4.0 INSTALLATION

4.1  PROTECTION DU MUR ET DU PLAFOND

70.1

!

AVERTISSEMENT

NE REMPLISSEZ L’ESPACE ENTRE LE CONDUIT D’ÉVENT ET LA CHARPENTE AVEC AUCUN TYPE DE MATÉRIAU. 

NE BOURREZ PAS D’ISOLANT NI DE MATÉRIAUX COMBUSTIBLES ENTRE LES ESPACEURS COUPE-FEU DU 

PLAFOND. CONSERVEZ TOUJOURS LES DÉGAGEMENTS REQUIS AUTOUR DES CONDUITS D’ÉVENT ET 

L’ASSEMBLAGE DE L’ESPACEUR COUPE-FEU. INSTALLEZ LES ÉCRANS MURAUX ET LES ESPACEURS COUPE-

FEU TEL QUE SPÉCIFIÉ. SI VOUS NE GARDEZ PAS L’ISOLANT OU TOUT AUTRE MATÉRIAU À L’ÉCART DU 

CONDUIT D’ÉVENT, UN RISQUE D’INCENDIE POURRAIT S’ENSUIVRE.

!

AVERTISSEMENT

AFIN D’ASSURER UN FONCTIONNEMENT SÉCURITAIRE ET ADÉQUAT DE L’APPAREIL, VOUS DEVEZ 

OBSERVER LES INSTRUCTIONS D’ÉVACUATION À LA LETTRE.

TOUS LES JOINTS DES CONDUITS INTÉRIEURS ET EXTÉRIEURS PEUVENT ÊTRE SCELLÉS AVEC DU 

SCELLANT DE SILICONE ROUGE À HAUTE TEMPÉRATURE RTV W573-0002 (NON FOURNI) OU DU 

SCELLANT NOIR À HAUTE TEMPÉRATURE MILL PAC W573-0007 (NON FOURNI) À L’EXCEPTION DU 

RACCORDEMENT DU CONDUIT D’ÉVACUATION À LA BUSE DE L’APPAREIL QUI DOIT ÊTRE SCELLÉ 

AVEC LE SCELLANT MILL PAC.

SI VOUS UTILISEZ DES COLLIERS POUR TUYAU POUR RACCORDER LES COMPOSANTS 

D’ÉVACUATION, VOUS DEVEZ AUSSI INSTALLER TROIS VIS POUR VOUS ASSURER QUE LE 

RACCORDEMENT NE SE DÉFASSE PAS.

NE SERREZ PAS LA GAINE FLEXIBLE. 

RISQUE D'INCENDIE, D'EXPLOSION OU D'ASPHYXIE. SI L'ENSEMBLE DU SYSTÈME DE CONDUIT 

D'ÉVENT N'EST PAS ADÉQUATEMENT SOUTENU, IL RISQUE DE FLÉCHIR OU DE SE SÉPARER. 

UTILISEZ DES SUPPORTS DE CONDUIT ET RACCORDEZ LES SECTIONS DE CONDUITS SELON LES 

INSTRUCTIONS D’INSTALLATION.

RISQUE D'INCENDIE. ÉVITEZ QUE L'ISOLANT TOUCHE AU CONDUIT D'ÉVACUATION. RETIREZ 

L'ISOLANT POUR PERMETTRE L'INSTALLATION DE L'ÉCRAN PROTECTEUR DU GRENIER ET POUR 

MAINTENIR LES DÉGAGEMENTS AUX MATÉRIAUX COMBUSTIBLES.

68.2A

Pour une performance optimale de l’appareil, toutes les courses horizontales devraient avoir une élévation 
minimale de 1/4” (6.4m) par pied/mètre lorsque vous utilisez des composants 

fl

 exibles d’évacuation. A

fi

 n 

d’assurer un fonctionnement sécuritaire et adéquat de l’appareil, vous devez observer les instructions 
d’évacuation à la lettre.

Pour les dégagements du conduit d'évent aux matériaux combustibles, voir la section « DÉGAGEMENTS
MINIMAUX AUX MATÉRIAUX COMBUSTIBLES ».

