Continental Hydraulics Installation Manual
Page 7 of 24
CEM-PA-B
CHI 1020688 01/2016
LED Definitions
LEDs
Description of the LED function
Identical to the READY output.
OFF:
No power supply or ENABLE is not activated
ON:
System is ready for peration
Flashing:
Error discovered
Only active when SENS = ON
YELLOW A
Intensity of the solenoid current
1.
Chasing light (over all LEDs):
The bootloader is active. No
normal functions are possible.
2.
All LEDs flash shortly every 6 s:
An internal data error was
detected and corrected automatically! The module still works
regularly. To acknowledge the error the module has to be cycle
powered.
YELLOW A +
YELLOW B
Both yellow LEDs flash oppositely every 1 s:
The nonvolatile stored
parameters are inconsistent! To acknowledge the error, data has to
be saved with the SAVE command or the corresponding button in the
CHI-PC.
GREEN
GREEN + YELLOW A
Terminal Identification - Input and output signals
Connection
Supply
PIN 7
Power supply (see technical data)
PIN 8
0 V (GND) connection.
Connection
Analogue signals
PIN 9 / 10
Pressure command value (WA), signal range 0… 10 V or 4… 20 mA,
scalable (SIGNAL W)
PIN 13 /14
Pressure feedback value (X), signal range 0… 10 V or 4… 20 mA,
scalable (SIGNAL X)
PIN 11
0 V (GND) connection for analogue signals
PIN 12
8V reference voltage output
PIN 3 / 4
PWM output to the solenoid
Connection
Digital inputs and outputs
Enable input:
Generally enabling of the application.
RUN (Start) Input
:
ON:
The controller is active.
OFF:
The controller is not active.
READY output:
ON:
The module is enabled; there are no discernable errors.
OFF:
ENABLE (PIN 15) is not active or an error has been detected.
PIN 15
PIN 6
PIN 5