button Set temp Indoor ambient temp Temp display type Dry mode Fan mode Heat mode Set temperature 8 C heating function Health mode Scavenging functio...

Page 18: ...give out a di sound which means the signal has been sent to the air conditioner When selecting auto mode air conditioner will operate automatically according to ex factory setting Set temperature can...

Page 19: ...nder COOL or HEAT mode press this button to turn to quick COOL or quick HEAT mode icon is displayed on remote controller Press this button again to exit turbo function and icon will disappear If start...

Page 20: ...CLOCK button to confirm the time icon stops blink ing button Under on and off status you can set T OFF or T ON simultaneously Before setting T ON or T OFF please adjust the clock time After starting u...

Page 21: ...art up the ener gy saving function will cancel sleep function Under OFF status press and MODE buttons simultaneously to switch temperature display between C and F Under cooling mode press TEMP and CLO...

Page 22: ...y clean it once a month if not clean it once every three months After the auto clean function is turned on you can leave the room When auto clean is finished the air conditioner will enter standby sta...

Page 23: ...nction or damage the parts Is there any obstruction in the air inlet and outlet Is heat insulation of pipe line sufficient It may cause malfunction or damage the parts The gas valve and liquid valve o...

Page 24: ...20 Parts name Outdoor Unit 127 Actual product may be different from above graphics please refer to actual product air inlet air outlet...

Page 25: ...ubstances other than the specified refrigerant Any presence of air or other foreign substance in the refrigerant circuit will cause system pre ssure rise or compressor rupture resulting in injury Meas...

Page 26: ...roper power supply cables before using the air conditioner 5 Be sure to cut off the power supply before pr 4 Make sure that the installation follows the req uirement of installation dimension diagram...

Page 27: ...n vent As for the shape of drainage joint please refer to the current product Do not install the drainage joint in the severe cold area Otherwise it will be frosted and then cause malfunction Take suf...

Page 28: ...er connection wire and signal con trol wire with wire clip only for cooling and h eating unit 1 The through wal height of drain hose shoul not be higher than the outlet pipe hole of in door unit 24 Sl...

Page 29: ...Leakage detection Use vacuum pump Remove the valve caps on the liquid valve and It may cause insufficient cooling heating capacity 1 1 2 5 Remove the piezometer open the valve core Reinstall the handl...

Page 30: ...and 8m the min length of con nection pipe is 3m Max length of connection pipe is shown as below 4 1 2 The calculation method of additional refrigerant oil and refrigerant charging amount after prolon...

Page 31: ...below 1 8 1 0 2 4 2 2 27 uneven thickness the length is equal hard mold NOTICE Outer diameter mm B Remove the burrs Remove the burrs with shaper and prevent the D Put on the union nut pipe and outdoo...

Page 32: ...eal ed or intrinsically safe Presence of fire extinguisher If any hot work is to be conducted on the refrigera tion equipment or any associated parts appropriate Ventilated area Ensure that the area i...

Page 33: ...and being used correctly the recovery process is supervised at all times by a competent person Labelling d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so th...

Page 34: ...refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant waste transfer note arranged Do not mix refrigerants in recovery units and especially not i...

Page 35: ...nter is co onstantly y w w wo o ork king g to o im m mpro o ov v ve th heir pro o od d du u ucts so o th he inf f fo o orm m matio on in th his m m manu ual is su u ub b bjjject to o ch hang ge w with...

Page 36: ...U Cozy inverter CH S07FTXK NG CH S09FTXK NG CH S12FTXK NG CH S18FTXK NG CH S24FTXK NG HVLJQHG E RRSHU XQWHU QWHUQDWLRQDO RUSRUDWLRQ 0LDPL 86...

Page 37: ......

Page 38: ...5 5 5 5 P D 5 5 67...

Page 39: ...2 1 6 1 9 2 1 2 4 2 8 3 1 3 4 3 8 4 2 4 6 5 5 5 6 1 1 1 3 1 4 1 6 1 8 2 1 2 3 2 6 2 8 3 1 3 4 3 7 4 14 5 16 8 19 3 24 8 27 8 34 3 5 2 6 1 7 7 9 8 9 10 11 2 12 4 13 6 16 3 17 8 19 3 2 2 12 5...

Page 40: ...5...

Page 41: ...6...

Page 42: ...7...

Page 43: ...8...

Page 44: ...9...

Page 45: ...10...

Page 46: ...5 10 11...

Page 47: ...15 20 30 40 45 55 70 75 12...

Page 48: ...13 N 1 2 2 3...

Page 49: ...8 14...

Page 50: ...15 a...

Page 51: ...16...

Page 52: ...17 X FAN 8 C Wi Fi I Feel TIMER ON TIMER OFF...

Page 53: ...18 FAN MODE ON OFF a a 1 1 1 1 1 1 1 1 1...

Page 54: ...7XUER 7 0 5 21 7 0 5 2 2 2 7 0 5 21 7 0 5 2 6 3 22 7 19 TURBO SLEEP X FAN X FAN COOL DRY 10 AUTO FAN HEAT...