NOTE: Lorsque les conduits traversent un mur ou un plancher combustible, vous devez utiliser 
l'espaceur coupe-feu / protecteur de conduit d'évacuation fourni avec l'appareil.

Summary of Contents for CHD4N

Page 1: ...supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified instal...

Page 2: ...5 1 FRAMING 26 5 1 1 SEE THRU FRAMING 26 5 1 2 PENINSULA FRAMING 26 5 2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES 27 5 3 INSTALLING CEMENT BOARD 28 5 3 1 FINISHING SUPPORT ADJUSTMENT 29 5 4 NON COMB...

Page 3: ...TERIAL Venting see VENTING section Rating plate see RATING PLATE INFORMATION section Door see DOOR REMOVAL INSTALLATION section Framing see FRAMING section NON COMBUSTIBLE MATERIAL Door see END DOOR I...

Page 4: ...The appliance is a vented gas fired appliance Do not burn wood or other materials in the appliance It is imperative that the control compartments burners and circulating blower and its passageway in t...

Page 5: ...8 511 2mm 17 5 8 447 7mm 14 3 4 374 7mm RIGHT SIDE LEFT SIDE 30 1 4 768 4mm 20 1 8 511 2mm 36 1 8 917 6mm 41 1 8 1044 6mm GAS INLET ELECTRICAL INLET RIGHT SIDE LEFT SIDE 32 1 4 819 2mm 1 3 4 44 5mm 13...

Page 6: ...uld choose a location where the vent will pass through the house without cutting a floor or roof joist If the appliance is installed directly on carpeting vinyl tile or other combustible material othe...

Page 7: ...l and are to be expected If utilizing one of Wolf Steel s trim or surround kits follow the framing instructions and the finishing instructions for removal of the top extension NOTE The protective wrap...

Page 8: ...AREIL PAR LE FABRICANT 352 8 7 e 25 7 1 3 6 87 6 5 200 APPAREIL DE CHAUFFAGE e 0 176 0 1 0 8 6 0 7e5 8 COMBUSTIBLES DESSUS 0 PLANCHER 0 7e6 ARRI RE 0 6686 8 21 8 7 9 17 7e6 7 66286 8 21 8 7 9 17 21 8...

Page 9: ...itial installation NOTE This appliance must be installed with a continuous connection of exhaust and air intake vent pipes Utilizing alternate constructions such as a chimney as part of the vent syste...

Page 10: ...ither the 5 foot 1 5m vent kit GD420 or the 10 foot 3 1m vent kit GD430 For optimum flame appearance and appliance performance keep the vent length and number of elbows to a minimum The air terminal m...

Page 11: ...ust have a minimum vertical rise immediately off the appliance of 57 1447 8mm On all horizontal vent runs ensure that the vent pipe does not slope downward When terminating vertically the vertical ris...

Page 12: ...bove grade The periscope must be installed so that when final grading is completed the bottom air slot is located a minimum of 12 304 8mm above grade The maximum allowable vent length is 10 3 1m for a...

Page 13: ...406 4mm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without openings Q 3 0 9m 3 0 9m See cha...

Page 14: ...l run 3 times the vertical rise equal to or greater than the horizontal run maximum of 40 feet 12 2m maximum of 40 feet 12 2m 3 6 DEFINITIONS 14 2 For the following symbols used in the venting calcula...

Page 15: ...FT 0 8m HT HR HO 4 5 FT 1 4m 2 7 FT 0 8m 7 2 FT 2 2m HT VT 7 2 FT 2 2m 8 FT 2 4m 15 2 FT 4 6m Formula 1 HT VT 7 2 FT 2 2m 8 FT 2 4m Formula 2 HT VT 40 FT 12 2m 15 2 FT 4 6m 40 FT 12 2m Since both form...

Page 16: ...5m HT HR HO 5 5 FT 1 7m 8 1 FT 2 5m 13 6 FT 4 2m HT VT 13 6 FT 4 2m 5 5 FT 1 7m 19 1 FT 5 8m Formula 1 HT 4 2FT 1 3m VT 4 2FT 1 3m VT 4 2 FT 1 3m x 5 5 FT 1 7m 23 1 FT 7m 13 6 FT 4 2m 23 1 FT 7M Form...

