29
Mounting and installation work
Minimum distances to be observed
To prevent the steam, that is emitting from the steam distributor, from condensing on downstream system
components, a minimum distance to the steam distributor must be observed (depends on the absorp-
tion distance "B
N
").
before/after constriction
after expansion
0.5 x B
N
(1.97")
50 mm
0.5 x B
N
before bend
before branch
1 x B
N
1 x B
N
before diffuser
before humidity controller/ humidity sensor
1 x B
N
5 x B
N