background image

EN

W415-4006 / A / 03.01.22

47

  

troubleshooting

!

WARNING

•  Always light the pilot whether for the fi rst time or if the gas supply has run out, with the glass door open or 

removed.

•  Turn off gas and electrical power before servicing the appliance.

•  Appliance may be hot. Do not service until appliance has cooled.

•  Do not use abrasive cleaners

27.1A

symptom

problem

test solution

Main burner fl ame is a 

blue, lazy, transparent 

fl ame.
(This is not applicable 

in outdoor appliances)

Blockage in vent.

 -

Remove blockage. In really cold conditions, ice buildup may occur 

on the terminal and should be removed as required. (To minimize this 

from reoccuring, the vent lengths that pass through unheated spaces 

(attics, garages, crawl spaces) should be wrapped with an insulated 

mylar sleeve). 

Incorrect installation.

 -

Refer to “venting” section to ensure correct installation.

Flames are consistently 

too large or too small. 

Carboning occurs.

Appliance is over-fi red or under-

fi red.

 

-

Check pressure readings: 

Inlet pressure can be checked by turning screw (A) counter-clock-

wise 2 or 3 turns and then placing pressure gauge tubing over the 

test point. Gauge should read as described on the chart below. 

Check that main burner is operating on ‘HI’. Outlet pressure can be 

checked the same as above using screw (B). Gauge should read as 

described on the chart below. Check that main burner is operating 

on ‘HI’. 

After taking pressure readings, be sure to turn screws 

clockwise fi rmly to reseal. DO NOT OVER TORQUE.

Leak test with a soap and water solution.

Air shutter improperly adjusted.

 -

Return air shutter to specifi ed opening, see “

venturi adjustments

” 

section in the installation manual.

Carbon is being 

deposited on glass, 

logs, rocks, media, or 

combustion chamber 

surfaces.

Air shutter is blocked.

 -

Ensure air shutter opening is free of lint or other obstructions.

Flame is impinging on the glass, 

logs, rocks, media or combus-

tion chamber.

 -

Ensure the media is positioned correctly in the appliance.

 -

Open air shutter to increase the primary air.

 -

Check the input rate: check the manifold pressure and orifi ce size as 

specifi ed by the rating plate.

 -

Ensure door gaskets are not broken or missing and the seal is tight.

 -

Ensure vent liners are free of holes and well sealed at all joints. 

 -

Check that minimum rise per foot (meters) has been adhered to for 

any horizontal venting.

White / grey fi lm forms.

Sulphur from fuel is being depos-

ited on glass, logs, or combus-

tion chamber surfaces.

 -

Clean the glass with a recommended gas fi replace glass cleaner. 

DO

 

NOT CLEAN GLASS WHEN HOT.

 -

If deposits are not cleaned off regularly, the glass may become 

permanently marked.

Exhaust fumes smelled 

in room, headaches.

Appliance is spilling.

(This is not applicable in outdoor 

appliances).

 -

Check door seal.

 -

Check for exhaust damage.

 -

Check that venting is installed correctly.

 -

Room is in negative pressure; increase fresh air supply.

INSERT 

PHOTO 

OF VALVE 

HERE

symptom

problem

test solution

Pilot will not light. Makes 

noise with no spark at 

pilot burner.

Wiring: short, loose, or damaged 

connections

(poor fl ame rectifi cation).

 -

Verify the thermocouple/sensor is clean and the wiring is undamaged.

 -

Verify the interrupter block is not damaged or too tight. Verify 

connections from pilot assembly are tight; also verify the connections 

are not grounding out to any metal. (Remember, the fl ame carries the 

rectifi cation current, not the gas. If fl ame lifts from pilot hood, the circuit 

is broken. A wrong orifi ce or too high of an inlet pressure can cause the 

pilot fl ame to lift)*. The sensor rod may need cleaning.

No signal from remote with no 

pilot ignition.

 -

Reprogram receiver code.

 -

Replace receiver.

Poor grounding.

 -

Verify the valve / pilot assembly are properly grounded

Improper switch wiring.

 -

Troubleshoot the system with the simplest 

on/off

 switch.

Dirty, painted, or damaged pilot 

and/or dirty sensor rod.

 -

Clean sensor rod with a green Scotch-Brite™ pad to remove any 

contamination that may have accumulated. Verify continuity with 

multimeter with ohms set at the lowest range.

Pilot sparks but will 

not light.

Gas supply.