Page 17: ...ample V1 5 FT 1 5m V2 10 FT 3 1m VT V1 V2 5 FT 1 5m 10 FT 3 1m 15 FT 4 6m H1 3 FT 0 9m H2 2 5 FT 0 8m HR H1 H2 3FT 0 9m 2 5FT 0 8m 5 5 FT 1 7m HO 03 one 45 three 90 elbows 135 03 45 270 135 5 4 FT 1 6...

Page 18: ...5 4 FT 1 6m HT HR HO 8FT 2 4m 5 4FT 1 6m 13 4FT 4 1m HT VT 13 4FT 4 1m 2 5FT 0 8m 15 9FT 4 8m Formula 1 HT 3VT 3VT 3FT 0 9m x 2 5FT 0 8m 7 5FT 2 3m 13 4 FT 4 1m 7 5 FT 2 3m Since this formula is not m...

Page 19: ...ith this appliance must be used when passing through a combustible wall or floor WARNING FOR SAFE AND PROPER OPERATION OF THE APPLIANCE FOLLOW THE VENTING INSTRUCTIONS EXACTLY ALL INNER EXHAUST AND OU...

Page 20: ...from your authorized dealer distributor See accessories to order specific kits required A Determine the air terminal location cut and frame a square opening as illustrated in the ceiling and the roof...

Page 21: ...t connecting the inner flex pipe and the exhaust flue collar Use only approved flexible vent pipe kits marked Wolf Steel Approved Venting as identified by the stamp only on the outer flex pipe 22 1 EL...

Page 22: ...the exterior wall and make weather tight by sealing with caulking not supplied D If more vent pipe needs to be used to reach the fireplace couple them together as illustrated The vent system must be...

Page 23: ...the roof Do not nail through the lower portion of the flashing Make weather tight by sealing with caulking Where possible cover the sides and top edges of the flashing with roofing material F Alignin...

Page 24: ...supplied with the mobile home appliance Conversion Kits This appliance is field convertible between Natural Gas NG and Propane LP To convert from one gas to another consult your Authorized dealer dis...

Page 25: ...RRIER COMING IN CONTACT WITH THE APPLIANCE BODY IT IS RECOMMENDED THAT THE WALLS OF THE APPLIANCE ENCLOSURE BE FINISHED IE DRYWALL SHEETROCK AS YOU WOULD FINISH ANY OTHER OUTSIDE WALL OF A HOME THIS W...

Page 26: ...e ensuring a height of 10 254mm Stand offs are not used for structural support 42 1 2 1079 5mm 40 3 4 1035 1mm A 42 1 2 1079 5mm A 38 3 8 974 7mm 5 1 FRAMING 5 1 1 SEE THRU FRAMING 5 1 2 PENINSULA FRA...

Page 27: ...materials is required All other clearances within the enclosure including where the vent pipe exits the enclosure are subject to 2 50 8mm to the sides and bottom and 3 76 2mm to the top for horizontal...

Page 28: ...light movement in the normal operation of the appliance If grout is used between the tiles a polymer based grout such as Mapei Ultracolour plus is recommended Primer Paint For a painted surface use a...

Page 29: ...on NOTE Peninsula models have one end support that can also be adjusted by loosening the two screws SIDE VIEW NOTE Framing dimension A will be affected as the finishing supports are adjusted outwards...

Page 30: ...re desired increase the clearance to the sides and top by 2 50 8mm for every additional 1 25 4mm of projection If using an optional surround then 2 50 8mm clearance from the surround is required befor...

Page 31: ...to combustibles are maintained Non combustible material can be used provided the minimum clearances to combustible materials are applied The minimum enclosure volume must be increased by no less than...

Page 32: ...L FRONT ETC ARE CLEARLY MAINTAINED WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL THE PAINT OR LACQUER MUST BE HEAT RESISTANT TO PREVENT DISCOLOURATION 73 1 MANTEL DIMENSIONS Ref Height Depth D 8 20...

Page 33: ...eleased tilt the door forward and out of the bottom door retainer D Reverse this process to install the door IMPORTANT Once latches are engaged test that the door is secure and will not fall forward b...

Page 34: ...TALLATION section B Remove the 6 screws securing the end door in place as shown below Ensure to keep one hand on the door from the inside of the appliance at all times to prevent it from falling C Til...

Page 35: ...the corner of the burner on the left side and place one pin into the log as shown in Figure 1 4 Place the 2 log onto the pin located in the 1 log it should rest in the middle of the right side log sup...

Page 36: ...upport as shown in Figure 10 Place one pin into the 1 log as shown in Figure 10 13 Place the 11 log onto the pin located in the 1 log and let is rest on the left end of the log support as shown in Fig...

Page 37: ...soap drain rinse thoroughly and dry before placing around the burner CLEAN THE GLASS MEDIA PRIOR TO INSTALLATION BEFORE APPLYING THE CLEANED GLASS ENSURE THAT IT IS DRY DO NOT CHANGE OR SUBSTITUTE THE...

Page 38: ...TED FOR DAMAGE TO THE ELECTRICAL CIRCUIT RISK OF ELECTRICAL SHOCK OR EXPLOSION DO NOT WIRE 110V TO THE VALVE OR TO THE APPLIANCE WALL SWITCH INCORRECT WIRING WILL DAMAGE CONTROLS ALL WIRING SHOULD BE...

Page 39: ...d in the bottom corner of the appliance refer to the illustration below NOTE It is recommended that you change the battery at the start of the heating season ELECTRICAL COVER CABLE CONNECTOR L1 BLACK...

Page 40: ...BAGGIE GROUND DFC VALVE ORANGE GREEN GROUND EYELET ON OFF IPI CPI DISCONNECT THESE CONNECTIONS TO THE ON OFF SWITCH AND CONNECT TO AN OPTIONAL THERMOSTAT IPI BOARD DC SUPPLY TRANSFORMER VALVE ELECTRO...

Page 41: ...RE 2 TOURNEZ LA SOUPAPE D ARR T MANUELLE VERS LA DROITE OFF NE FORCEZ PAS TO TURN OFF GAS INSTRUCTIONS POUR COUPER LE GAZ OPERATING INSTRUCTIONS INSTRUCTIONS D OPERATION FOR YOUR SAFETY READ BEFORE OP...

Page 42: ...witching to the standing pilot on those colder days The anti condensation switch standing pilot is located in the control panel Using your finger flip the switch up for standing pilot or down for inte...

Page 43: ...the gas flow Check Pressure Readings Inlet pressure can be checked by turning screw A counter clockwise 2 or 3 turns and then placing pressure gauge tubing over the test point Gauge should read as des...

Page 44: ...flames Compare them to the illustration provided If any flames appear abnormal call a service person FLAME MUST ENVELOP UPPER 3 8 9 5mm TO 1 2 12 7mm OF FLAME SENSOR PILOT BURNER ELECTRODE FLAME SENS...

Page 45: ...distributor G Check that the gasketing on the sides top and bottom of the door is not broken or missing Replace if necessary H If for any reason the vent air intake system is disassembled re install a...

Page 46: ...normal cleaning procedures given but require specialized techniques Contact you local authorized dealer distributor for complete cleaning instructions HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNT...

Page 47: ...n slide the burner off of the orifice and remove from the appliance E To reinstall the burner reverse these steps NOTE When reinstalling the burner ensure that the venturi rests on the orifice D C A R...

Page 48: ...lve and turn to the off position Disconnect the flex connector from the valve You may now lift the valve train out of the appliance 77 3 Vertical installations may display a very active flame If this...

Page 49: ...TO POSITION THE PARTS IN ACCORDANCE WITH THIS MANUAL OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED WITH THIS APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY THIS IS A FAST ACTING THER...

Page 50: ...ROOF 40 W263 0055 ROOF FLASHING 8 12 TO 12 12 PITCH 41 W010 0453 ROOF SUPPORT TERMINAL KITS REF NO PART NO DESCRIPTION 42 GD401 PERISCOPE 43 GD422R 1 ROUND WALL TERMINAL COMPONENTS REF NO HD4ST HD4P...

