
UM-15094500-AA0
Page 17
Occupancy Setting
There are several ways to define thermostat occupancy state. Note: Occupancy will be
detected by ESI contact by default.
•
Energy Savings Input (ESI) This is a dry contact input meant for communication
from a customer supplied occupancy sensor. (default)
•
Occupancy status (occupied/unoccupied) can be set by a BACnet supervisor
using writable object
ESI Contact Definition
[
BV14
]. “0” for occupied, and “1” for
unoccupied. E12/AV18 must be set with a value of 64 (disabled) in advance
(E12/AV18 is set as 0 by default)
•
User control of occupancy state is allowed from the SET button if E12/ AV18
Lock has the ESI Contact disabled. Pressing the SET button and UP/DOWN
buttons will toggle the occupancy state. Press SET button to confirm. The SET
button can work in conjunction with
BACnet occupancy Command
[
BV14
] on
last-write-wins basis. The SET button could be locked to limit user control (use
Lock
[
AV18
] BACnet object or (
LOC
) engineering menu item to lock SET
button). In this case only the BACnet supervisor can set occupancy states.
•
Occupancy Status
[
BI0
] is a read-only BACnet object indicating current
occupancy state -“0” for occupied, and “1” for unoccupied. (AV18 is set as 0 by
default).
•
When in unoccupied state, a Moon (
) icon will be displayed on the LCD and
the thermostat will change the set-point temperatures to the
Unoccupied Cool
and
Unoccupied Heat
setpoints
[
AV8 – 9
]. When the state changes back to
occupied, the thermostat will return to the occupied set-point values for
Cooling
and
Heating Temperature Setpoint
[
AV0, AV3
] and a sunlight icon (
) will be
displayed to indicate occupied state on LCD.
4.3 Engineering Mode Menu
Thermostat configuration can be performed using the engineering menu or by
controlling BACnet objects using a BACnet client tool such as Contemporary Controls
free
. It is highly suggested that engineering mode be
operated by trained installers only, because it is related to system parameters that will
affect the control results.
Operation of Engineering Menu
•
At power “ON”, press and hold both the UP and DOWN buttons simultaneously
for 5 seconds to enter Engineering Mode menu.
•
Press the UP or DOWN buttons to rotate through the menu items. The last item
loops back to first item at the end of items in menu. Press the MODE button to
enter a submenu item.
•
Press the UP or DOWN button to change the setting in the submenu item.
Press the MODE button to confirm the setting and return to menu item
selection. If no button is pressed for 10 seconds, the display will return to the