- 20 -
the range between 25 °C and 35 °C through the
calibration slot at the bottom of
KonvekPRO
.
5.4.
Wait 20 to 30 minutes so that the system
assumes its operating temperature.
5.5.
Turn the temperature regulating knob of
your gas heater very slowly towards higher
temperatures. When the switching threshold
value set on
KonvekPRO
is reached the gas
heater ignites. This probably will happen near
the maximum grade. If the gas heater fails to
ignite then it means
KonvekPRO
has heated the
probe above the temperature limit that can be
sensed by the gas heater. It does not present
any problem just the response time of the
system (the period of time that elapses between
the arrival of the heat command coming from
the thermostat and the actual point of time
when the gas heater switches on) is increased
somewhat.