Page 51: ...LP TO NG 53 GD 850 KT DECORATIVE BRICK PANELS NEW PORT SEE THRU 54 GD 851 KT DECORATIVE BRICK PANELS NEW PORT PENINSULA 55 PRP4ST PORCELAIN REFLECTIVE RADIANT PANELS SEE THRU 56 PRP4P PORCELAIN REFLEC...

Page 52: ...module Check voltage of the transformer under load at the spade connections on the module with the ON OFF switch in the ON position Acceptable readings of a good transformer are between 6 2 and 7 0 v...

Page 53: ...ame rectification Verify correct pilot orifice is installed and inlet gas specifications to manual Remember the flame carries the rectification current not the gas If the flame lifts from pilot hood t...

Page 54: ...or plate See RESTRICTING VENTS section if applicable Main burner flame is a blue lazy transparent flame Blockage in vent Remove blockage In really cold conditions ice buildup may occur on the terminal...

Page 55: ...ntilation excessive venting configurations insufficient makeup air or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans furnaces clothes dryers etc Any d...

Page 56: ......

Page 57: ...tement votre fournisseur de gaz d un t l phone voisin Suivez ses instructions Si vous ne pouvez pas rejoindre votre fournis seur de gaz appelez le service des incendies L installation et l entretien d...

Page 58: ...OD LE BINAIRE 82 5 1 2 OSSATURE DU MOD LE P NINSULE 82 5 2 D GAGEMENTS MINIMAUX AUX MAT RIAUX COMBUSTIBLES 83 5 3 INSTALLATION DU PANNEAU DE CIMENT 84 5 3 1 L AJUSTEMENT DE LA SUPPORT DE FINITIONS 85...

Page 59: ...ON Plaque d homologation voir la section INFORMATION SUR LA PLAQUE D HOMOLOGATION Porte voir la section INSTALLATION ENL VEMENT DE LA PORTE Porte voir la section INSTALLATION DE LA PORTE D EXTR MIT MA...

Page 60: ...en place avant d utiliser l appareil Cet appareil est un appareil gaz ventil Ne br lez pas de bois ou autres mat riaux dans cet appareil Il est primordial de garder propres les compartiments de contr...

Page 61: ...447 7mm 14 3 4 374 7mm 30 1 4 768 4mm 20 1 8 511 2mm ENTR E DU GAZ ENTR E LECTRIQUE C T DROITE C T GAUCHE 36 1 8 917 6mm 41 1 8 1044 6mm 32 1 4 819 2mm 1 3 4 44 5mm 13 1 4 336 6mm 8 1 2 215 9mm 6 1 2...

Page 62: ...ers la maison sans avoir d couper des solives de plancher ou de toit Si l appareil est install directement sur un tapis sur une surface de vinyle ou tout autre rev tement de plancher combustible autre...

Page 63: ...ensembles de moulures ou de contours Wolf Steel suivez les instructions relatives l ossature et les instructions de fi nition pour l enl vement de l extension sup rieure NOTE L emballage de protectio...

Page 64: ...ESSURE 10 WATER COLUMN D U NE COLONNE D EAU R U E T C E L L O C Y PRESSURE 11 WATER COLUMN D U NE COLONNE D EAU ENTATION MINIMALE LY PRESSURE 13 WATER COLUMN D U NE COLONNE D EAU NTATION MAXIMAL E 9 7...

Page 65: ...structions fournies dans l installation initiale NOTE Cet appareil doit tre install de mani re ce que le conduit d vacuation et de prise d air se prolongent sur toute la longueur de la chemin e Toute...

Page 66: ...vents de 10 pieds 3 1m GD430 Pour une performance optimale de l appareil et une apparence optimale des flammes gardez la longueur des vents et le nombre de coudes au minimum La prise d air de la termi...

Page 67: ...a sortie de l appareil d un minimum de 57 pouces 1447 8mm Sur toutes les courses horizontales assurez vous que la pente des conduits d vent ne soit pas descendante Quand elle se termine verticalement...

Page 68: ...du sol L ensemble p riscopique doit tre install de fa on ce que la fente d air du bas soit situ e un minimum de 12 pouces 304 8mm au dessus du niveau du sol La longueur maximale permise de l vent est...

Page 69: ...des murs adjacents incluant les maisons voisines P 8 2 4m 8 2 4m Le toit doit tre incombustible et sans ouvertures Q 3 0 9m 3 0 9m Voir le tableau pour les dimensions d un mur plus large R 6 1 8m 6 1...

Page 70: ...us grande ou gale la course horizontale 3 fois la course verticale plus grande ou gale la course horizontale VACUATION SUR LE DESSUS 3 6 L GENDE 14 2 Les symboles suivants sont utilis s dans le calcul...

Page 71: ...vacuation exige plus qu un coude de 45 et de 90 les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 8 PI 2 4m VT V1 8 PI 2 4m H1 2 5 PI 0 8m H2 2 PI 0 6m HR H...

Page 72: ...13 6 PI 4 2m 5 5 PI 1 7m 19 1 PI 5 8m Formule 1 HT 4 2 VT 4 2 VT 4 2 PI 1 3m x 5 5 PI 1 7m 23 1 PI 7m 13 6 PI 4 2m 23 1 PI 7m Formule 2 HT VT 24 75 PI 7 5m 19 1 PI 5 8m 24 75 PI 7 5m Puisque les deux...

Page 73: ...0 pieds 12 2m Exemple V1 5 PI 1 5m V2 10 PI 3 1m VT V1 V2 5 PI 1 5m 10 PI 3 1m 15 PI 4 6m H1 3 PI 0 9m H2 2 5 PI 0 8m HR H1 H2 3 PI 0 9m 2 5 PI 0 8m 5 5 PI 1 7m HO 0 03 un coude 45 trois coudes 90 135...

Page 74: ...35 5 4 PI 1 6m HT HR HO 8 PI 2 4m 5 4 PI 1 6m 13 4 PI 4 1m HT VT 13 4 PI 4 1m 2 5 PI 0 8m 15 9 PI 4 8m Formule 1 HT 3VT 3VT 3PI 0 9m x 2 5PI 0 8m 7 5PI 2 3m 13 4PI 4 1m 7 5PI 2 3m Puisque cette formul...

Page 75: ...ERS POUR TUYAU POUR RACCORDER LES COMPOSANTS D VACUATION VOUS DEVEZ AUSSI INSTALLER TROIS VIS POUR VOUS ASSURER QUE LE RACCORDEMENT NE SE D FASSE PAS NE SERREZ PAS LA GAINE FLEXIBLE RISQUE D INCENDIE...

Page 76: ...uit d vacuation est en place appliquez un agent d tanch it entre le conduit d vacuation et l espaceur coupe feu C Dans le grenier faites glisser le collet de conduit d vacuation vers le bas afin de re...

Page 77: ...e scell avec le scellant Mill Pac W573 0007 non fourni N utilisez que les ensembles certifi s de gaines flexibles portant l inscription 22 1 COUDE ESPACEURS NE LAISSEZ PAS LA GAINE FLEXIBLE SE TASSER...

Page 78: ...ns le coupe feu tout en conservant le d gagement n cessaire aux mat riaux combustibles En soutenant la terminaison les inscriptions tant l endroit et lisibles fixez la terminaison au mur ext rieur et...

Page 79: ...une marge de 3 4 19 1mm tout autour Fixez le au toit Ne clouez pas travers la partie inf rieure du solin Imperm abilisez le en le scellant avec du calfeutrage Si possible recouvrez les c t s et le bo...

Page 80: ...ppareil en place et fixez le B Si l appareil est muni d un raccord flexible celui ci est con u pour recevoir une conduite de gaz de 1 2 Sans raccord flexible l appareil est con u pour recevoir une con...

Page 81: ...X MAT RIAUX COMBUSTIBLES DOIVENT TRE MAINTENUS L ENCEINTE DE L APPAREIL DOIT RESPECTER LA HAUTEUR MINIMALE REQUISE MESUREZ PARTIR DE LA BASE DE L APPAREIL SI DES ENSEMBLES DE MONTANTS EN ACIER AVEC PA...

Page 82: ...une hauteur de 10 254mm Les espaceurs ne sont pas utilis pour un support structurel 5 1 OSSATURE 5 1 1 OSSATURE DU MOD LE BINAIRE 5 1 2 OSSATURE DU MOD LE P NINSULE 42 1 2 1079 5mm 40 3 4 1035 1mm A 4...

Page 83: ...NON COMBUSTIBLES TELS QUE DE LA BRIQUE DU MARBRE DU GRANITE ETC ASSUREZ VOUS QUE CES MAT RIAUX N EMPI TENT JAMAIS SUR L OUVERTURE DU L APPAREIL Le CHD4 requiert une hauteur d enceinte minimale de 46 1...

Page 84: ...tes avec un additif au latex acrylique tel que Mapei Kerabond Kerlastic pour permettre un l ger mouvement lors du fonctionnement normal de l appareil Si du coulis est utilis entre les carreaux un coul...

Page 85: ...sont quip avec une support de fin qui peut tre ajust en desserrant les deux vis VUE DU C T NOTE Dimension A de l ossature sera affect quand les supports de finitions sont adjuster vers l ext rieur Vo...

Page 86: ...mentaire de projection Si vous utilisez un moulure optionelle un d gagement de 2 24 5mm au dessus du cadre est requis pour une projection maximale de 2 24 5mm Si des projections plus grandes sont requ...

Page 87: ...mat riaux combustibles sont respect s Vous pouvez utiliser un mat riau incombustible pourvu que les d gagements minimaux aux mat riaux combustibles soient appliqu s Le volume minimal de l enceinte doi...

Page 88: ...QU ILS SOIENT R SISTANTS LA CHALEUR AFIN DE PR VENIR LA D COLORATION 73 1 7 7 7 8 7 8 5 PROFONDEUR DE LA TABLETTE Ref Hauteur Plafondeur A B C D E 16 406 4mm 14 355 6mm 12 304 8mm 10 254mm 8 203 2mm 6...

Page 89: ...rifiez que la porte est bien fix e et qu elle ne tombera pas avant de la l cher LATCHES 6 1 INSTALLATION ENL VEMENT DE LA PORTE AVERTISSEMENT LA VITRE PEUT TRE CHAUDE NE TOUCHEZ PAS LA VITRE JUSQU CE...

Page 90: ...ALLATION DES PORTES B Enlevez les 6 vis qui retiennent la porte d extr mit comme illustr ci dessous Pour emp cher la porte de tomber retenez la en tout temps avec votre main depuis l int rieur de l ap...

Page 91: ...acer b che 4 sur l pingle en b che 2 il devrait se reposer sur la base la c t droite comme illustr e en Figure 4 et au vue du c t gauche ci dessous 6 Placer b che 5 sur l pingle la c t droite dans la...

Page 92: ...me illustr e en Figure 10 12 Placer b che 11 sur l pingle en b che 1 il devrait se reposer sur la base la c t gauche comme illustr e en Figure 11 13 Placer la morceau de charbon 12 sur les deux pingle...

Page 93: ...es avec un savon vaisselle doux gouttez les rincez les fond et laissez les s cher NETTOYEZ LES BRAISES VITRIFI ES AVANT L INSTALLATION ASSUREZ VOUS QU ELLES SONT S CHES AVANT DE LES DISPOSER DANS LE P...

Page 94: ...ES LOCAUX EN L ABSENCE DE CODES LOCAUX UTILISEZ LA VERSION COURANTE DU CODE CANADIEN DE L LECTRICIT CSA C22 1 AU CANADA OU LE NATIONAL ELECTRICAL CODE ANSI NFPA 70 AUX TATS UNIS ALLUMEZ TOUJOURS LA VE...

Page 95: ...IQUE L2 BLANC NOIR BLANC TERRE VERT A En cas de panne de courant trouver votre bo tier de piles fourni aux sac du manuel B Installes les 4 piles AA s il n est pas d j install C Conecter le bo tier de...

Page 96: ...TERRE INTERRUPTER ACS IPI D branchez ces connecteurs de l interrupteur marche arr t pour les connecter au thermostat optionnel TRANSFORMATEUR T L COMMANDE ON OFF Cette appareil est fourni avec une sau...

