A corrosion inhibitor suitable for the materials in the system should be added to the
glycol/water solution.
If straight water use is desired, contact Fleming Dynamics Pty Ltd.
The 23 litre reservoir is
not
designed to withstand water pressure above
34 kPa.
The fill opening and vent line must be vented to the atmosphere for proper operation.
Ethylene Glycol Required
For Evaporator Freeze Protection
Figure 6: Ethylene Glycol Curve
30%
Ethylene
Glycol
20%
Percent
By
Volume
10%
0%
-3.8
o
1.6
o
7.2
o
12.7
o
18.3
o
Chilled Water
Operating Temperature
o
C
(Set Point)
Normal Operating Range between -1.1
o
C
– 21.1
o
C