M’Ax Installation Guide
25
Issue Number: 6
www.controltechniques.com
Appendix A
UL Listing
Information
The drive conforms to UL listing requirements only when the following
are observed:
•
The drive is installed in a type 1 enclosure, or better, as defined by
UL50
•
UL-listed fuses class CC 600VAC are used in the AC supply
•
Class 1 60/75°C (140/167°F) copper wire only is used in the
installation
•
The ambient temperature does not exceed 40°C (104°F) when the
drive is operating
•
The terminal tightening torques specified in section 2.29 Terminal
sizes and tightening torques on page 17 are used
A.1
AC supply specification
The drive is suitable for use in a circuit capable of delivering not more
than 5000 RMS symmetrical Amperes at 528VAC RMS maximum.
A.2
Maximum continuous output current
The drive models are listed as having the maximum continuous output
currents (FLC) shown in Table A-1.
Table A-1
Maximum continuous output current
Model
FLC (A)
MAX403SL
3.5
MAX403AN
MAX406SL
6.5
MAX406AN
MAX409SL
9.5
MAX409AN
MAX412SL
12.5
MAX412AN