Continental Hydraulics Installation Manual
Page 17 of 24
CEM-PA-B
CHI 1020688 01/2016
MIN (Deadband compensation)
MAX (Output scaling)
TRIGGER (Response threshold for the MIN parameter)
Command
Parameters
Unit
Group
MIN:I
X
MAX:I
X
TRIGGER X
x= 0… 6000
x= 3000… 10000
x= 0… 3000
0.01 %
0.01 %
0,01 %
STD
With this command, the output signal is adjusted to the valve characteristics. With the
MAX value the output signal (the maximum valve current) will be defined. With the MIN
value the overlap (dead band of the valve) will be compensated. Via the TRIGGER the
activation point of the MIN function is set and so a non-sensitive range around the zero-
point
1
can be specified.
If the MIN value is set too high, it influences the minimal pressure, which cannot be
adjusted any longer. In extreme case this causes to an oscillating at small input values.
1
This dead band is necessary, in order to avoid unrequested activations caused by small variations of the
input signal. If this module is used in pressure controls, the TRIGGER value should be reduced (typical:
1…10).
Eingang / Input
100%
10V
A
u
sg
a
n
g
/
O
u
tp
u
t
MAX
MIN
TRIGGER