45
Planning
Nortec RS
2596995_0_EN_1905
Figure 25:
o
F
15
20
25
30
35
40
45
-40
-35
-30
-25
-20
-15
-10
-5
0
5
-40
-31
-22
-13
-4
5
14
23
32
41
o
C
Setpoint Limit (% RH)
10
Outdoor Temperature
Default Temperature Setback
4.4.3.2 Space Distribution Control Design
When distributing steam directly into the conditioned environment the humidification system will require
a wall-mounted On/Off humidistat or transducer (RH sensor). Condair also recommends a high limit
switch. Environments with exterior walls should consider using an outdoor temperature sensor to prevent
condensation on windows/walls.
The following installation requirement must be observed when using humidity controllers in a space
distribution system:
Wall-mounted controls should be located in an area that is not exposed to infiltrating air, and where
there are no discharge diffusers or localized variations in temperatures.
2
1
Figure 26: Space Humidity Control Location
1 High limit switch (recommended)
2 Humidity controller (inside the space)