 - Verify that the incoming gas line ball valve is “open”.

 - Verify that the inlet pressure reading is within acceptable 

limits, inlet pressures must not exceed 13” W.C. (32.4mb).

Out of propane gas.

 - Fill the tank.

Pilot supply line may contain 

air.

 - Repeat ignition process several times or purge the pilot 

supply line.

Incorrect wiring / grounding.

 - Ensure correct polarity of wiring of thermocouple (if 

equipped).

 - Verify pilot assembly / valve are properly grounded.

Receiver (if equipped).

 - Reset program: hold reset button on receiver and wait for 2 

beeps. Release after second beep. Press small fl ame button 

on remote within 20 seconds, you will hear an additional 

beep (this signals a successful reset).

 - Replace receiver.

Valve.

 - Check valve and replace if necessary (Do not to overtighten 

thermocouple).

Burner continues to 

spark and pilot lights 

but main burner 

does not light.

Short or loose connection in 

sensor rod.

 - Verify all connections. Verify the connections from the pilot 

assembly are tight. Also, verify these connections are not 

grounding out to any metal.

Dirty, painted, or damaged 

pilot assembly components.

 - Clean using a green Scotch-Brite™ pad to remove any 

contamination that may have accumulated on the sensor 

rod, pilot hood, ignitor, or fl ame sensor. Verify continuity with 

multimeter with ohms set at the lowest range.

Remote wall switch 

is in “

off

” position; 

burner comes on.

Wall switch mounted upside 

down.

 - Reverse.

Remote wall switch and/or 

wire is grounding.

 - Replace. 

 - Check for ground (short); repair ground or replace wire.

Faulty wire

 - Replace. 

Remote and / or 

receiver is not 

functioning properly.

Remote controls lights but 

no spark or fl ame. (Remote is 

locked out).

 -

Reset by turning power source off then on.

Receiver or remote has low battery.

 -

Replace batteries.

Appliance functions but does not 

respond to receiver / remote 

 -

Ensure appliance is being operated by the same device that turned it 

on. Remote controls function if appliance was turned on by remote. 

Receiver controls function if appliance was turned on by receiver.

Error with synchronizing.

 -

Reset receiver and remote.

Remote too far away from receiver.

 -

Refer to “wiring diagram” section.

Wire connector pins are bent.

 -

Straighten pins.

Valve wiring is damaged.

 -

Replace valve.

symptom

problem

test solution

The following applies specifi cally to the SIT system only:

Pilot will not light. 

Makes no noise with 

no spark at pilot 

burner. (Lights and 

blower operate, if 

equipped).

Ignition box has been locked 

out.

Choose one of the 3 methods below to reset the system.

1. 

To reset ignition box when locked out. Turn off power supply 

and remove batteries (if used) from the back up battery pack.

2. 

To reset the DFC Board when the board goes into a lock 

out condition and the LED is blinking 3 times using the 

transmitter 

on/off

 button:

Step 1:

 Turn the system off by pressing the 

on/off

 

button to turn the system off.

Step 2:

 After approximately 2 seconds press the 

on/

off

 button on the transmitter again. The DFC Board will 

reset and the ignition sequence will start again.

3. 

To reset the DFC Board when the board goes into a lock out 

condition and the LED is blinking 3 times by cycling fl ame:

Step 1:

 In the manual fl ame control mode, use the down 

arrow button to reduce the fl ame to off, indicated by the 

word OFF displayed on the transmitter LCD screen.

Step 2:

 Wait approximately 2 seconds and press the up 

arrow button, the ignition sequence will start.

symptom

problem

test solution

The following applies specifi cally to the Maxitrol system only:

Pilot lights. 

No gas fl ow.

Manual override knob is in the 

“MAN” position.

 -

Turn the knob to the “ON” position. 

Valve is not functioning properly.

 -

Valve is on pilot fl ow. Turn to the high setting, double click the large 

fl ame button on the remote.

 -

Replace valve. Do not overtighten.

No spark after pilot 

ignition. Valve turns off 

in one minute and does 

not operate.

Minimal voltage from thermocou-

ple or resistance in circuit ports 

(Parts include: “ON/OFF” switch, 

receiver, thermocurrent connec-

tions or temperature switches).

 -

Measure the voltage, it should read a least 5mV. The spade 

connector is on the outer surface beside the magnet nut. Verify with 

manufacturer the drop time, after thermocouple is heated measure 

the drop time.

No pilot ignition 

(5 second continuous 

beep).

Switch is in “OFF” position on 

the valve.

 -

Switch to “ON“ position.

Wiring is loose.

 -

Ensure wiring is properly secured.

Receiver (if equipped).

 -

Reset program: hold reset button on receiver and wait for 2 beeps. 

Release after second beep. Press small fl ame button on remote 

within 20 seconds, you will hear an additional beep (this signals a 

successful reset).

 -

Replace receiver.

Wire connector pins are bent.

 -

Straighten pins.

Valve wiring is damaged.

 -

Replace valve.

Burner continues to 

spark and pilot lights 

but main burner does 

not light.

Connections are loose or dam-

aged.

 -

Verify the thermocouple is clean and the wiring between it and the 

valve is undamaged.

 -

Verify the interrupter block is not damaged or too tight.

Remote and / or re-

ceiver  is not function-

ing properly.

Receiver not communicating 

properly.

 -

Hold reset button on the receiver and wait for 2 beeps. Release after 

second beep. Press the small fl ame button on the remote within 

20 seconds, you will hear an additional beep (this signals that the 

receiver has been successfully reset).

Motor is turning, 

frequent beeping 

occurs.

Receiver batteries low.

 - Replace batteries.

*Maximum inlet pressure not to exceed 13” w.c.

Pressure

Natural Gas

(inches)

Natural Gas

(millibars)

Propane

(inches)

Propane

(millibars)

Inlet 

*7”

(minimum 4.5”)

17.4mb

(minimum 11.2mb)

13”

(minimum 11”)

32.4mb

(minimum 27.4mb)

Outlet 

3.5”

8.7mb

10”

24.9mb

If back up batteries are installed, they must also be removed to 

re-program

note:

Starting from 

off

, press the 

on 

button on the transmitter. After approximately 4 seconds 

on/off 

button is pressed, the ignition 

board will start the spark. The atempt for ignition will last approximately 60 seconds. If there is no fl ame ignition (rectifi cation), 

the board will stop sparking and the board will go into lock out.

note:

symptom

problem

test solution

Lights or blower 

won’t function (if 

equipped).

Control module switch in 

wrong position.

 - Verify ON/OFF switch is in the “I” position which denotes on.

COM switch is unplugged.

 - Verify “COM” switch is plugged into the front of the control 

module.

Flames are very 

aggressive.

Door is ajar.

 - Ensure door is secured properly.

Venting action is too great.

 - Check to ensure venting is properly sealed or restrict vent 

exit with restrictor plate. (Not available in all appliances).

Appliance won’t per-

form any functions.

No power to the system.

 - Check breaker to verify it’s in the “

on

” position.

Receiver switch in wrong 

position (if equipped).

 - Verify that the 3 position switch on the receiver is in the 

remote position (middle).

Transmitter isn’t operational.

 - Check battery power and battery orientation.

Summary of Contents for CDVS280-1NEA

Page 1: ...call the re department Installation and service must be performed by a quali ed installer service agency or the supplier This appliance may be installed in an aftermarket permanently located manufact...

Page 2: ...touching hot surfaces Even after the appliance is off it will remain hot for an extended period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect c...

Page 3: ...and repair should be done by a qualified service person It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean For outdoor products only this...

Page 4: ...tallation 22 appliance vent connection 23 natural vent specifics 23 chimney installation 23 combustion air 23 installing natural vent 24 natural vent 24 adding vent sections 25 gas installation 26 fin...

Page 5: ...ected This appliance may be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated o...

Page 6: ...bathroom unless the unit is a direct vent sealed combustion product The installation must conform with local codes or in absence of local codes the National Gas and Propane Installation Code CSA B149...

Page 7: ...devant entretien contact avec les flammes autre que celui qui est fourni avec cet appareil par le fabricant Maximum horizontal extension X See installation manual for greater extensions minimum vent...

Page 8: ...ral information GAS LINE ACCESS HOLE LOCATED IN PEDESTAL BASE 26 3 4 680mm 22 1 2 572mm 11 1 4 286mm 7 178mm AIR INTAKE 10 254mm 12 305mm 17 3 4 451mm 18 1 2 470mm 5 1 2 127mm 4 102mm FLUE SAFETY BARR...

Page 9: ...a continuous connection of exhaust and air intake vent pipes Utilizing alternate constructions such as a chimney as part of the vent system is not permitted This template must be used in conjunction w...

