GSM-PRO2
- 16 -
7
Log
7.1
Log
The module can keep log files with a maximum size of 100kB. Select an email address in the Log tab to auto
send a full log and continue logging.
When no email is selected and a log is 90% full the module sends a warning message to the users in the general
message tab. When the log is 100% full the module sends another warning message and then it stops logging
until downloaded and erased.
Each log can be viewed and erased while connected to the PC by clicking the button or remote by sending a
command.
7.1.1
Event log
When this log is enabled the module logs the following events:
•
Reached threshold limits on the AI inputs
•
Rising and falling flank on the digital inputs (DI)
•
Received messages
•
Sent messages
•
Data transmissions
•
OTA updates
•
Extension changes
When c
onnected, view this log by clicking ‘download event log’. View remote by sending:
evlog
directly
followed by a valid email address (e.g.
evlog
[email protected]). When ready, the module answers with a
confirmation message and the event log is received at the email address.
When connected erase the event log by clicking ‘erase event log’. Erase remote by sending:
evclr
. The module
answers with a confirmation message.
7.1.2
AI log
Choose the interval for the AI log:
•
10 min (5 days)
•
15 min (7.5 days)
•
20 min (10 days)
•
30 min (15 days)
•
45 min (22.5 days)
•
60 min (30 days)
The log duration in days is based on logging 1 AI.
When connected, view this log by clicking ‘download AI log’. View remote by sending:
ailog
directly followed by
a valid email address (e.g.
ailog
[email protected]). When ready the module answers with a confirmation
message and the AI log is received by the email address.
When connected, erase the event log by clicking ‘erase AI log’. Erase remote by sending:
aiclr
. The module
answers with a confirmation message.