X-320M™ User's Manual
Installation and Setup
Deadband
The Deadband prevents alarms from triggering excessively when the sensor measurement
vacillates around the trigger point.
With High Alarms, the measurement must fall below the High Alarm point minus the Deadband
before the High Alarm will be triggered again. Likewise, the Deadband on the Low Alarm requires
the measurement to rise above the Low Alarm point plus the deadband before the Low Alarm will be
triggered again.
For example, if the deadband is set to 5, and a high alarm occurs at 50, the alarm will not trigger
again until the value first drops below 45 (50 - 5), as shown in the figure below. The default
Deadband is
0.50
.
Email Option
Simple email messages can be sent in response to alarm conditions. This parameter is used to
specify what alarm conditions, if any, will cause email messages to be sent. Email notification will
work only if email is correctly set up in the
Network
setup page.
-
No Email Messages
:
No email messages will be sent due to alarm conditions.
-
Send Email on High Alarm
: Email notifications will be sent due to the High Alarm condition.
-
Send Email on Low Alarm
:
Email notifications will be sent due to the Low Alarm condition.
-
Send Email on High and Low Alarm
:
Email notifications will be sent due to the High and/or
Low Alarm condition.
-
Send Email on High, Low, and Normal
:
Email notifications will be sent due to the High
Alarm, Low Alarm, or when Normal conditions are regained.
Use Email Address
If email messages are to be sent based on alarm conditions, these check boxes specify to which
email addresses the message will be sent. Email addresses specified on the
Network
setup tab will
be shown next to each check box.
Output 1 or Output 2 (This option will only appear if one of the Digital I/O's is selected as an
output on the I/O tab)
This field is used to set the action that the corresponding Output will have due to an alarm condition.
The first drop down box specifies the action. The following actions are available:
Xytronix Research & Design, Inc.
Page 85
Figure 2.4y - AUX Alarm Deadband
Summary of Contents for X-320m