Page 10: ...runs may have a 0 rise per foot or 0mm rise per meter however for optimum performance it is recommended that all horizontal runs have a minimum 1 4 rise per foot or 21mm rise per meter using flexible...

Page 11: ...pleted the bottom air slot is located a minimum 12 305mm above grade The maximum allowable vent length including both rise and run is 10 3m for a fireplace and 8 2m for a stove An insulation sleeve is...

Page 12: ...m an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without openings Q 3 0 9m 3 0 9m See chart for wider wall dimensions R 6 1 8m 6 1 8m See chart for deep...

Page 13: ...f 40 feet 12 2m Horizontal run vertical rise to maximum of 40 feet 12 2m Vertical Termination 11 1 For the following symbols used in the venting calculations and examples are greater than equal to or...

Page 14: ...4m H1 2 5 FT 0 8m H2 2 FT 0 6m HR H1 H2 2 5 FT 0 8m 2 FT 0 6m 4 5 FT 1 4m HO 03 three 90 elbows 90 03 270 90 5 4 FT 1 7m HT HR HO 4 5 FT 1 4m 5 4 FT 1 7m 9 9 FT 3m HT VT 9 9 FT 3m 11 FT 3 4m 20 9 FT...

Page 15: ...16 7FT 5 1m Formula 1 HT 4 2 VT 4 2 VT 4 2FT 1 3m x 6FT 1 8m 25 2 FT 7 7m Formula 2 HT VT 24 75 FT 7 5m 16 7 FT 5 1m 24 75 7 5m Since both formulas are met this vent configuration is acceptable 90 V1...

Page 16: ...V1 5 FT 1 5m V2 6 FT 1 8m V3 10 FT 3 1m VT V1 V2 V3 5FT 1 5m 6FT 1 8m 10FT 3 1m 21FT 6 4m H1 8 FT 2 4m H2 2 5 FT 0 8m HR H1 H2 8FT 2 4m 2 5FT 0 8m 10 5 FT 3 2m HO 03 four 90 elbows 90 03 360 90 8 1 F...

Page 17: ...1 H2 6FT 1 8m 2FT 0 6m 8 FT 2 4m HO 03 four 90 elbows 90 03 360 90 8 1 FT 2 5m HT HR HO 8FT 2 4m 8 1FT 2 5m 16 1FT 4 9m HT VT 16 1FT 4 9m 4 5FT 1 4m 20 6 FT 6 3m Formula 1 HT 3VT 3VT 3FT 0 9m x 4 5FT...

Page 18: ...intake flex liner and the exhaust collar must be connected to the exhaust flexible liner Both Simpson Duravent and Selkirk co linear to co axial adaptors have been approved on this appliance Follow v...

Page 19: ...xhaust and intake vent pipe joints must be sealed using red RTV high temp silicone sealant W573 0002 not supplied or black high temp Mill Pac W573 0007 not supplied If using pipe clamps to connect rig...

Page 20: ...ough a roof Installation kits for various roof pitches are available from your authorized dealer distributor See the accessories section to order specific kits required A Determine the air terminal lo...

Page 21: ...the exterior wall and make weather tight by sealing with caulking not supplied D If more vent pipe needs to be used to reach the fireplace couple them together as illustrated The vent system must be s...

Page 22: ...er the air terminal connector leaving a min 3 4 19mm of the air terminal connector showing above the top of the flashing Slide the flashing underneath the sides and upper edge of the shingles Ensure t...

Page 23: ...installing 8 10 or 8 11 venting Seal the joint and screw holes using Mill Pac sealant W573 0007 not supplied C Run a bead of high temperature red RTV silicone sealant W573 0002 not supplied around the...

Page 24: ...t the protective bushing Pull both spill switch wires through the bushing taking up any slack Replace the cover plate FOR Disconnect one of the black on off switch wires connected to the control modul...

Page 25: ...e chimney extends more than 5ft 1 5m above the roof it must be secured using a roof brace or guide wires A raincap must be installed to avoid internal damage and corrosion 3 FT 1m MIN 3 FT 1m MIN 10 F...

Page 26: ...test pressures above 1 2 PSIG Valve settings have been factory set do not change Installation and servicing to be done by a qualified installer Move the appliance into position and secure If equipped...

Page 27: ...to the touch Doors are heavy and fragile so handle with care 47 2 45 1 WARNING Risk of fire Never obstruct the front opening of the appliance The front of the appliance must be finished with any non...

Page 28: ...me Snap the rear handle hook to lock the latch closed To open the door repeat in reverse order HINGE PIN BUSHING CATCH SLOT DOOR LATCH WARNING Glass may be hot Do not touch glass until cooled If equip...

Page 29: ...Ensure the left support tab and the two right support tabs are bent down to ensure the front burner flame does not get sucked beneath the front log 5 3 log placement WARNING Failure to position the lo...

Page 30: ...sed to direct flame Use only certified glowing embers and PHAZER logs available from your local authorized dealer distributor WARNING Completely blocking the burner ports can cause an incorrect flame...

Page 31: ...it 1 25mm into the hole located above the spill switch bracket on the adaptor D Venting action is satisfactory if the flame stays lit Venting action is unsatisfactory if the flame extinguishes E If v...

Page 32: ...nsmitter to the receiver It is recommended that the distance between the transmitter and receiver never exceeds 20 and 10 if the receiver is located within the fireplace s outer or inner cavity surrou...

Page 33: ...Turn off the gas and disconnect the electrical power supply from the appliance C Locate the battery housing inside the valve compartment D Install 2 D alkaline batteries not supplied into the battery...

Page 34: ...3 volt battery pack supplied Do not use any other type of battery pack note BATTERY HOLDER GAS VALVE PILOT ASSEMBLY IGNITION MODULE PILOT GAS LINE I S AC ADAPTOR BATTERY RELAY WIRE HARNESS MAIN BURNE...

Page 35: ...er Set thermostat to desired setting if equipped I Turn on the remote wall switch to the appliance J If the appliance will not operate follow instructions TO TURN OFF GAS and call your service technic...

Page 36: ...ot assembly or replace Fine emery cloth or a synthetic scrub pad such as Scotch Brite can be used to remove the paint from the pilot hood electrode and flame sensor Maximum inlet pressure not to excee...

Page 37: ...all a service person ADD IMAGE HERE 36 1 thermocouple 9 5m Flame must envelop upper 3 8 to 1 2 12 7mm 9 5mm of Flame sensor SIT ELECTRONIC IGNITION 3 8 1 2 9 5mm 12 7mm La fla la s 3 8 1 2 9 5mm 12 7m...

Page 38: ...he burner 5 If your appliance is equipped with a safety barrier cleaning may be necessary due to excessive lint dust from carpeting pets etc simply vacuum using the brush attachment 6 If your applianc...

Page 39: ...ld be performed by a qualified service technician The firebox becomes very hot during operation Let the appliance cool completely or wear heat resistant gloves before conducting service Never vacuum h...

Page 40: ...rfere with the blower operation Re secure the air intake manifolds INSTALLATION THROUGH THE FIREBOX REPLACEMENT BLOWER ACCESS GASKET IS REQUIRED Turn off the electrical power and the gas supply to the...

Page 41: ...r warranty replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of appli...

Page 42: ...Charcoal embers GL 620 Left side log GL 620 W550 0001 W135 0061 11 12 10 9 5 6 7 8 Yes Glowing embers GL 620 W361 0016 Yes ON OFF switch W660 0009 Trivet W010 2511 Yes Right side log GL 620 W135 0060...

Page 43: ...4 14 14 12 14 12 1 2 2 3 2 3 5 4 1 11 12 12 13 2 Yes W010 2900 Pilot assembly P Yes Yes 14 14 W290 0043 Burner gasket Yes W455 0068 Pilot orifice 35 P 10 Yes W190 0135 Control module W750 0463 Wire ha...

Page 44: ...95 SER Safety barrier assembly 1 Stocked 23 23 23 5 23 4 23 3 23 1 7 6 23 2 23 8 AR28SS W660 0081 Wall mounted thermostat F45 F60 Hand held remote control 6 3 3 GS328SSB Satin chrome plated door GS328...

Page 45: ...ns Flame is impinging on the glass logs rocks media or combus tion chamber Ensure the media is positioned correctly in the appliance Open air shutter to increase the primary air Check the input rate c...

Page 46: ...equipped Reset program hold reset button on receiver and wait for 2 beeps Release after second beep Press small flame button on remote within 20 seconds you will hear an additional beep this signals a...

Page 47: ...nimal voltage from thermocou ple or resistance in circuit ports Parts include ON OFF switch receiver thermocurrent connec tions or temperature switches Measure the voltage it should read a least 5mV T...

Page 48: ...h as rooftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which may or may not be caused b...

Page 49: ...A 03 01 22 49 service history Appliance Service History This appliance must be serviced annually depending on usage Date Dealer Name Service Technician Name Service Performed Special Concerns 15 0 ser...

Page 50: ...Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41030 7200 Route Transcanadienne Montr al Qu bec Canada H4T 1A3 P 1 866 820 8686...

Page 51: ...tall dans une maison pr fabriqu e mobile d j install e demeure si les r glements locaux le permettent Cet appareil doit tre utilis uniquement avec le type de gaz indiqu sur la plaque d homologation Ce...

Page 52: ...ts et loin des meubles et des rideaux Les meubles ou autres objets doivent tre gard s une distance d au moins 4 pieds 1 22m du devant de l appareil Assurez vous de disposer de mesures de s curit ad qu...

Page 53: ...on devraient tre effectu es par un technicien qualifi Il est imp ratif que les compartiments de contr le le br leur et les passages de circulation d air soient gard s propres afin de fourni une combus...

Page 54: ...type B 72 3 3 3 vent de type naturel 72 3 3 5 ajout de sections d vents 73 4 0 branchement du gaz 74 5 0 finitions 75 5 1 installation enl vement de l cran de protection 75 5 2 ouverture et fermeture...

Page 55: ...permanente sauf si les codes locaux l interdisent Cet appareil ne doit fonctionner qu avec le type de gaz sp cifi sur la plaque d homologation Cet appareil ne peut tre converti un autre type de gaz m...

Page 56: ...ntation il doit tre connect une r ceptacle correctement mise la terre La fiche de mise la terre ne doit pas tre retir du cordon d alimentation Ce qui suit ne s applique pas aux foyers encastr s tant q...

Page 57: ...face X Tablette X de l ouverture de l appareil WARNING Do not add any material to the appliance which will come in contact with the flames other than that supplied by the manufacturer with the applian...

Page 58: ...LE TROU D ACC S DE LA CONDUITE DE GAZ EST SITU DANS LA BASE DU PI DESTAL PRISE D A IR BUSE 26 3 4 680mm 22 1 2 572mm 11 1 4 286mm 7 178mm 10 254mm 12 305mm 17 3 4 451mm 18 1 2 470mm 5 1 2 127mm 4 102...

Page 59: ...d inspecter visuellement le raccord des vents l appareil apr s que l appareil est install Utilisez un espaceur coupe feu un protecteur de conduit d vacuation ou un cran thermique de grenier lorsque l...

Page 60: ...t au dessus d un trottoir ou d une entr e pav e situ e entre deux maisons unifamiliales et servant aux deux maisons Les codes ou r glementations locaux peuvent exiger des d gagements diff rents Ne lai...

Page 61: ...on ci dessous de l vacuation sur le sessus utiliser seulement lorsqu ils sont fournis avec l appareil Un manchon isolant n est pas requis avec une appareil po le 8 1 VACUATION SUR LE DESSUS VACUATION...

Page 62: ...u pour les dimensions d un mur plus large R 6 1 8m 6 1 8m Voir la tableau pour les dimensions d un mur plus profond La terminaison ne doit pas tre install e sur quelconque mur ayant une ouverture entr...

Page 63: ...se horizontale la course verticale jusqu un maximum de 40 12 2m Terminaison verticale 11 1 Les symboles suivants sont utilis s dans le calcul et les exemples d vacuation plus grand que plus grand ou g...

Page 64: ...HR HO 4 5 PI 1 4m 5 4 PI 1 7m 9 9 PI 3m HT VT 9 9 PI 3m 11 PI 3 4m 20 9 PI 6 4m Formule 1 HT VT 9 9 PI 3m 11 PI 3 4m Formule 2 HT VT 40 PI 12 2m 20 9 PI 6 4m 40 PI 12 2m Puisque les deux formules son...

Page 65: ...3m 6PI 1 8m 16 7PI 5 1m Formule 1 HT 4 2 VT 4 2 VT 4 2PI 1 3m x 6PI 1 8m 25 2PI 7 7m 10 7PI 3 3m 25 2 PI 7 7m Formule 2 HT VT 24 75 PI 16 7PI 5 1m 24 75 7 5m Puisque les deux formules sont respect es...

Page 66: ...VT 40 pieds 12 2m Exemple V1 5 PI 1 5m V2 6 PI 1 8m V3 10 PI 3 1m VT V1 V2 V3 5PI 1 5m 6PI 1 8m 10PI 3 1m 21 PI 6 4m H1 8 PI 2 4m H2 2 5 PI 0 8m HR H1 H2 8 PI 2 4m 2 5 PI 0 8m 10 5 PI 3 2m HO 0 03 qua...

Page 67: ...m 2PI 0 6m 8 PI 2 4m HO 0 03 quatre coudes 90 90 0 03 360 90 8 1 PI 2 5m HT HR HO 8 PI 2 4m 8 1 PI 2 5m 16 1 PI 4 9m HT VT 16 1PI 4 9m 4 5PI 1 4m 20 6 PI 6 3m Formule 1 HT 3VT 3VT 3PI 0 9m x 4 5PI 1 4...

Page 68: ...tre raccord au conduit flexible de prise d air et le collet d vacuation de la terminaison au conduit flexible d vacuation Les adaptateurs colin aire coaxial Simpson Duravent et Selkirk sont approuv s...

Page 69: ...oints des conduits doivent tre scell s avec du scellant de silicone rouge haute temp rature RTV W573 0002 non fourni ou du scellant noir haute temp rature Mill Pac W573 0007 non fourni l exception du...

Page 70: ...l ouverture Assurez vous que l espaceur coupe feu et l cran protecteur conservent le d gagement n cessaire aux mat riaux combustibles C Fixez en place l espaceur coupe feu l aide des quatre vis longu...

Page 71: ...ce entre le diam tre ext rieur de l vent et l espaceur coupe feu DOIT tre compl tement scell avec du RTV haute temp rature Pour les appareils 4 7 Lors d utiliser l vacuation flexible utiliser l ensemb...

Page 72: ...necteur de terminaison en laissant un minimum de 3 4 19 1mm de connecteur de terminaison visible au dessus du haut du solin Glissez le solin sous les c t s et le bord sup rieur des bardeaux Assurez vo...

Page 73: ...ENT 1 1 4 31 8mm chevauchement TOP VENT FLEX TOP VENT RIGID FLEX Scellant haute temp rature 8 X 1 2 vis autoperceuses 8 X 1 2 vis autoperceuses 8 X 1 2 vis autoperceus Scellant haute temp rature Scell...

Page 74: ...tez les fils des deux interrupteurs d coulement par le trou de la bague en s assurant qu ils sont bien tendus Replacez la plaque d acc s POUR MILLIVOLT D branchez un des fils noir de l interrupteur pu...

Page 75: ...5m elle devra tre fix e au toit avec un support de toit ou des brides de s curit Un chapeau de chemin e devra tre install afin d viter des dommages internes et la corrosion 3 PI 1m MIN 3 PI 1m MIN 10...

Page 76: ...st me lorsque les pressions d essai exc dent 1 2 LB PO2 3 5 KPA Les r glages de la soupape ont t faits en usine ne les modifiez pas L installation et l entretien doivent tre effectu es par un installa...

Page 77: ...n gratignez pas la porte vitr e Ne faites pas fonctionner l appareil lorsque la porte vitr e est enlev e fissur e bris e ou gratign e Les mat riaux de fa ade ou de finition ne doivent jamais empi ter...

Page 78: ...Pour vous assurer que la porte est en position horizontale il sera peut tre n cessaire de la soulever lorsque vous la fixez Pour ouvrir la porte suivez les instructions en sens inverse TIGE CHARNI RE...

Page 79: ...2 3 4 1 2 3 4 NOTE Assurez vous que la patte de support gauche et les deux pattes de support droite sont pli vers le bas pour assurez que la flamme du br leur avant n est pas aspir en dessous du b ch...

Page 80: ...raises incandescentes et b ches PHAZERMD disponible de votre d taillant autoris locale AVERTISSEMENT Obstruez pas ni fermer les orifices du br leur Le blocage des orifices du br leur peut cr er une fl...

Page 81: ...de 1 25mm l int rieur du trou situ au dessus du support de l interrupteur d coulement sur l adaptateur D Le fonctionnement de l vacuation est satisfaisant si la flamme reste allum e mais insatisfaisan...

Page 82: ...oyer autour d un encastr Des piles faibles r duiront galement la distance de fonctionnement ON OFF AFFICHEUR INDICATEUR DE SIGNAL AMPOULE DU THERMOSTAT TEMP RATURE DE R GLAGE DU THERMOSTAT INDICATEUR...

Page 83: ...la sauvegarde de piles dedans le compartiment de soupape D Installez 2 piles alcalines D non fournies dans la sauvegarde de piles Assurez vous que les fins positives et les fins n gatives corresponden...

Page 84: ...l ou la soupape de gaz l alimentation lectrique 110 V AVERTISSEMENT I S 1 4 3 16 3 8 1 2 9 5mm 12 7mm LA FLAMME DOIT ENVELOPPER LA PARTIE SUP RIEURE DE LA SONDE DE FLAMME DE 3 8 9 5mm 1 2 12 7mm LECTR...

Page 85: ...errupteur murale de l appareil la position ON J Si l appareil ne fonctionne pas suivre les instructions de couper l alimentation de gaz et puis appelez votre technicien de service ou fournisseur de ga...

Page 86: ...ture des pressions assurez vous de tourner fermement les vis vers la droite pour sceller Ne serrez pas trop fort V rifiez pour des fuites en appliquant une solution d eau savonneuse Avant d effectuer...

Page 87: ...flamme doit envelopper la thermocouple et thermopile de 3 8 1 2 9 5mm 12 7mm SIT MILLIVOLT 3 8 1 2 9 5mm 12 7mm Flame must envelop upper 3 8 to 1 2 12 7mm 9 5mm of thermocouple La flamme doit envelopp...

Page 88: ...igne le br leur 5 Si votre appareil est fourni avec une cran de protection le nettoyage peut tre n cessaire en raison d un exc s de poussi re peluches des tapis animaux etc utilisez un l attachement d...

Page 89: ...rez nettoyer le capteur de flamme l aide d une morceau de laine d acier ou un tampon r curage Scotch BriteMD afin de retirer toute trace d oxydation Nettoyez l assemblage du pilote l aide d un aspirat...

Page 90: ...ez les collecteurs de prise d air INSTALLATION DEPUIS LA CHAMBRE DE COMBUSTION UN JOINT D TANCH IT DE REMPLACEMENT POUR LA PORTE D ACC S DE LA SOUFFLERIE EST REQUIS Coupez l alimentation lectrique et...

Page 91: ...ement de pi ce sous garantie une photocopie de la facture originale sera requise afin de pouvoir honorer la demande Lorsque vous commandez des pi ces donnez toujours l information suivante Mod le et n...

Page 92: ...9 5 11 12 13 14 19 16 19 19 19 20 7 10 15 4 4 19 18 19 17 19 19 21 22 19 23 W390 0001 Loquet de porte X2 W380 0002 Interrupteur vitesse variable seulement bouton GZ552 Soufflerie KB 35 Interrupteur vi...

Page 93: ...4 14 14 13 14 14 14 12 14 12 1 2 2 3 2 3 5 4 1 11 12 12 13 2 Oui W010 2900 Assemblage de pilote P Oui Oui 14 14 W290 0043 Joint de br leur Oui W455 0068 Injecteur de pilote 35 P 10 Oui W190 0135 Modul...

Page 94: ...565 0195 SER 1 En stock AR28SS W660 0081 F45 F60 8 3 3 W361 0239 BULK GS200 SS GS328SSB GS328KSB 4 5 6 7 ANI K 2 Thermostat mural num rique T l commande manuelle L cran de protection GS328 Andirons en...

Page 95: ...au savonneuse Le volet d air est r gl incorrectement Voir la section r glage du venturi pour le r glage de l ouverture du volet d air dans le manual d installation Du carbone se d pose sur la vitre le...

Page 96: ...terre Assurez le bon polarit du thermocouple si fourni V rifiez si les assemblages de le veilleuse et de la soupape sont bien mis la terre R cepteur si quip R initialisez la programme tenir le bouton...

Page 97: ...pour le syst me de SIT seulement La veilleuse ne s allume pas Aucun bruit et aucune tincelle au br leur de la veilleuse Les lumi res et la souffle rie fonctionnent si quip La bo te d allumage a t ver...

Page 98: ...les ventilateurs d vacuation les fournaises les s cheuses de linge etc Tous dommages caus s a l appareil la chambre de combustion l changeur de chaleur aux garnitures de laiton ou autres composants p...

Page 99: ...historique d entretien FR Historique de service de l appareil Cet appareil doit tre entretenu annuellement selon son usage Date D taillant Nom du Technicien Travail Effectu Probl mes Particuliers 15 0...

Page 100: ...Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41030 7200 Route Transcanadienne Montr al Qu bec Canada H4T 1A3 P 1 866 820 8686...

Reviews: