If there is a water tank temperature probe fault and then ambient temp decides to go
into anti-freeze mode, it will only trigger mode 1.
If there is an ambient temperature probe fault, then the unit automatically goes into
mode 1 anti-freeze protection.
If ambient temperature probe and outlet temperature probe both give a fault, then
then the unit will go into mode 1 anti-freeze protection and water pump will function.
9.
Compressor over Current Protection (Er37): - Not Currently Used
10.
Controller Communication Faults (Er08):
The first time the unit powers on, if within 20 seconds the PCB
doesn’t receive
communication from remote controller, it will operate
to “the last input parameter”;
If when the unit is running, and
remote controller doesn’t receive communication from PC
B for a
constant 10 seconds it is judged as a communication fault, the unit will display fault code Er08.
During this time the unit works as per original settings and after communication fault is corrected
the fault will disappear.