9
Product Overview
3
Product Overview
3.1
Models overview
Nortec RS steam humidifiers are available in
different housing sizes (S, M and L)
with
different heating
voltages
and
steam capacities ranging from 10 lbs/hr up to a maximum of 180 lbs/hr (5 ... 80 kg/h)
.
3.1.1 Units small ("S") and medium ("M")
Housing
size
Nortec
RS
208 V/1~
240 V/1~
480 V/1~
600 V/1~
208 V/3~
240 V/3~
480 V/3~
600 V/3~
lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h)
S
...10...
10.9 (4.9)
10.9 (4.9)
9.7 (4.4)
11.4 (5.2)
10.9 (4.9)
10.9 (4.9)
11.3 (5.1)
11.1 (5.0)
...15...
15.9 (7.2)
14.5 (6.6)
14.1 (6.4)
14.7 (6.7)
15.9 (7.2)
14.5 (6.6)
14.6 (6.6)
17.6 (8.0)
...20...
21.2 (9.6)
21.2 (9.6)
18.8 (8.5)
19.6 (8.9)
21.2 (9.6)
21.2 (9.6)
19.4 (8.8) 22.8 (10.3)
M
...30...
31.8 (14.4) 31.8 (14.4) 31.5 (14.3) 31.4 (14.2) 28.8 (13.1) 31.8 (14.4) 31.5 (14.3) 31.4 (14.2)
...45...
––
––
––
––
47.7 (21.6) 47.9 (21.7) 45.2 (20.5) 47.1 (21.4)
...65...
––
––
––
––
71.6 (32.5) 71.9 (32.6) 63.0 (28.6) 70.6 (32.0)
...90...
––
––
––
––
––
––
94.6 (42.9) 94.3 (42.8)
Fig. 1: Overview units small ("S") and medium ("M")
I/O
Driver board
Module A
Control
board
RFI
Heating voltage
Module A
Control voltage
Control signal
External Enable
Limiter signal
Safety chain
Remote indication
(optional)
Main
Module A