PROGRAMMING E+
(FRONT PANEL) - ENGINEER SETTINGS
AEROSOL AND FLUID BOTTLE VERSION
Connect all test connectors.
Ensure Trigger / Set switch is closed.
•
Ensure HO (Hold-off) switch is closed.
•
Power up E+.
Enter the parameter adjustment mode and check the following settings are correct:
Level 1
Smoke On Time :
120 seconds.
Sound Rpt:
5 min.
Sound Sil:
2 hrs.
Aux Run:
59 minutes.
Level 2
Smoke Test:
Off.
UPS Alarm:
Off (On if UPS is fitted).
HO Alarm:
On (Off if no Hold Off fitted).
HO Retrigger:
On.
Alarm Ignore:
1 (usual setting, i.e. 0.5 seconds).
Temp Display:
Off (if used at On, leave Off when finished).
Network Address:
001.
Engineer:
1993 (change if required).