UM-15094500-AA0
Page 21
Item
Mnemonic
Description
°C Scale
°F Scale
Step
Default
Range
Default
Range
E30
tyPE
Control Type
2
1~2
2
1~2
1: C&H
Manual
2: C&H Auto
NOTE: Cool
only and
Heat only
types
E31
OPL2
Minimum Output for AO2
(not used)
E32
SPA2
Span Offset for AO2
(not used)
E33
Hrtr
Communication Heartbeat Minimum
Rate
60
10~3600 60
10~3600 10s
E34
rhPb
Humidity Control PB
E35
rhdF
Humidity Control Diff.
E36
Pb-2
E37
CO2F
CO2 Offset Value
E38
AFtH
After Hour Extension Time
(not used)
E39
VALL
Not Used
E40
VALH
Not Used
E41
OPts
Options
E42
dlAb
DI contact Definition
E43
Hrt
Communication Heartbeat Flip-Flop
0
0/1
0
0/1
0: Off 1: On
E44
CSPL
Minimum Cooling Temperature Setpoint
18.0 0.0-50.0 65.0 32.0-
122 0
0.1 (°C/°F)
E45
HSPH
Maximum Heating Temperature Setpoint
25.0 0.0-50.0 77.0 32.0-
122 0
0.1 (°C/°F)
E46
nFAn
Minimum Fan Output
(not used)
E47
hFAn
Maximum Fan Output
(not used)
E48
FAnL
Low Fan Speed Setting
(not used)
E49
FAn2
Med. Fan Speed Setting
(not used)
E50
FAnH
Hi Fan Speed Setting
(not used)
E51
ObAb
Reversing Valve Polarity
0
0/1
0
0/1
Cooling/Heatin
g
0: N.O./N.C.
E52
OFFt
Minimum Off Time
180
0~600
180
0~600
5 (seconds)
E53
On-t
Minimum On Time
0
0~600
0
0~600
5 (seconds)
E54
It-2
Integral Time and Output Cycle Time 2
E55
Phy1
MAC address 1st & 2nd bytes
hhhh
hhhh
h: 0~F in hex
E56
Phy2
MAC address 3rd & 4th bytes
hhhh
hhhh
h: 0~F in hex