2.7
RJ45 connectors and cables
RJ45 connectors
For connection to the following connectors on the drive...
•
SLM
•
MC
•
MULTIDROP OUT
•
MULTIDROP IN/PC
... use the following:
Cables
Up to four twisted-pairs having an overall shield (unused wires must not
be connected to pins at the other end)
Maximum length: 50m (165ft)
Maximum diameter: 6.6mm (
1
/
4
in)
Static installations: for example, use BICC type S-FTP patch, four
twisted pairs, 5.33mm diameter
Dynamic installations: for example, use Intercond type 3MBM 26P 02P,
2 twisted pairs, 5.5mm diameter
Connectors
Shielded 8-way RJ45 plugs
Connect the pins in pairs as shown.
Comb out the braided shield, fold the strands back and trap them under
the cable clamp to ensure good electrical contact with the clamp.
Do not use unshielded plugs.
Use RS Component part no 290-4780 for shielded
connector 5.7mm, or
Use RS Component part no 342-2087 for shielded
connector 6.6mm
Ordering signal cables
Cables of the required lengths and fitted with RJ45 connectors as
required are supplied by Control Techniques Dynamics Ltd. For
ordering, create the required order code (see below) and contact the
supplier of the drive.
The order code is constructed as follows:
Details of the code are as follows:
Wait 30 seconds after removing power to the drive before
inserting or removing control cables as ‘hot plugging’
cables can result in damage to the drive or SLM.
1
2
3
4
5
6
7
8
1
8
WARNING
1
Type of cable
SL
Two twisted pairs in overall shield
2
Type of sheath
B
PUR
Use for dynamic applications (motor mounted on a moving
structure) – increased oil resistance
3
Options
A
Standard
4
Cable terminations
F
RJ45 plug
5-way Din connector Drive to SLM
G
RJ45 plug
Cut end
K
RJ45 plug
RJ45 plug
Drive to drive
X
Cut end
Cut end
5
Cable length
Specify length in metres
Minimum: 002 (2 metres)
Maximum: 050 (50 metres)
CAUTION