Appendix 10: M30 Air Flow Performance Table
Coolerado M30 Performance Table*
External Static
Pressure
Full Speed Product Air
Flow
Approx.
Product
Air Wet
Bulb
Approach
Product Approx.
= WB + below
Working Air Flow
Inches
H2O
Pascal
CFM
CMH
LPS
F
C
CFM
CMH
LPS
0.00
0
900
1,529
425
94%
3
1.7
710
1206
335
0.10
24.9
850
1,444
401
95%
2
1.1
680
1155
321
0.20
49.8
800
1,359
378
95%
1
.6
640
1087
302
0.30
74.7
750
1,274
354
98%
1
.6
610
1036
288
0.40
99.5
710
1,206
335
100%
0
0
580
985
274
0.50
124.4
660
1,121
312
103%
-1
-.6
540
917
255
0.60
149.3
610
1,036
288
107%
-2
-1.1
510
866
241
0.70
174.2
560
951
264
110%
-3
-1.7
470
799
222
0.80
199.1
510
866
241
113%
-4
-2.2
430
731
203
0.90
224
460
782
217
117%
-5
-2.8
390
663
184
1.00
248.9
420
714
198
120%
-6
-3.3
360
612
170
* Performance at sea level: Performance increases ~0.5% for every 1,000 feet/305 m increase above sea level.
Example: Design 98F DB / 62F WB, 0.1” ext. static, 98 - 62 = 36, 36 * 0.95 = 34.2, 98 – 34.2 = 63.8 ºF Product Air Temperature ≈
Design WB + 2 = 64 ºF
Example: Design 36C DB / 16C WB, 0.1” ext. static, 36 - 16 = 20, 20 * 0.95 = 19, 36 – 19 = 17C Product Air Temperature ≈ Design
WB + 1.1C = 18.1 ºC
Summary of Contents for C60A
Page 4: ...Page 4 of 53 Installation Notes ...
Page 34: ...Coolerado Installation Page 34 of 53 Appendix 9 M30 Dimensional Specifications ...
Page 36: ...Coolerado Installation Page 36 of 53 Appendix 11 M50B Dimensional Specifications ...
Page 40: ...Coolerado Installation Page 40 of 53 C60A Dimensional Specifications Continued ...