Power Meter
–
POM200
User Manual v1
www.compressedairalliance.com
49
Set Power System
Command
Number
Action
R/W
Size
Type
Units
Range
Description
1003
Write (W)
1
UInt16
-
0,1,2,3,4
Wiring
0 = 1PH2W L
–
N
1 = 1PH2W L
–
L
2 = 3PH4W
3 = 3PH3W
4 = 1PH3W_LLN
Write (W)
1
UInt16
Hz
50,60
Nominal Frequency
VT Primary
Write (W)
2
UInt32
V
>0
VT Secondary
=RealValue*1000
Write (W)
2
UInt32
V
>0
CT Primary
Write (W)
2
UInt32
A
>0
CT Secondary
=RealValue*1000
Write (W)
2
UInt32
mV
>0
Rcoil Primary
Write (W)
2
UInt32
A
>0
Rcoil Secondary
=RealValue*1000
Write (W)
2
UInt32
mV
>0
Voltage Connection
0 = Direct Connect
1 = 3 VT
Write (W)
1
UInt16
-
0,1
Current Connection
0 = Rogowski coil
1 = CT