29 |
P a g e
Lift the filter and clean it from possible impurities. Put
again the cleaned filter and the opening before restart
the equipment.
5.6 Water circuit / Condensate discharge
The water circuit check is limited to the integrated filter installed by the customer (if any; in this case
follow the instructions provided by the valve manufacturer); also check the tightness of the valves, of
the screw connections, etc.; should they be loose, have them tightened by technicians.
As to the condensate drain, you have to check its operation, the condensate elimination (transparent
plastic pipe), the tightness and the presence of any impurities at the pipe ends, cleaning them if
needed.
5.7
Air circuit supply
Maintenance operations only include the cleaning of the evaporator, when needed or at the end of
each shift, when checking the protective magnesium anodes.
WARNING:
U
Danger of injuries due to the presence of sharp edge blades. The blades must not
U
U
be deformed or damaged
– (comb blades of the condenser).
5.8 Descaling and limestone deposit removal
(periodic)
Since almost anywhere deposits of limestone can be formed, verify the infiltrations of dirty water and
for hygienic motives, the inside tank should be controlled and checked by a qualified person at least
after the first 2 years of use, but however when the production of hot water decreases.
The limestone deposits reduce the tank volume, so also the transmission capacity of the heat
exchanger and the production of hot water are reduced.
Maintenance must be done by qualified personnel.
For an accurate and competent maintenance of the inner tank it is necessary to have free access to the
flange in order to control and clean the inner boiler.