Page 55: ...R 2N 7 0 5 21 21 7 0 5 21 7 0 5 21 21 7 0 5 21 7 0 5 21 7 0 5 21 TIMER 2FF 7 0 5 2 2 7 0 5 2 7 0 5 2 2 7 0 5 2 7 0 5 2 7 0 5 2 20 I FEEL 7 0 5 21 7 0 5 2 7 0 5 21 7 0 5 2 7 0 5 21 2 CLOCK 7 0 5 21 7 0...

Page 56: ...21 7 03 2 6 7 03 2 02 785 2 7 03 2 7 03 2 785 2 6 3...

Page 57: ...22 Wi Fi MODE TURBO WIFI WIFI WiFi 10 WIFI WIFI Double Self Clean 0RGH DQ...

Page 58: ...23 02...

Page 59: ...24 15 15 15 20 25 25 30 30 30 30 A 5 _ _ 80 200 200 280 280 12 12 200 280...

Page 60: ...25...

Page 61: ...26...

Page 62: ...27...

Page 63: ...28...

Page 64: ...29...

Page 65: ...0...

Page 66: ...10A 16A 31...

Page 67: ...2 a...

Page 68: ...8 33 15 20 30 40 45 55 60 65 70 75 1 4 3 8 1 2 5 8 3 4 L L N L N 1 2 3 N 1 2 3 L N 1 2 N L 8...

Page 69: ...Lo Hi Lo Hi 34 02...

Page 70: ...Cooper Hunter...

Page 71: ...Cozy inverter CH S07FTXK NG CH S09FTXK NG CH S12FTXK NG CH S18FTXK NG CH S24FTXK NG RU HVLJQHG E RRSHU XQWHU QWHUQDWLRQDO RUSRUDWLRQ 0LDPL 86...

Page 72: ......

Page 73: ...5 5 5 5 P D 5 5...

Page 74: ...2 1 6 1 9 2 1 2 4 2 8 3 1 3 4 3 8 4 2 4 6 5 5 5 6 1 1 1 3 1 4 1 6 1 8 2 1 2 3 2 6 2 8 3 1 3 4 3 7 4 14 5 16 8 19 3 24 8 27 8 34 3 5 2 6 1 7 7 9 8 9 10 11 2 12 4 13 6 16 3 17 8 19 3 2 2 1 5...

Page 75: ...5...

Page 76: ...6 F...

Page 77: ...7...

Page 78: ...8...

Page 79: ...9...

Page 80: ...10...

Page 81: ...5 10 2 3 2 2 3 1 1 1 11 2 3...

Page 82: ...15 20 30 40 45 55 70 75 4 1 2 2 1 12...

Page 83: ...3 1 5 2 3 4 4 2 3 1 13 N 1 2 2 3...

Page 84: ...2 1 3 4 5 1 1 2 3 8 2 1 14...

Page 85: ...15 16 C C...

Page 86: ...16...

Page 87: ...17 X FAN 8 C Wi Fi I Feel TIMER ON TIMER OFF T ON T OFF...

Page 88: ...18 FAN MODE ON OFF a a 1 1 1 1 1 1 1 1 1...

Page 89: ...1 C F 22 7 5Y 19 TURBO SLEEP...

Page 90: ...5 21 7 0 5 21 21 7 0 5 21 7 0 5 21 21 7 0 5 21 7 0 5 21 7 0 5 21 7 0 5 2 7 0 5 2 2 7 0 5 2 7 0 5 2 2 7 0 5 2 7 0 5 2 7 0 5 2 20 I FEEL 7 0 5 21 7 0 5 2 7 0 5 21 7 0 5 2 7 0 5 21 7 0 5 2 2 7 0 5 21 7 0...

Page 91: ...21 X FAN 1 22 5Y 10 AUTO FAN HEAT 7 03 2 6 7 03 2 02 785 2 7 03 2 7 03 2...

Page 92: ...22 785 2 6OHHS 6OHHS Wi Fi MODE TURBO WIFI WIFI WiFi MODE TURBO 10 WIFI WIFI WIFI Double Self Clean 0RGH DQ...

Page 93: ...23 21 2 02...

Page 94: ...24 15 15 15 20 25 25 30 30 30 30 Max length of connection pipe A 5 _ _ 80 200 200 280 280 12 12 200 280...

Page 95: ...25...

Page 96: ...26...

Page 97: ...27...

Page 98: ...28...

Page 99: ...29...

Page 100: ......

Page 101: ...10A 16A 31 1 3 5 6 7 8 10 11 13...

Page 102: ...2 2 1 1 2 2 1 1 2 a...

Page 103: ...4 2 1 2 8 1 33 15 20 30 40 45 55 60 65 70 75 1 4 3 8 1 2 5 8 3 4 L L N L N N 1 2 3 N N 1 2 3 L N N 1 2 L 3 N L 8 F F F F F F...

Page 104: ...1 2 1 1 2 7 Lo Hi 34 3 4 5 6 2 21 2 02...

Page 105: ...Co o oo o oper Hu unter...

Reviews: