Metasys Ethernet networks use a default value of 11001 for the UDP
port address (UDPPA) and NCMs automatically configure themselves
to use this value. Since each N1 network must have a unique UDPPA,
other values must be used when multiple N1 networks are involved.
Any UDPPA from 2050 to 65535 (except 11002) can be used, but it is
best to start numbering networks in a Multinetwork configuration with
11003 and continue sequentially.
Ask the Network Administrator or the customer’s Ethernet network
support provider if they know of any reason why any UDDPA you
have chosen should not be used on their network.
For more information, refer to the following document:
LIT-6360175 N1 Ethernet/IP Network Technical Bulletin.
Appendix
F
:
UDP Port Address Assignments
TD060100-0MA
4
9