9 |
P a g e
Cool Energy Pro Series Air Source Heat Pump Specification
Note:
The above design and specifications are subject to change without prior notice for product
improvement. For detailed specifications of the units please refer to name plate on the units.
Correct installation is required to ensure safe operation. The requirements for Cool Energy heat
pumps include the following:
1.
Appropriate site location and clearances.
2.
Wiring to conform to 17
th
edition wiring regulations.
3.
Adequate water flow.
This manual provides the information needed to meet these requirements. Review all application
and installation procedures completely before continuing the installation.
Cool Energy Air to Water Heat Pumps
Model
CE-H4
CE-H6
CE-H8
CE-H17
CE-iH6-18
ERP Energy Rating:
A++
A++
A++
A++
A++
Rated Capacity
@ 35
°
C
Water/ 20
°
C
Ambient
Heating Capacity
5.15kW
8.41kW
11.6kW
16.9kW
18.7kW
Power Input
1.25kW
1.9kW
2.52kW
3.6kW
3.7kW
Coefficient Performance
4.26 Cop
4.39 Cop
4.57 Cop
4.69 Cop
5.05 Cop
Rated Capacity
@ 35
°
C
Water/ 7
°
C
Ambient
Heating Capacity
4.16kW
8.16kW
10.98kW
16.5kW
17.5kW
Power Input
1.2kW
2.1kW
2.6kW
4.19kW
4.3kW
Coefficient Performance
3. 44Cop
3.88 Cop
4.2KW
3.95 Cop
4.01 Cop
Rated Capacity
@ 45
°
C
Water/ 20
°
C
Ambient
Heating Capacity
4.3kW
7.59kW
10.6kW
15.5kW
16.5kW
Power Input
1.41kW
2.1kW
2.68kW
3.8kW
3.7kW
Coefficient Performance
3.6 Cop
3.59Cop
3.95 Cop
4.06 Cop
4.46 Cop
Rated Capacity
@ 45
°
C
Water/ 7
°
C
Ambient
Heating Capacity
4.0kW
7.14kW
10.16kW
14.8kW
14.6kW
Power Input
1.21kW
2.15kW
2.68kW
4.2kW
3.9kW
Coefficient Performance
3.3 Cop
3.32 Cop
3.49 Cop
3.48 Cop
3.69 Cop
Noise:
≤
52dB(A)
≤
52dB(A)
≤
52dB(A)
≤
60dB(A)
≤
60dB(A)
Rated Power Input:
1.34kW/5.86A
2kW/9.09A
2.5kW/11.4A
3.9kW/17.85A
4kW/18.8A
Max Power Input:
1.45kW/6.3A
2.2kW/10A
2.9kW/13.1A
4.6kW/20.9A
4.8kW/21.8A
Compressor Make/Model:
Mitsubishi
RN145VHEMC
Mitsubishi
RN222VHFMC
Mitsubishi
LN28VBRMC
Copeland
ZW
54KWP-PFS-52E
Mitsubishi
Inverter
Power supply:
220-240V AC
–
50Hz
Outlet Water Temperature:
35
℃
-60
℃
Protection class:
IPX4
Anti-electric shock class:
Class I
Refrigerant/Charge:
R410A-800g
R410A-1000g
R410A-2000g
R410A-3000g
R410A-4100g
Average Water Flow Required:
1.75m3/H
1.9m3/H
2m3/H
3m3/H
3m3/H
Water Pump Model:
Wilo 15/6
Wilo 15/6
Wilo 25/8
Wilo PUN-200EH
Water Connections:
1
”
Male
1
”
Male
1
”
Male
1
”
Male
Climate Type:
-15~43
℃
Product dimension: L x W x H:
mm
670/365/990
670/365/990
680/305/110
0
768/732/955
768/732/955
Net weight:
63kg
64Kg
68Kg
132Kg
118Kg
Manufacture Date / Serial Number See Bar Code
Cool Energy Holding Ltd
Grimsby, UK
01472 867497
www.coolenergyshop.com
Summary of Contents for CE-H17
Page 12: ...12 P a g e Suggested Installation Method 1 Heating with Hot Water Priority Buffer ...
Page 13: ...13 P a g e Suggested Installation Method 2 Hot Water Buffer Thermal Store Only ...
Page 14: ...14 P a g e Suggested Installation Method 3 Heating Only with Buffer ...