VTop Control Valves
M/VTOP-M/E ed. 01 2020
3.3 – COVER REMOVAL
Figure 5: Cover Removal
ATTENTION
PSL202 AMS – PSL 210 AMS ( IP65 )
Remove the handwheel loosening it, pull the cover
upwards.
PSL214 AMS and PSL202- 210 AMS ( IP67 )
Remove the handwheel by loosening the locking
grub screw, remove the locking screws of the
actuator cover, pull the cover upwards.
For electrical connection, there is no need to remove
the cover.
PSL320 AMS – PSL 325 AMS ( IP65 )
Unscrew the locking screws of the actuator.
Pull the cover upwards.
3.4 - ELECTRICAL POWER SUPPLY
ATTENTION
The electrical connection work can only be carried out by authorised staff.
When electrical works are carried out, safety regulations must strictly be complied with, observe the
standards EN 60204-1 (VDE 0113 part 1) to guarantee staff safety.
The electrical supply lines must be adequately dimensioned for the maximum current required by the
actuator and must meet IEC 227 and IEC 245 standards.