background image

SIGNALLING RELAYS

Relay terminology refers to the relay condition in the de-energised state, i.e. if a relay is Normally Open (NO) the 

 

wiring across Common and NO will be open when not energised and closed when energised. All signalling relays have 
changeover contacts for flexible configuration. The Smoke Screen E+ has 5 Low voltage signalling relays with change 
over volt free contacts rated at 1 amp max for:

Ready

• 

  (Energised when Ready).

Low Fluid

• 

 (Energised when Fluid OK).

UPS

• 

 (Energised when UPS OK or UPS Alert is disabled).

Verification

• 

 (Energises with the pump relay).

• 

Auxiliary

’ relay is normally configured as an extra timer relay initiated by an alarm.

MAINS POWER LOSS

(No UPS connected). When mains power is restored after a temporary power loss the unit will be ‘

Not Ready

’ for 

approximately 30 seconds even if the unit is still up to operating temperature. This is to allow the Hold-off PIR to 
stabilise and prevent the unit from firing in the event of a false panel alarm.

SMOKE PRODUCTION TIME 

The ‘Smoke On’ time can be set in 15 second increments up to a maximum of 10 minutes (parameter Level 1).  If the 
unit goes ‘

Not Ready

’ during alarm the system does not include the ‘

Not Ready

’ time in the ‘Smoke On’ time total.  

When the Smoke Screen goes ‘

Ready

’ again the smoke production restarts until elapsed time reaches the pre-set 

figure or the ‘

Set

’ contact is closed.

SMOKE TEST 

A 3-second smoke test can be made if the unit is ‘Ready’ and the ‘Set’ contact is open by:

Setting Smoke Test parameter in Level 2 to “On” (resets to ‘Off’ when the engineer PIN is entered or times out).

• 

Pressing and holding all 3 buttons (

• 

!

qp

).

The ‘On’ time is set by the manufacturer to 3 seconds in Level 3 “Smk Test”.

• 

AUDIBLE WARNINGS

The Smoke Screen ‘beeps’ during the ‘alert’ conditions detailed in the “Status and Conditions” table. If the condition 
persists, the sounder repeats at an interval set in Level 1 parameter “Sound Rpt”. The sounder can be silenced for a 
period set in Level 1 parameter “Sound Sil” by a momentary contact closure on the sounder silence connections.

Summary of Contents for E+ Series

Page 1: ...E SERIES INSTALLATION AND OPERATORS MANUAL v2011 1 CAN T SEE IT CAN T STEAL IT...

Page 2: ...t Smoke Screen Limited 1 2 North End Swineshead Lincolnshire PE20 3LR Tel 44 01205 821111 Email info smoke screen co uk www smoke screen co uk IMPORTANT Please read this manual before commencing insta...

Page 3: ...f 40 years of continuous application development There is even a very good reason for the shape of the generators The E Series is exactly the right shape to be passed through a ceiling grid and mounte...

Page 4: ...inputs are open and the Hold off is open providing confirmation No Hold off attached Both Set and Trigger inputs are open If no Hold off is attached the Level 2 parameter HO Alarm on off should be cha...

Page 5: ...nt the unit from firing in the event of a false panel alarm SMOKE PRODUCTION TIME The Smoke On time can be set in 15 second increments up to a maximum of 10 minutes parameter Level 1 If the unit goes...

Page 6: ...old down the and p buttons to display Access Code 0 0 0 0 with a flashing cursor underline on the first digit Press q or p to select the first number Press to move to the second digit Repeat the above...

Page 7: ...On off On H O R e t r i g On off On A l a r m I g n o r e 0 to 9 half second increments 0 4 5 secs 1 T e m p D i s p l a y On off Off N e t w o r k A d d r 1 to 999 001 E n g i n e e r Engineer Code...

Page 8: ...ter a period with no button pressed in manual mode If any of the following conditions exist the display will alternate between the Ready Smoke display and the Conditions displays If more than one cond...

Page 9: ...m m h h d d m m Alarm Panel Off Closed Contacts P o n s s m m h h d d m m Panel Set On Open Contacts P o f f s s m m h h d d m m Panel Set Off Closed Contacts H O o n s s m m h h d d m m Hold off On O...

Page 10: ...djustment mode and check the following settings are correct Level 1 Smoke On Time 120 seconds Sound Rpt 5 min Sound Sil 2 hrs Aux Run 59 minutes Level 2 Smoke Test Off UPS Alarm Off On if UPS is fitte...

Page 11: ...ed Relay rated at 1A 24vDC Contacts close when Smoke activated Contacts close when UPS is OK or UPS Alert is disabled Contacts closed when fluid level low Contacts closed when ready Additional Informa...

Page 12: ...wFlu n o Ready n c Ready c Ready n o Notes Take care with Trigger and Set connections Do not cross connect ve and ve rails together PCB max output current is 250mA Alarm Panel Set Set Intruder Intrude...

Page 13: ...NSTALLATION GUIDE Wall mounting slot Cable entry Carry handle and suspension bracket fitting Mains cable LED Display Fluid bottle Door lock hold off optional Interface optional Intruder alarm panel ho...

Page 14: ...ceed to step 2 If the unit is to be mounted in the ceiling proceed to step 3 Fixing the mounting bracket First drill four holes using the mounting bracket as a template Then secure the bracket to the...

Page 15: ...ut Put two nuts and washers on each bar leaving enough space in between for the units mounting bracket ceiling false roof Fixing the mounting bracket First remove the handle on top of the unit using a...

Page 16: ...erfly nut and wiring case to expose a bank of connector blocks Carefully connect the wires to the corresponding connector block If no PIR is used link both Tamper PIR Finally the on board timer should...

Page 17: ...racket ELM HP bracket E S e r ie s b r a c k e t Ducting bracket E Series suspension kit Wall mounted E Series aerosol M8 studding Zebedee M8 large washer M8 large washer M8 nut Unistrut M8 studding M...

Page 18: ...Mounting Examples...

Reviews: