3.3 Power Supply Precautions
Internally, the BASstat utilizes a half-wave rectifier and can share the same AC power
source with other half-wave rectified devices. Sharing AC power with full-wave rectified
devices is NOT recommended. AC power sources that power several half-wave devices
have a common secondary connection called COMMON, LO, or GROUND. Connect the
HOT side of the secondary to the 24 VAC high side input on the BASstat and the LO side
to 24 VAC common.
WARNING:
Devices powered from a common AC source could be damaged if a mix of
half- wave and full-wave rectified devices are both present. If you are not sure of the type
of rectifier used by another device, do not share the AC source with it.
3.4 Wiring Diagram