![Compressed Air Alliance POM200 User Manual Download Page 11](http://html1.mh-extra.com/html/compressed-air-alliance/pom200/pom200_user-manual_2647447011.webp)
Power Meter
–
POM200
User Manual v1
www.compressedairalliance.com
11
Rogowski Coil Specifications
500 Amps
1,000 Amps
3,000 Amp
Coil Length
200 mm or 7.87”
350 mm or 13.78”
510 mm or 20.08”
Window Size
50 mm or 1.97”
100 mm or 3.94”
150 mm or 5.91”
Ratio
Calibrated:
85mV / kA@50Hz / 100mV / kA@50Hz
Uncalibrated:
110mV / kA@50Hz
Read Accuracy
Calibrated:
<0.5% (central position, 25
℃
)
Uncalibrated:
< 5% tolerance (central position, 25
℃
)
Maximum Current
Measurable
100kA
Coil Resistance
from 100 to 250 Ω
Position Error
±1% maximum
Phase error
≤0.5°
Shielded
00% coil, 100% output cable
Couplings
PA6 UL 94 V-O rated
Voltage Insulation
Coil: 3000V
Signal cable: 1000V
Compliance
LVD EN 61010-1:2010
EMC EN 61326-1:2013
Safety
1000V CATIII ,600V CATIV
Materials
Coil & cable: Thermoplastic rubber, flame retardant UL 94
V-0 rated
Lead Length
5 meters
Operation
Temperature
-20
℃
to +70
℃
-4°F to 158°F
Storage Temperature
-30
℃
to +90
℃
-22°F to 194°F
Installation Type
Temporary or permanent installation
Warranty
12 months
Summary of Contents for POM200
Page 1: ...www compressedairalliance com 1 User Manual Power Meter Din Rail with Display Model POM200...
Page 19: ...Power Meter POM200 User Manual v1 www compressedairalliance com 19 3PH4W no VT...
Page 20: ...Power Meter POM200 User Manual v1 www compressedairalliance com 20 3PH4W with VT...
Page 21: ...Power Meter POM200 User Manual v1 www compressedairalliance com 21 3PH3W no VT 3PH3W with VT...
Page 22: ...Power Meter POM200 User Manual v1 www compressedairalliance com 22 1PH3W 1PH2W...
Page 23: ...Power Meter POM200 User Manual v1 www compressedairalliance com 23 Input Output Wiring diagram...