9.2
Universal Inputs
The universal inputs can individual be configured as:
Analog input AI (0..10V or 0..20mA)
Digital input DI (default)
The selected button represents the chosen function and is set after uploading.
9.2.1
Select receivers
The recipients receive the messages of the selected UI.
NOTE
: Selected UI users do not have any rights to send commands to the module.
9.2.2
Confirmation sequence
When the confirmation is enabled, the module sends the message to the selected users one by one with an
adjustable interval delay.
E.g. the sequence starts, the first phone number is addressed. When the delay time has expired, the next
phone number in the list is addressed, and so on until the last phone number in the list is addressed.
This can be repeated for selected number of times before the module stops the sequence.
The user who receives the message is able to stop the confirmation sequence by sending a chosen text (can be
left blank) to the module before the delay has expired. The module answers: ‘Confirmation ended
<timestamp>’
NOTE
: When a new status is reached on the UI, a new sequence is started and the old sequence is stopped
automatically.
When there are one or more email addresses in the user list, the email is sent only once to all email addresses
at the beginning of the sequence.
9.3
Analog inputs
Each analog input (AI) represents a scaled value from 0 to 100% (10V or 20mA). Within this scale threshold
values can be monitored.
9.3.1
Configuration
Configure the following items:
Name
The unit for the input feedback. E.g. litres (Ltr) or kilograms (kg).
Log this AI at a pre-set interval, see for interval settings.