A.1
Sample Specification
1.1 Work Included:
a. Nortec RS Series resistive element humidifier[s] as indicated on drawing[s] and as indicated
on schedule[s].
b. Complete and operable humidification system [which meets applicable building codes]
c. Equipment start-up and project inspection by qualified factory trained representative.
1.2 Quality Assurance:
a. Certifications, C-UL US Listed.
b. ISO 9001-2008.
c. ANSI/NFPA 70 - National Electrical Code.
d. AHRI 640, “Standard for Commercial and Industrial Humidifiers.”
e. ASHRAE Standard 135 BACnet
1.3 Related Sections:
a. 23 Mechanical General
b. 23[ ] Piping Installation
c. 23[ ] Control System
1.4 Submittals:
a. Submit product data under provisions of Section 23. Include product description, model,
dimensions, component sizes, rough-in requirements, service sizes, and finishes. Include
rated capacities, operating weights, furnished specialties, and accessories.
b. Submit manufacturer’s installation instructions.
c. Submit operation and maintenance data.
d. Submit coordination drawings. Detail fabrication and installation of humidifiers. Include pip-
ing details, plans, elevations, sections, details of components, and dispersion tubes. Detail
humidifiers and adjacent equipment. Show support locations, type of support, weight on each
support, and required clearances.
e. Submit wiring diagrams including power, signal, and control wiring. Differentiate between
manufacturer-installed and field-installed wiring.
f. Submit water pressure requirements.
1.5 Schedules:
a. Refer to information contained in schedule[s] attached to this specification.
b. Humidifiers to be of type, capacity, and arrangement as listed in schedule[s].
c. Include accessories listed in schedule[s] and those accessories required for type of unit.