Appendix 15: C60A Air Flow Performance Table
Coolerado C60 Performance Table*
External Static
Pressure
Full Speed Product Air
Flow
Approx.
Product
Air Wet
Bulb
Approach
Product Approx.
= WB + below
Working Air Flow
Inches
H2O
Pascal
CFM
CMH
LPS
F
C
CFM
CMH
LPS
0.00
0
1550
2630
729
94%
2
1.1
1200
1380
560
0.10
24.9
1470
2490
690
95%
2
1.1
1140
1310
540
0.20
49.8
1380
2340
650
96%
1
.6
1070
1230
500
0.30
74.7
1300
2200
611
98%
1
.5
1000
1150
470
0.40
99.5
1220
2070
570
100%
0
0
940
1080
440
0.50
124.4
1130
1910
530
103%
-1
-.6
870
1000
410
0.60
149.3
1050
1780
490
107%
-2
-1.1
810
930
380
0.70
174.2
970
1640
460
110%
-3
-1.7
750
860
350
0.80
199.1
900
1520
420
113%
-4
-2.2
700
800
330
0.90
224
810
1370
380
117%
-5
-2.8
630
720
300
1.00
248.9
720
1220
340
120%
-6
-3.3
560
640
260
* Performance at sea level: Performance increases ~0.5% for every 1,000 feet / 305 m increase above sea level.
Example: Design 98F DB / 62F WB, 0.1” ext. static, 98 - 62 = 36, 36 * 0.95 = 34.2, 98 – 34.2 = 63.8 ºF Product Air Temperature ≈
Design WB + 2 = 64 ºF
Example: Design 36C DB / 16C WB, 0.1” ext. static, 36 - 16 = 20, 20 * 0.95 = 19, 36 – 19 = 17C Product Air Temperature ≈ Design
WB + 1.1C = 18.1 ºC
Summary of Contents for C60A
Page 4: ...Page 4 of 53 Installation Notes ...
Page 34: ...Coolerado Installation Page 34 of 53 Appendix 9 M30 Dimensional Specifications ...
Page 36: ...Coolerado Installation Page 36 of 53 Appendix 11 M50B Dimensional Specifications ...
Page 40: ...Coolerado Installation Page 40 of 53 C60A Dimensional Specifications Continued ...