![Coolerado C60A Installation Manual Download Page 8](http://html1.mh-extra.com/html/coolerado/c60a/c60a_installation-manual_2661042008.webp)
Coolerado Installation
Page
8
of
53
Filter Flow Arrow, Figure 4
NOTE: One 1” (25 mm) thick filter can be used in place of 2”
(50 mm) filters but will need to be changed twice as often.
CAUTION: Do not substitute the recommended 2” (50 mm)
filter with two 1” (25 mm) filters, this will significantly
reduce the airflow through the unit. See Figure 5
DANGER: Do not expose the intake air to flammable liquids
or vapors.
Filter image, Figure 5
Step 3—Clearance Requirements
1.)
Inspect clearances and position the unit for
installation – see
Appendices 8, 10 or 12
for unit
dimensions and clearance details per model.
2.)
Familiarize yourself with the unit’s connection and
service points. See
Figure 6.
Pre-Cut 16" (406 mm)
Diameter Exhaust In Top
High Voltage Power
Factory Wired
Connections
Soap
Pump
Control Wiring,
Low Voltage
Do Not Block
Filter Access Door
Filter Access
Door Handles
Pre-Cut 16" x 16"
(406 x 406 mm)
Louver/ Cover
Lifting Lugs
Drain
Water In
Low Voltage Wire
Terminals In
High Voltage Wire
Terminals In
Outdoor
Air In
Identifying System Components, M50A, Figure 6
NOTE: Ensure unit is positioned so that filters, soap pump
and electrical service areas are easily accessible for
maintenance and seasonal changes.
NOTE: Figure 7 shows the working exhaust air from the top.
For units using side working air exhaust
.
CAUTION: Ensure a minimum of 24” (610 mm) clearance for
side mounted working air exhaust.
NOTE: Take precautions not to block service areas of unit
and that ductwork connections have enough flexibility for
leveling or seasonal re-leveling purposes.
Summary of Contents for C60A
Page 4: ...Page 4 of 53 Installation Notes ...
Page 34: ...Coolerado Installation Page 34 of 53 Appendix 9 M30 Dimensional Specifications ...
Page 36: ...Coolerado Installation Page 36 of 53 Appendix 11 M50B Dimensional Specifications ...
Page 40: ...Coolerado Installation Page 40 of 53 C60A Dimensional Specifications Continued ...