Appendix 12: M50B Air Flow Performance Table
Coolerado M50A Performance Table*
External Static
Pressure
Full Speed Product Air
Flow
Approx.
Product
Air Wet
Bulb
Approach
Product Approx.
= WB + below
Working Air Flow
Inches
H2O
Pascal
CFM
CMH
LPS
F
C
CFM
CMH
LPS
0.00
0
1350
2290
635
94%
2
1.1
1000
1700
470
0.10
24.9
1280
2170
601
95%
2
1.1
950
1610
445
0.20
49.8
1200
2050
567
95%
1
.6
890
1510
420
0.30
74.7
1140
1930
534
98%
1
.5
840
1430
395
0.40
99.5
1060
1810
500
100%
0
0
790
1340
370
0.50
124.4
990
1690
466
103%
-1
-.6
730
1240
345
0.60
149.3
920
1560
433
107%
-2
-1.1
680
1150
320
0.70
174.2
850
1440
399
110%
-3
-1.7
630
1070
295
0.80
199.1
780
1320
366
113%
-4
-2.2
570
970
271
0.90
224
710
1200
332
117%
-5
-2.8
520
880
246
1.00
248.9
630
1080
298
120%
-6
-3.3
470
800
221
* Performance at sea level: Performance increases ~0.5% for every 1,000 feet / 305 m increase above sea level.
Example: Design 98F DB / 62F WB, 0.1” ext. static, 98 - 62 = 36, 36 * 0.95 = 34.2, 98 – 34.2 = 63.8 ºF Product Air Temperature ≈
Design WB + 2 = 64 ºF
Example: Design 36C DB / 16C WB, 0.1” ext. static, 36 - 16 = 20, 20 * 0.95 = 19, 36 – 19 = 17C Product Air Temperature ≈ Design
WB + 1.1C = 18.1 ºC
Summary of Contents for C60A
Page 4: ...Page 4 of 53 Installation Notes ...
Page 34: ...Coolerado Installation Page 34 of 53 Appendix 9 M30 Dimensional Specifications ...
Page 36: ...Coolerado Installation Page 36 of 53 Appendix 11 M50B Dimensional Specifications ...
Page 40: ...Coolerado Installation Page 40 of 53 C60A Dimensional Specifications Continued ...