![Compressed Air Alliance POM200 User Manual Download Page 6](http://html1.mh-extra.com/html/compressed-air-alliance/pom200/pom200_user-manual_2647447006.webp)
Power Meter
–
POM200
User Manual v1
www.compressedairalliance.com
6
Note
: The accuracy of
the power meter is
affected by the quality of
installation. On-site
conditions such as oil,
high humidity or other
impurities can also affect
the accuracy of the
power meter
Rated current
500A (0.5% from 10A to 600A)
3,000A (0.5% from 30A to 3600A)
10kA (0.5% from 100A to 12kA)
Rogowski coil
specification
85mV/kA@50Hz±0.5%
Voltage
0.2% from 100V to 500V
(L-L and L-N)
Power factor
±0.005 from 10% to 120%
Active/Apparent
Power
IEC62053-22 Class 0.5
Reactive power
IEC62053-21 Class 2
Frequency
0.01% from 45 to 65Hz
Active energy
IEC62053-22 Class 0.5s
Reactive energy IEC62053-21 Class 2
Maximum value measured
Parameter
Range
Resolution (number of decimal
points)
Voltage
0.001 V
999.9 V
999.9 kV
999.9 MV
0.1
Current
999.9 A
999.9 kA
0.1
Power
999.9 kW
999.9 MW
0.1
Power factor
0.999
0.001
THD
99.9%
0.1%
Energy
999.9 Wh
999.9 kWh
999.9 MWh
999.9 GWh
0.1
Summary of Contents for POM200
Page 1: ...www compressedairalliance com 1 User Manual Power Meter Din Rail with Display Model POM200...
Page 19: ...Power Meter POM200 User Manual v1 www compressedairalliance com 19 3PH4W no VT...
Page 20: ...Power Meter POM200 User Manual v1 www compressedairalliance com 20 3PH4W with VT...
Page 21: ...Power Meter POM200 User Manual v1 www compressedairalliance com 21 3PH3W no VT 3PH3W with VT...
Page 22: ...Power Meter POM200 User Manual v1 www compressedairalliance com 22 1PH3W 1PH2W...
Page 23: ...Power Meter POM200 User Manual v1 www compressedairalliance com 23 Input Output Wiring diagram...