31
Mounting and installation work
5.4.4 Positioning and mounting of the blower packs (accessory BP)
The blower packs can either be mounted directly on the humidifier or separately above the humidifier
to the wall. To allow the steam coming from the blower pack to spread out evenly, without condensing
on obstacles (ceilings, joists, pillars, etc.), the following minimum dimensions must be observed when
selecting the location for the blower pack.
BP-Series blower pack
Capacity
5 lb/h
(2.2 kg/h)
10 lb/h
(4.5 kg/h)
20 lb/h
(9 kg/h)
30 lb/h
(13.6 kg/h)
50 lb/h
(22.7 kg/h)
75 lb/h
(34 kg/h)
100 lb/h
(45 kg/h)
Low Speed
Dimension "A" (min.)
9" (0.23 m) 18" (0.46 m) 75" (1.91 m) 86" (2.19 m) 174" (4.42 m) 189" (4.81 m) 248" (6.30 m)
Dimension "B" (min.)
12" (0.31 m)
48" (1.22 m) 84" (2.14 m)
High Speed
Dimension "A" (min.)
6" (0.16 m)
60" (1.53 m) 71" (1.81 m) 132" (3.36 m) 153" (3.89 m) 218" (5.54 m)
Dimension "B" (min.)
12" (0.31 m)
Dimension "C" (approx.)
90" (2.3 m)
Dimension "D" (approx.)
12" (0.31 m)
30" (0.77 m)
Dimension "E" (min.)
39.5" (1.0 m)
Dimension "E" (max.)
158" (4.0 m) – Condair recommends 79" (2.0 m)
The values in the table above are based on the following nominal conditions: 72 °F (22 ˚C), 40% RH.
The blower pack should not be installed near cold surfaces or where dew point may be reached.
Higher humidity or lower room temperature may require increased clearances.
Note: In order to achieve a uniform distribution of the humidity within the room, additional factors such as
the room size, the room height, etc., must be taken into consideration besides observing the minimum
distances for the blower packs. If you have questions concerning the direct room humidification, please
contact your Condair representative.
Further information is provided in the separate installation and operating instructions for the correspond-
ing blower pack.
A
C
B
D
D
C
B
E
D
D
A