Page 97: ...AREA FOR GAS AND NEXT TO THE FLOOR BECAUSE SOME GAS IS HEAVIER THAN AIR AND WILL SETTLE ON THE FLOOR WHAT TO DO IF YOU SMELL GAS 7851 2 6 72 7 5 3 23 1 1 2 6 2 127 75 72 7 1 33 1 2 127 728 1 75 6 7 2...

Page 98: ...se permanent sur ces jours plus froids L interrupteur anticondensation veilleuse permanente est situ au centre du panneau de commande Avec le doigt basculez l interrupteur vers le haut pour le mode ve...

Page 99: ...CELLER NE SEREZ PAS TROP FORT V rifiez pour des fuites en apliquant une solution d eau savonneuse 39 7 3 8 1 2 9 5mm 12 7mm LA FLAMME DOIT ENVELOPPER LA PARTIE SUP RIEURE DE LA SONDE DE FLAMME DE 3 8...

Page 100: ...LECTRODE LA SONDE DE FLAMME VEILLEUSE 54 1B Il est important d effectuer p riodiquement une inspection visuelle de la flamme de la veilleuse et du br leur Comparez les ces illustrations Si des flammes...

Page 101: ...z votre d taillant autoris G V rifiez si les joints d tanch it sur les c t s le haut et le bas de la porte ne sont pas bris s ou manquants Remplacez si n cessaire H Si pour une raison quelconque le sy...

Page 102: ...r les instructions de nettoyage compl tes LA VITRE CHAUDE CAUSERA DES BR LURES NE PAS TOUCHER LA VITRE AVANT QU ELLE AIT REFROIDI NE JAMAIS LAISSER LES ENFANTS TOUCHER LA VITRE AVERTISSEMENT 10 2 REMP...

Page 103: ...r e ci dessous Glissez le br leur hors de l injecteur puis enl vez le de l appareil E Pour re installer le br leur renverser ces tapes NOTE En r installant le br leur garantir que le venturi se repose...

Page 104: ...is tournez la OFF D branchez le raccord flexible de la soupape Vous pouvez maintenant retirer l assemblage de la soupape de l appareil 77 3 Certaines configurations d vacuation verticales peuvent avoi...

Page 105: ...es de rechange Normalement toutes les pi ces peuvent tre command es chez votre d taillant autoris POUR UN REMPLACEMENT DE PI CE SOUS GARANTIE UNE PHOTOCOPIE DE LA FACTURE ORIGINALE SERA REQUISE AFIN D...

Page 106: ...E TOIT 8 12 12 12 PENTE 41 W010 0453 SUPPORT DE TOIT ENSEMBLE DE TERMINAISON N R F N DE PI CE DESCRIPTION 42 GD401 L ENSEMBLE P RISCOPIQUE 43 GD422R 1 ENSEMBLE DE TERMINAISON MURALE ROND COMPOSANTS N...

Page 107: ...ANNEAUX D CORATIFS SIMILIBRIQUE NEW PORT BINAIRE 54 GD 851 KT PANNEAUX D CORATIFS SIMILIBRIQUE NEW PORT P NINSULE 55 PRP4ST PANNEAUX R FLECTEURS RADIANTS EN PORCELAINE BINAIRE 56 PRP4P PANNEAUX R FLEC...

Page 108: ...ables d un bon transformateur se situent entre 3 2 et 2 8 volts C A Syst me de d pannage piles s il y a panne de courant V rifiez les piles Une connexion desserr e ou causant un court circuit Retirez...

Page 109: ...era le redressement du courant de la flamme V rifiez si le bon injecteur de veilleuse est install et que l alimentation en gaz est conforme aux sp cifications du manuel Souvenez vous que la flamme tra...

Page 110: ...y a lieu La flamme du br leur principal est bleue paresseuse et transparente Syst me d vacuation bloqu Enlevez ce qui obstrue Dans des conditions de froid extr me une accumulation de glace peut se for...

Page 111: ...s par des syst mes m caniques tels que les ventilateurs d vacuation les fournaises les s cheuses de linge etc Tous dommages caus s a l appareil la chambre de combustion l changeur de chaleur aux garni...

Page 112: ......