- 24 -
Symptom
Possible cause
What to do
The thermostat
does not control
the gas heater
at all.
The thermostat has
not been connected
to the gas heater
properly.
Check the connection
between
KonvekPRO
and the
thermostat, especially that
you have connected the
appropriate connection points
to
KonvekPRO
.
Check LEDs on the top
of
KonvekPRO
and the
temperature of the probe that
protrudes from
KonvekPRO
.
In normal operation, when the
gas heater is not heating, the
probe is lukewarm (approx.
30 °C) and the orange LED
alternately is on and goes out.
If this is not the case
remove the cable leading
to the thermostat from the
KonvekPRO
. If the LED is on
periodically and the probe
warms up the defect is in the
connection to the thermostat
or in the thermostat.
Try to connect the thermostat
again, making sure that the
two wires of the cable do not
touch.